Plan Review Details - Permit 21100937
Plan Review Stops For Permit 21100937
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-03 Cont ID  
Sent By cthroop Date 2022-03-03 Time 09:32 Rev Time 0.00
Received By cthroop Date 2022-03-03 Time 09:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-23 Cont ID  
Sent By cthroop Date 2021-12-23 Time 14:34 Rev Time 0.00
Received By cthroop Date 2021-12-23 Time 14:28 Sent To  
Notes
2021-12-23 14:38:32PLAN REVIEW BUILDING FLOORING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTE: APPLICATION IS FOR VINYL FLOORING. ASTM TEST
 REPORTS SUBMITTED FOR REVIEW ARE FOR LAMINATE WOOD
 FLOORING.
  
 1. PROVIDE THE FOLLOWING ASTM TEST REPORTS FOR VINYL
 FLOORING.
  
 FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE
 AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT
 INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45
 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E
 492.
  
 FBC 603.1 FLAME SPREAD SEC 803.1.1, PROVIDE TEST DATA
 IN ACCORDANCE WITH ASTM E 84 OR UL 723
 FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723
 FBC 804.4.1 TEST REQUIREMENT.
  
 2. PROVIDE SPECIFICATIONS FOR VINYL FLOORING.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-28 Cont ID  
Sent By cwalker Date 2022-01-28 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-04 Cont ID  
Sent By cwalker Date 2021-11-04 Time   Rev Time  
Received By cwalker Date   Time   Sent To  
Notes
2021-11-04 09:45:25PROVIDE INFORMATION ON THE CRITICAL RADIANT FLUX OF THE
 VINYL FLOOR FOR FLAME SPREAD AND SMOKE GENERATION NFPA
 101 10.2.7

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-03 Cont ID  
Sent By cthroop Date 2022-03-03 Time 09:32 Rev Time 0.00
Received By cthroop Date 2022-01-27 Time 07:11 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-23 Cont ID  
Sent By cthroop Date 2021-12-23 Time 14:38 Rev Time 0.00
Received By cthroop Date 2021-11-03 Time 09:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-12-23 Cont ID  
Sent By cthroop Date 2021-12-23 Time 14:38 Rev Time 0.00
Received By cthroop Date 2021-12-23 Time 14:38 Sent To  
Notes
***NONE***