Plan Review Details - Permit 21100991
Plan Review Stops For Permit 21100991
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 12:43 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 12:43 Sent To  
Notes
2021-10-27 12:44:09SEE THE SEPARATE DEMO PERMIT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 12:44 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 12:44 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By lcrespo Date 2021-10-27 Time 11:50 Rev Time 0.00
Received By jleahy Date 2021-10-27 Time 11:50 Sent To  
Notes
2021-10-27 10:20:50 
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By pleduc Date 2021-11-01 Time   Rev Time 0.00
Received By pleduc Date 2021-11-01 Time 11:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By pleduc Date 2021-10-26 Time   Rev Time 0.00
Received By pleduc Date 2021-10-26 Time 09:54 Sent To  
Notes
2021-10-26 10:20:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THEE IS AN INDICATION OF NEW FLOORING WITH AN
 UNDERLAYMENT; HOWEVER, THE NEW FLOORING TYPE OR PRODUCT
 IS NOT PROVIDED.
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS
 MANUFACTURED FROM AROUND THE WORLD AND NOT ALL ARE
 TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101, CH 30
  
 30.3.3.3 INTERIOR FLOOR FINISH.
 30.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
  
 10.2.7* INTERIOR FLOOR FINISH TESTING AND
 CLASSIFICATION.
 10.2.7.1* CARPET AND CARPET LIKE INTERIOR FLOOR
 FINISHES SHALL
 COMPLY WITH ASTM D 2859, STANDARD TEST METHOD FOR
 IGNITION
 CHARACTERISTICS OF FINISHED TEXTILE FLOOR COVERING
 MATERIALS.
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 10.2.7.4 INTERIOR FLOOR FINISHES SHALL BE GROUPED IN
 THE CLASSES SPECIFIED
 IN 10.2.7.4.1 AND 10.2.7.4.2 IN ACCORDANCE WITH THE
 CRITICAL RADIANT FLUX
 REQUIREMENTS.
 10.2.7.4.1 CLASS I INTERIOR FLOOR FINISH. CLASS I
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.45 W/CM2, AS DETERMINED
 BY THE TEST DESCRIBED IN 10.2.7.3.
 10.2.7.4.2 CLASS II INTERIOR FLOOR FINISH. CLASS II
 INTERIOR FLOOR FINISH
 SHALL HAVE A CRITICAL RADIANT FLUX OF NOT LESS THAN
 0.22 W/CM2, BUT LESS
 THAN 0.45 W/CM2, AS DETERMINED BY THE TEST DESCRIBED IN
 10.2.7.3.
  
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED FLOORING
 INDICATING THE FIRE BEHAVIOR RATING.
  
  
  
 2) THERE ARE INDICATIONS OF NEW WALLS AND NEW SPACES;
 WITH ANY REMOVAL OF WALLS OR THE CREATION OF NEW WALLS,
 REQUIRES A CODE COMPLIANT SPRINKLER HEAD COVERAGE
 REVIEW BY A FIRE SPRINKLER CONTRACTOR.
  
 ANY REQUIRED FIRE SPRINKLER WORK SHALL BE DONE UNDER
 SEPARATE PERMIT AND SHOP DRAWINGS.
  
 SHOULD NO MODIFICATIONS BE REQUIRED, A SIGNED LETTER ON
 THEIR LETTERHEAD WILL BE REQUIRED AT THE TIME OF FIRE
 INSPECTION FOR
 THE FIRE INSPECTOR REVIEW AND VERIFICATION.
  
 PLEASE PROVIDE A NOTE OF ACKNOWLGMENT OF DEFERRED
 SUBMITTALS.
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-11-02 Time   Rev Time 0.00
Received By aoliver Date 2021-10-29 Time 09:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-28 Cont ID  
Sent By aoliver Date 2021-10-28 Time 10:09 Rev Time 0.00
Received By aoliver Date 2021-10-28 Time 10:07 Sent To  
Notes
2021-10-28 10:10:27ONE DOCUMENT UPLOADED W ERRORS, APPLICANT MUST
 RE-UPLOAD AO

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2021-10-25 Time 09:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By lcrespo Date 2021-10-27 Time 10:22 Rev Time 0.00
Received By lcrespo Date 2021-10-27 Time 10:19 Sent To  
Notes
2021-10-27 10:22:4510/27/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By ccole Date 2021-11-02 Time 10:33 Rev Time 0.00
Received By ccole Date 2021-11-02 Time 10:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By rmcphers Date 2021-10-27 Time 12:46 Rev Time 0.00
Received By rmcphers Date 2021-10-27 Time 12:46 Sent To  
Notes
***NONE***