Plan Review Details - Permit 21100781
Plan Review Stops For Permit 21100781
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By cpuell Date 2021-11-19 Time 12:19 Rev Time 0.00
Received By cpuell Date 2021-11-19 Time 12:19 Sent To  
Notes
2021-11-19 12:21:41BLDG ADDRESS OK FOR THE PROJECT, TENANT SPACES
 EFFECTED: 413, 423, 437, 447, 457 AND 473

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 11:11 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By rmcphers Date 2022-01-27 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 15:31 Sent To  
Notes
2022-01-27 15:32:39AN ASBESTOS SURVEY IS NOT REQUIRED - PLEASE PROVIDE THE
 SIGNED LETTER FROM THE CONTRACTOR AS NOTED --
  
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 12:53 Sent To  
Notes
2021-11-18 14:27:45PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 11:11 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By rmcphers Date 2022-01-27 Time 15:30 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 15:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 14:39 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 12:53 Sent To  
Notes
2021-11-18 14:30:45RETAIL BUILDING ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) STEEL COLUMN SHOWN ON DRAWING S-3.1.1 - PLEASE SHOW
 THE CONNECTION OF THE STEEL COLUMN TO THE CONCRETE DECK
 ABOVE. FBC WPB 107.2.1

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 08:09 Rev Time 0.00
Received By jleahy Date 2021-11-04 Time 16:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-27 Cont ID  
Sent By pleduc Date 2021-10-27 Time   Rev Time 0.00
Received By pleduc Date 2021-10-26 Time 14:32 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2021-11-08 Cont ID  
Sent By lcrespo Date 2021-11-08 Time 08:59 Rev Time 0.00
Received By lcrespo Date 2021-11-08 Time 08:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-23 Cont ID  
Sent By lmarchan Date 2022-02-23 Time 10:59 Rev Time 0.00
Received By lmarchan Date 2022-02-11 Time 11:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-02 Cont ID  
Sent By lmarchan Date 2022-02-02 Time 15:40 Rev Time 0.00
Received By lmarchan Date 2022-01-20 Time 09:08 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-19 Cont ID  
Sent By cpuell Date 2021-11-19 Time 12:21 Rev Time 0.00
Received By cpuell Date 2021-10-21 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-01-21 Cont ID  
Sent By medwards Date 2022-01-21 Time 08:15 Rev Time 0.00
Received By medwards Date 2022-01-21 Time 08:15 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-11-01 Cont ID  
Sent By medwards Date 2021-11-01 Time 10:53 Rev Time 0.00
Received By medwards Date 2021-11-01 Time 10:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-08 Cont ID  
Sent By lcrespo Date 2021-11-08 Time 08:22 Rev Time 0.00
Received By lcrespo Date 2021-11-03 Time 15:12 Sent To  
Notes
***NONE***

Review Stop P-GREASE GREASE INTERCEPTOR/TRAP REVIEW
Rev No 1 Status N Date 2021-11-08 Cont ID  
Sent By lcrespo Date 2021-11-08 Time 08:58 Rev Time 0.00
Received By lcrespo Date 2021-11-08 Time 08:58 Sent To  
Notes
2021-11-08 08:59:19A SEPARATE PERMIT APPLICATION AND REVIEW ARE
 REQUIRED FORM PLUMBING, ENGINEERING FOR THE GREASE
 INTERCEPTOR FOR THIS SCOPE OF WORK PER THE WPB
 AMENDMENTS TO THE FBC SEC. 105.1.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 11:11 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 11:11 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-18 Cont ID  
Sent By rmcphers Date 2021-11-18 Time 14:26 Rev Time 0.00
Received By rmcphers Date 2021-11-18 Time 14:26 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-02-22 Cont ID  
Sent By eschneid Date 2022-02-22 Time 16:45 Rev Time 0.25
Received By eschneid Date 2022-02-22 Time 16:13 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-02 Cont ID  
Sent By eschneid Date 2022-02-02 Time 13:44 Rev Time 0.50
Received By eschneid Date 2022-02-02 Time 11:59 Sent To  
Notes
2022-02-02 13:48:11FAILED
  
 1) THANK YOU FOR SHOWING THE MINI-SPLIT UNIT BEING
 REMOVED FROM THE REAR OF THE BUILDING. THE NOTES STATE
 THAT THIS WILL BE MOVED TO THE ROOF. PLEASE PROVIDE
 DRAWINGS, WITH DIMENSIONS, TO VERIFY THAT THE UNIT AND
 THE RACK IT IS INSTALLED ON WILL BE SCREENED FROM
 PUBLIC VIEW IN ACCORDANCE WITH THE CITYPLACE DRI
 REQUIREMENTS. THE LOCATION ON THE ROOF ALSO NEEDS TO BE
 SHOWN.
  
 2) THE EAST ELEVATION DRAWING SHOWS A 97 SF EXISTING
 WINDOW THAT DOES NOT EXIST (BETWEEN THE NEW 97 SF
 WINDOW AND THE 142 SF FUTURE STOREFRONT). THIS OPENING
 IS NOT SHOWN ON SHEET A1.1.2 THE SOUTH PARTIAL FLOOR
 PLAN, NOR IS IT SHOWN ON THE INTERIOR BUILDOUT PERMIT
 21101293 (NOTE AN ALTERNATE OPENING IS SHOWN AT THIS
 LOCATION). THE GLAZING SF SHOWN ON SHEET A3.0.1 IS
 INCORRECT AND THE REMOVAL OF THE NONEXISTING 97 SF
 OPENING WILL REDUCE THE PROVIDED GLAZING TO LESS THAN
 THE MINIMUM REQUIRED 60%. CORRECTLY SHOWING THE PERMIT
 2110293 PROPOSED GLAZING MAY RESULT IN MEETING THE 60%
 ALLOWANCE. CORRECT INFORMATION MUST BE SHOWN ON ALL THE
 PLANS. ADDITIONALLY, THE DIMENSIONS SHOWN ON THE SHELL
 PLAN DO NOT MATCH THE DIMENSIONS ON THE BUILD OUT PLAN.
 THE BUILD OUT SHOWS LESS WIDTH ON THE EXISTING WINDOW
 AND ON THE PROPOSED STOREFRONT. THIS WOULD RESULT IN
 NOT ENOUGH GLAZING.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-11-04 Cont ID  
Sent By eshneide Date 2021-11-04 Time 17:29 Rev Time 0.50
Received By eschneid Date 2021-11-04 Time 17:29 Sent To  
Notes
2021-11-04 17:30:38FAILED
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 2) IN ACCORDANCE WITH THE DEVELOPMENT ORDER FOR THE
 DEVELOPMENT AT 575 S. ROSEMARY, THE MINI SPILT SHOWN ON
 THE REAR OF THE BUILDING MUST BE REMOVED. THIS NEEDS TO
 BE DONE AS PART OF THIS DEMO PERMIT.
  
 3) ON SHEET A3.01, PLEASE INCLUDE THE UPDATED GLAZING
 CALCULATIONS FOR THE EAST FA?ADE WITH THE NEW
 STOREFRONTS BEING INSTALLED AS PART OF THIS PERMIT.
 ADDITIONALLY, THE NORTH FACADE IS MISLABELED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
 [email protected]