Plan Review Details - Permit 21100899
Plan Review Stops For Permit 21100899
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-10-28 Cont ID  
Sent By cpuell Date 2021-10-28 Time 15:14 Rev Time 0.00
Received By cpuell Date 2021-10-28 Time 15:14 Sent To  
Notes
2021-10-28 15:15:31WORK IS BEING DONE ON THE FRONT MAIN PROPERTY. THE REAR
 HALF ADDRESS READDRESSED AS 735 NEW YORK ST

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By cpuell Date 2021-10-20 Time 16:02 Rev Time 0.00
Received By cpuell Date 2021-10-20 Time 16:01 Sent To  
Notes
2021-10-20 16:02:16WHICH BUILDING IS THE WORK TO BE DONE, NORTH OR SOUTH?
 THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-13 Cont ID  
Sent By cthroop Date 2021-11-13 Time 09:45 Rev Time 0.00
Received By cthroop Date 2021-11-13 Time 09:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By cthroop Date 2021-11-02 Time 16:58 Rev Time 0.00
Received By cthroop Date 2021-11-02 Time 12:25 Sent To  
Notes
2021-11-02 17:15:12BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. REF. THE WALL LEGEND ON PLAN PAGES A-1 AND A-2 FOR
 THE FOLLOWING COMMENT:
 THE WALL LEGEND SHOWS THE EXTERIOR LOAD BEARING WALLS
 TO BE REMOVED.
 PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 2. WINDOW TYPE ON PAGE A-2 STATES SINGLE HUNG WINDOWS.
 NOA 20-0519.09 IS FOR FIXED WINDOWS.
 PROVIDE PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 3. NOTE ON PAGE A-2 STATES PROVIDE NEW HURRICANE
 SHUTTER.
 SUBMIT A SCHEDULE FOR OPENING PROTECTIVE DEVICES OR
 ASSEMBLIES.
 SUBMIT PRODUCT APPROVALS FOR SHUTTERS.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 4. PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR
 NEW FIREPLACE.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 5. PROVIDE AN EXTERIOR WALL ELEVATION AND DETAIL. SHOW
 INTERIOR FINISH, WALL INSULATIUON AND EXTERIOR
 CLADDING.
 FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE
 PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD.
  
 6. REF. PLAN PAGE A-2 FOR THE FOLLOWING COMMENT:
 GROUND FLOOR PLAN HAS A CUT DETAIL 3&4/S-1. THERE IS NO
 S-1 PLAN TO REVIEW.
 PLEASE CLARIFY.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By jleahy Date 2021-10-27 Time 13:07 Rev Time 0.00
Received By jleahy Date 2021-10-27 Time 13:07 Sent To  
Notes
2021-10-27 13:09:04NO ELECTRICAL WORK TO BE DONE. JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By jleahy Date 2021-10-25 Time 08:34 Rev Time 0.00
Received By jleahy Date 2021-10-25 Time 08:34 Sent To  
Notes
2021-10-25 08:35:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO ELECTRICAL WORK SHOWN, PLEASE INDICATE ANY
 ELECTRICAL WORK TO BE DONE.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2021-10-26 Cont ID  
Sent By amhamilt Date 2021-10-26 Time 09:22 Rev Time 0.00
Received By amhamilt Date 2021-10-26 Time 09:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-13 Cont ID  
Sent By cthroop Date 2021-11-13 Time 09:45 Rev Time 0.00
Received By cthroop Date 2021-11-09 Time 08:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-03 Cont ID  
Sent By cthroop Date 2021-11-03 Time 09:46 Rev Time 0.00
Received By cthroop Date 2021-10-20 Time 11:52 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-11-10 Cont ID  
Sent By medwards Date 2021-11-10 Time 06:50 Rev Time 0.00
Received By medwards Date 2021-11-10 Time 06:50 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By medwards Date 2021-10-25 Time 07:47 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 07:47 Sent To  
Notes
2021-10-25 07:49:44SHEET A-2 REFERENCES MECHANICAL SHOP DRAWINGS, THESE
 WERE NOT SUBMITTED WITH THIS SUBMITTAL. PLEASE UPLOAD
 THE MECHANICAL DRAWINGS INDICATING THE ALL NEW
 MECHANICAL WORK FOR THIS PROJECT. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 14:45 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 14:09 Sent To  
Notes
2021-10-22 14:46:1410/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-13 Cont ID  
Sent By cthroop Date 2021-11-13 Time 09:45 Rev Time 0.00
Received By cthroop Date 2021-11-13 Time 09:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-20 Cont ID  
Sent By mpeterso Date 2021-10-20 Time 12:35 Rev Time 0.00
Received By mpeterso Date 2021-10-20 Time 12:35 Sent To  
Notes
2021-10-20 12:35:24REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE