Plan Review Details - Permit 21100762
Plan Review Stops For Permit 21100762
Review Stop AD ADDRESSING
Rev No 5 Status P Date 2022-05-16 Cont ID  
Sent By cpuell Date 2022-05-16 Time 15:08 Rev Time 0.00
Received By cpuell Date 2022-05-16 Time 15:08 Sent To  
Notes
2022-05-16 15:09:53THIS BUILDING HAS BEEN GIVEN THE PRIMARY ADDRES OF 740
 N DIXIE HWY, RETAIL SPACES FROM SOUTH TO NORTH HAVE
 BEEN GIVEN THE FOLLOWING ADDRESSES: 712 N DIXIE HWY,
 714 N DIXIE HWY, 716 N DIXIE HWY, 718 N DIXIE HWY AND
 720 N DIXIE HWY, APARTMENTS UNITS HAVE BEEN APPROVED

Review Stop AD ADDRESSING
Rev No 4 Status F Date 2022-04-11 Cont ID  
Sent By cpuell Date 2022-04-11 Time 16:57 Rev Time 0.00
Received By cpuell Date 2022-04-11 Time 16:57 Sent To  
Notes
2022-04-11 16:57:45PREVIOUS COMMENTS NOT ADDRESSED

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-03-29 Cont ID  
Sent By cpuell Date 2022-03-29 Time 15:10 Rev Time 0.00
Received By cpuell Date 2022-03-29 Time 15:10 Sent To  
Notes
2022-03-29 15:10:49APPLICANT NEEDS TO CONTACT ADDRESSING FOR UNIT NUMBERS
 TO THE UPPER FLOORS TO BE APPROVED. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status P Date 2022-01-20 Cont ID  
Sent By cpuell Date 2022-01-20 Time 09:20 Rev Time 0.00
Received By cpuell Date 2022-01-20 Time 09:20 Sent To  
Notes
2022-01-20 09:22:21THIS BUILDING HAS BEEN GIVEN THE PRIMARY ADDRES OF 740
 N DIXIE HWY, RETAIL SPACES FROM SOUTH TO NORTH HAVE
 BEEN GIVEN THE FOLLOWING ADDRESSES: 712 N DIXIE HWY,
 714 N DIXIE HWY, 716 N DIXIE HWY, 718 N DIXIE HWY AND
 720 N DIXIE HWY, UPDATED PERMIT TO REFLECT THE NEW
 ADDRESS. APPLICANT INFORMED THAT THE APARTMENT UNIT
 NUMBERS NEED TO BE APPROVED BY THE ADDRESSING
 COORDINATOR.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By cpuell Date 2021-11-05 Time 14:22 Rev Time 0.00
Received By cpuell Date 2021-11-05 Time 14:22 Sent To  
Notes
2021-11-05 14:23:00PARCEL NEEDS TO BE READDRESSED SO THAT THE ENTRANCES ON
 THE GROUND FLOOR FALL IN LINE WITH THE CITY'S ROAD
 CENTER LINES. ADDRESSES THAT NEED TO BE ESTABLISHED
 WOULD BE FOR THE TWO BUILDINGS, THE GROUND FLOOR
 COMMERCIAL SPACE AND THE UNITS ON THE UPPER FLOORS.
 PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO
 WORK ON THE READDRESSING ISSUES.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status P Date 2022-03-08 Cont ID  
Sent By scwelter Date 2021-11-10 Time 14:58 Rev Time 0.00
Received By scwelter Date 2022-03-08 Time 14:48 Sent To  
Notes
2021-11-10 14:59:34REQUIREMENT COMPLETED 3.08.2022
  
 PUBLIC ART REQUIREMENT:
 TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 CONTACT SYBILLE WELTER, ADMINISTRATOR OF PUBLIC ART &
 CULTURE AT [email protected] TO OBTAIN AN ART ASSESSMENT
 APPLICATION AND REVIEW THE REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 13:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-09 Cont ID  
Sent By rmcphers Date 2022-03-09 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-03-08 Time 13:00 Sent To  
Notes
2022-03-09 13:52:30NEW RESIDENTIAL 8 STORY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05
 SHOULD BE 48" HIGH PER FBC 454.1.3.1.9
  
 2) PLEASE SEE THE EXCEPTIONS - THE FIRE RATING OF THE
 WALLS SHOULD BE THE SAME (STAIR AND CORRIDOR) - - STAIR
 NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED CORRIDOR
 - FBC 1023.3 TERMINATION.
 INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN
 EXIT DISCHARGE OR A PUBLIC WAY.
  
 EXCEPTIONS: 1.NOT MORE THAN 50 PERCENT OF THE NUMBER
 AND MINIMUM WIDTH OR REQUIRED CAPACITY OF INTERIOR EXIT
 STAIRWAYS AND RAMPS IS PERMITTED TO EGRESS THROUGH
 AREAS ON THE LEVEL OF DISCHARGE PROVIDED ALL OF THE
 FOLLOWING CONDITIONS ARE MET:
  
 1.2.THE ENTIRE AREA OF THE LEVEL OF EXIT DISCHARGE IS
 SEPARATED FROM AREAS BELOW BY CONSTRUCTION CONFORMING
 TO THE FIRE-RESISTANCE RATING FOR THE ENCLOSURE.
  
 1.3.THE EGRESS PATH FROM THE INTERIOR EXIT STAIRWAY AND
 RAMP ON THE LEVEL OF EXIT DISCHARGE IS PROTECTED
 THROUGHOUT BY AN APPROVED AUTOMATIC SPRINKLER SYSTEM.
 PORTIONS OF THE LEVEL OF EXIT DISCHARGE WITH ACCESS TO
 THE EGRESS PATH SHALL BE EITHER EQUIPPED THROUGHOUT
 WITH AN AUTOMATIC SPRINKLER SYSTEM INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2, OR
 SEPARATED FROM THE EGRESS PATH IN ACCORDANCE WITH THE
 REQUIREMENTS FOR THE ENCLOSURE OF INTERIOR EXIT
 STAIRWAYS OR RAMPS.
  
 1.4.WHERE A REQUIRED INTERIOR EXIT STAIRWAY OR RAMP AND
 AN EXIT ACCESS STAIRWAY OR RAMP SERVE THE SAME FLOOR
 LEVEL AND TERMINATE AT THE SAME LEVEL OF EXIT
 DISCHARGE, THE TERMINATION OF THE EXIT ACCESS STAIRWAY
 OR RAMP AND THE EXIT DISCHARGE DOOR OF THE INTERIOR
 EXIT STAIRWAY OR RAMP SHALL BE SEPARATED BY A DISTANCE
 OF NOT LESS THAN 30 FEET (9144 MM) OR NOT LESS THAN
 ONE-FOURTH THE LENGTH OF THE MAXIMUM OVERALL DIAGONAL
 DIMENSION OF THE BUILDING, WHICHEVER IS LESS. THE
 DISTANCE SHALL BE MEASURED IN A STRAIGHT LINE BETWEEN
 THE EXIT DISCHARGE DOOR FROM THE INTERIOR EXIT STAIRWAY
 OR RAMP AND THE LAST TREAD OF THE EXIT ACCESS STAIRWAY
 OR TERMINATION OF SLOPE OF THE EXIT ACCESS RAMP.
  
 3) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT
 ACCESS CORRIDORS SUCH AS GROUND FLOOR DOOR AT STAIR #3
 DOOR (S116) AND ELECTRIC. ROOM DOOR (S126.1) COMPLY
 WITH FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 4) DRAWING A-10.2.2 - UNIT C3 - PLEASE SHOW THAT THE
 WALLS AROUND THE SHOWER AT THE FAUCET REQUIRE GRAB BAR
 BACKING FBC ACCESSIBILITY FAIR HOUSING.
  
 5) ON THE UNIT PLAN THE CORRIDOR WALLS ARE MARKED AS
 WALL #4 - THE WALL SCHEDULE FOR WALL #4 DOES NOT SHOW
 THE REQUIRED STC REQUIREMENT. PLEASE SHOW HOW THE STC
 SOUND RATING IS PROVIDED FOR THE WALLS - WHERE REQUIRED
 PER FBC 1207.2 AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90.
  
 6) ON THE UNIT PLANS SOME OF THE WALLS BETWEEN THE
 CORRIDOR AND UNITS ARE SHOWN TO BE FIRE RATED SOME ARE
 NOT - PLEASE CORRECT.
  
 7) THE EGRESS CORRIDOR BESIDE STAIR #3 SHOWS THE FLOOR
 TO BE RAMPED AND ALSO SHOWS STAIR ON THE RAMP - PLEASE
 CLARIFY
  
 8) DRAWING A-5.2.2 DETAIL 13 - SHOWS GRAB BAR HEIGHT AT
 3'3" - TYPO?
  
 9) THE STRUCTURAL DRAWINGS NEED TO SHOW - - THRESHOLD
 BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT 110.8.4.4
 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By rmcphers Date 2021-12-21 Time 14:27 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 15:01 Sent To  
Notes
2021-12-21 14:22:39NEW RESIDENTIAL 8 STORY
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT).
  
 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, ROOFING SYSTEMS ETC. - ALL PRODUCT APPROVALS
 NEED TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD FBC WPB 107.3.4
  
 3) POOL BARRIER GATE SHOWN ON DRAWING 064 L3-4-05
 SHOULD BE 48" HIGH PER FBC 454.1.3.1.9
  
 4) STAIR NUMBER 3 SHOULD NOT TERMINATE AT A 1 HR RATED
 CORRIDOR - FBC 1023.3 TERMINATION.
 INTERIOR EXIT STAIRWAYS AND RAMPS SHALL TERMINATE AT AN
 EXIT DISCHARGE OR A PUBLIC WAY.
  
 5) PLEASE SHOW THAT DOORS THAT OPEN INTO THE EXIT
 ACCESS CORRIDORS SUCH AS DOOR S226, SX25 ETC. COMPLY
 WITH FBC 1005.7.1 DOORS.
 DOORS, WHEN FULLY OPENED, SHALL NOT REDUCE THE REQUIRED
 WIDTH BY MORE THAN 7 INCHES (178 MM). DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY MORE
 THAN ONE-HALF.
  
 6) DRAWING A-10.2.1 - UNIT A4 - PLEASE SHOW THAT THE
 WALLS AROUND THE TOILET REQUIRE GRAB BAR BACKING FBC
 ACCESSIBILITY FAIR HOUSING.
  
 7) PLEASE SHOW HOW THE STC SOUND RATING IS PROVIDED FOR
 THE WALLS - WHERE REQUIRED PER FBC 1207.2 AIRBORNE
 SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90.
  
 8) FOR THE FINISH FLOORING IN THE UNITS ABOVE THE 1ST
 FLOOR - OTHER THAN CARPET - 1) THE FOLLOWING ACUSTICAL
 TEST REPORTS ARE REQUIRED:
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 9) DEFERRED SUBMITTALS NEED TO BE LISTED ON THE
 DRAWINGS - FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 10) PLEASE SHOW COMMON AREA RESTROOM WALLS AND BASE
 BOARDS TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,
 FBC 1210.2.1FLOORS AND WALL BASES.
 IN OTHER THAN DWELLING UNITS, TOILET, BATHING AND
 SHOWER ROOM FLOOR FINISH MATERIALS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE. THE INTERSECTIONS OF SUCH
 FLOORS WITH WALLS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT VERTICAL BASE THAT EXTENDS UPWARD ONTO THE
 WALLS NOT LESS THAN 4 INCHES (102 MM). (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 11) PLEASE SHOW THE WIDTH OF STAIR NUMBER 3 - FBC
 1011.2 WIDTH AND CAPACITY.
 THE REQUIRED CAPACITY OF STAIRWAYS SHALL BE DETERMINED
 AS SPECIFIED IN SECTION 1005.1, BUT THE MINIMUM WIDTH
 SHALL BE NOT LESS THAN 44 INCHES (1118 MM).
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-05-05 Cont ID  
Sent By jleahy Date 2022-05-05 Time 16:42 Rev Time 0.00
Received By jleahy Date 2022-05-05 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-28 Cont ID  
Sent By jleahy Date 2022-03-24 Time 16:18 Rev Time 0.00
Received By jleahy Date 2022-03-24 Time 16:18 Sent To  
Notes
2022-03-28 08:33:50FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 700.3(F) TEMPORARY SOURCE OF POWER FOR MAINTENANCE OR
 REPAIR OF THE ALTERNATE SOURCE OF POWER. IF THE
 EMERGENCY SYSTEM RELIES
 ON A SINGLE ALTERNATE SOURCE OF POWER, WHICH WILL BE
 DISABLED FOR MAINTENANCE OR REPAIR, THE EMERGENCY
 SYSTEM SHALL INCLUDE
 PERMANENT SWITCHING MEANS TO CONNECT A PORTABLE OR
 TEMPORARY ALTERNATE SOURCE OF POWER, WHICH SHALL BE
 AVAILABLE FOR THE
 DURATION OF THE MAINTENANCE OR REPAIR. THE PERMANENT
 SWITCHING MEANS TO CONNECT A PORTABLE OR TEMPORARY
 ALTERNATE SOURCE
 OF POWER SHALL COMPLY WITH THE FOLLOWING:
 (1) CONNECTION TO THE PORTABLE OR TEMPORARY ALTERNATE
 SOURCE OF POWER SHALL NOT REQUIRE MODIFICATION OF THE
 PERMANENT
 SYSTEM WIRING.
 (2) TRANSFER OF POWER BETWEEN THE NORMAL POWER SOURCE
 AND THE EMERGENCY POWER SOURCE SHALL BE IN ACCORDANCE
 WITH
 700.12.
 (3) THE CONNECTION POINT FOR THE PORTABLE OR TEMPORARY
 ALTERNATE SOURCE SHALL BE MARKED WITH THE PHASE
 ROTATION AND
 SYSTEM BONDING REQUIREMENTS.
 (4) MECHANICAL OR ELECTRICAL INTERLOCKING SHALL PREVENT
 INADVERTENT INTERCONNECTION OF POWER SOURCES.
 (5) THE SWITCHING MEANS SHALL INCLUDE A CONTACT POINT
 THAT SHALL ANNUNCIATE AT A LOCATION REMOTE FROM THE
 GENERATOR
 OR AT ANOTHER FACILITY MONITORING SYSTEM TO INDICATE
 THAT THE PERMANENT EMERGENCY SOURCE IS DISCONNECTED
 FROM
 THE EMERGENCY SYSTEM. IT SHALL BE PERMISSIBLE TO
 UTILIZE MANUAL SWITCHING TO SWITCH FROM THE PERMANENT
 SOURCE OF POWER TO THE PORTABLE OR TEMPORARY
 ALTERNATE SOURCE OF POWER AND TO UTILIZE THE SWITCHING
 MEANS FOR CONNECTION OF A LOAD BANK.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By jleahy Date 2022-01-06 Time 10:52 Rev Time 0.00
Received By jleahy Date 2022-01-05 Time 16:03 Sent To  
Notes
2022-01-06 11:01:19ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E.5.2.1
  
 1) FEED TO FIRE PUMP CONTROLLER SHOWS NO WIRE SIZES
 FROM FPL TRANSFORMER.
  
 2) FAULT CURRENT CALCULATION NOT SHOWN FOR SERVICE AND
 FEEDERS. 110.9, 110.10
  
 3) EMERGENCY RISER NOT SHOWN. PLEASE INDICATE THE WIRE
 SIZES ON THE RISER.
  
 4) PANEL UDP HAS 1200, AND 2000 AMPERE MAINS PLEASE
 SHOW HOW 240.87 COMPLIANCE WILL BE HANDLED.
 PANEL DPS HAS A 1400 AMPERS MAIN PLEASE SHOW HOW 240.87
 COMPLIANCE WILL BE HANDLED.
  
 5) RISER SHOWS ELEVATOR 1 AND 2 BUT PLANS ONLY SHOW
 ELEVATORS 3 AND 4.
  
 6) ELEVATORS ARE SHOWN BEING CONNECTED TO PANEL ERN
 WHICH IS NOT SHOWN ON THIS RISER.
  
 6) RISER DOES NOT SPECIFY WHAT SIZE GENERATOR IS BEING
 USED, GENERATOR PAGE E.7.2.3 SHOWS TWO GENERATORS?
  
 7) SEPARATE PERMITS ARE REQUIRED FOR THE FOLLOWING
 SYSTEMS. LOW VOLTAGE, FIRE ALARM, GENERATOR, POOL, BDA
  
 PAGE E4.2.1
  
 1) UNITS A1, A1.1, A2, A3 NEED ADDITIONAL OUTLETS IN
 KITCHEN BETWEEN STOVE AND SINK. 210.52
  

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2022-05-16 Cont ID  
Sent By rrossano Date 2022-05-16 Time   Rev Time 0.00
Received By rrossano Date 2022-05-16 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2022-04-13 Cont ID  
Sent By rrossano Date 2022-04-13 Time   Rev Time 0.00
Received By rrossano Date 2022-04-13 Time   Sent To  
Notes
2022-04-13 12:38:57UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-02-28 Cont ID  
Sent By rrossano Date 2022-02-28 Time   Rev Time 0.00
Received By rrossano Date 2022-02-28 Time   Sent To  
Notes
2022-02-28 08:35:27UNDER FORMAL ENGINEERING SUBMITTAL REVIEW.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-11-08 Cont ID  
Sent By rrossano Date 2021-11-08 Time   Rev Time  
Received By rrossano Date 2021-11-08 Time   Sent To  
Notes
2021-11-08 11:57:29FORMAL ENGINEERINMG SUBMITTAL IS REQUIRED.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-03 Cont ID  
Sent By pleduc Date 2022-03-03 Time   Rev Time 0.00
Received By pleduc Date 2022-02-28 Time 16:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By pleduc Date 2021-11-23 Time   Rev Time 0.00
Received By pleduc Date 2021-11-23 Time 14:42 Sent To  
Notes
2021-11-23 14:54:33THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 1.2 - THERE IS ARE INDICATIONS OF 2 EXITS
 FROM THE POOL DECK WITH 46" WIDTH AST EACH EXIT.
  
 THE TOTAL OCCUPANCY PROPOSED IS 41 FOR THE POOL + 390
 FOR THE POOL DECK68 FOR THE LOUNGE = 499.
  
 THE TOTAL OCUPANCY LOAD FOR THE EXITS IS 46"X 2 /.2=
 460.
  
 THERE IS INSUFFICIENT EXIT WIDTH FOR THE POOL DECK.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE A DETAIL
 NARRATIVE, CODE REFERNECES AND DETAILED OCCUPANCY LOAD
 CALCULATIONS.
  
  
  
 2) SHEET C 17 - ALL FIRE LINE UNDERGROUND INCLUDING
 FDC, DDCV AND PRIVATE FIRE HYDRANTS SHALL BE INSTALLED
 PER NFPA 24 BY A FLORIDA CERTIFIED UNDERGROUND
 CONTRACTOR AND UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGMENT.
  
  
  
 3) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE
 FOR EMERGENCY RADIO COMMUNICATIONS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
 24.9.1 GENERAL.
 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM
 CAPABLE
 OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON
 FREQUENCIES
 ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE
 INSTALLED
 WITHOUT PRIOR COORDINATION AND APPROVAL OF THE
 AUTHORITY
 HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL
 SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT
 DEGRADE
 THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM.
 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED
 FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
  
 4) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE
 FOR A FIRE ALARM SYSTEM.
  
 PER F.A.C. 61 G
  
 PLEASE PROVIDE FOR A FIRE LARM SYSTEM TO BE INSTALLED
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
  
 5) SHEET FIRE SPRINKLER - THERE IS NO INDICATION TO
 PROVIDE FOR A FIRE SPRINKLER SYSTEM.
  
 PER FLORIDA ADMINISTRATIVE CODE SECTION 61G15-32.004,
 FIRE PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE
 POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF
 APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT,
 CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR
 AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER
 SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA)
 AND ANY PERFORMANCE BASED INFORMATION SUCH AS
 PRE-ENGINEERED SYSTEMS.
  
 THIS INFORMATION SHALL BE PROVIDED IN THIS MASTER PERMI
 WITH SHOP DRAWINGS BEING SUBMITTED UNDER SEPARATE
 PERMIT.
  
 PLEASE PROVIDE THE REQUIRED FS DOCUMENTS IN PLAN
 DRAWINGS OR NARRATIVE FORM SIGNED AND SELAED BY THE
 EOR.
  
  
  
 6) SHEET A 2 2 1 - THERE IS AN INDICATION OF AN
 ELECTRIC FIRE PUMP AND A GENERATOR.
  
 PLEASE PROVIDE CLARIFICATION/VERIFICATION THAT THE FIRE
 PUMP IS BACKED-UP BY THE GENERATOR AS REQUIRED BY NFPA
 20 & 70.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-13 Cont ID  
Sent By lmarchan Date 2022-05-13 Time 09:29 Rev Time 0.00
Received By lmarchan Date 2022-04-07 Time 11:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-25 Cont ID  
Sent By aoliver Date 2022-03-25 Time 09:39 Rev Time 0.00
Received By aoliver Date 2022-02-24 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-10 Cont ID  
Sent By jleahy Date 2022-01-10 Time 09:38 Rev Time 0.00
Received By jleahy Date 2021-11-05 Time 12:53 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By lmarchan Date 2022-05-23 Time 14:02 Rev Time 0.00
Received By lmarchan Date 2022-05-02 Time 08:27 Sent To  
Notes
2022-05-23 10:22:09RECEIPT MU-2022-019864 - $844,474.02 PAID
2022-05-02 08:28:015/2/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By rmcphers Date 2021-12-21 Time 14:43 Rev Time 0.00
Received By rmcphers Date 2021-12-21 Time 14:43 Sent To  
Notes
2021-12-21 14:44:27PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-27 Cont ID  
Sent By medwards Date 2022-04-27 Time 06:54 Rev Time 0.00
Received By medwards Date 2022-04-27 Time 06:54 Sent To  
Notes
2022-04-27 06:55:49APPROVED WITH PRIVISO:
  
 BASED ON FMC 403.3.1.1 AND TABLE 403.3.1.1 THE OUTDOOR
 AIR REQUIRED FOR THE 1335 SQ FT WEIGHTROOM MUST BE A
 MINIMUM OF 360 CFMS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-11 Cont ID  
Sent By medwards Date 2022-03-11 Time 11:16 Rev Time 0.00
Received By medwards Date 2022-03-11 Time 11:15 Sent To  
Notes
2022-03-11 11:15:542ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21100762
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M-6.2.3: PLEASE USE THE OCCUPANCY
 CLASSIFICATION FROM TABLE 403.3.1.1 TO IDENTIFY THE
 FITNESS AREA AND THE YOGA ROOM I.E. HEALTH CLUB/WEIGHT
 ROOM OR HEALTH CLUB/AEROBICS ROOM. I CANNOT VERIFY THE
 OUTDOOR AIR CALCULATIONS UNTIL THESE OCCUPANCIES HAVE
 BEEN ADDED. PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS
 FOR EACH OCCUPANCY CLASSIFICATION BASED ON FBC M
 403.3.1.1 AND THEN TABLE 403.3.1.1. THE TABLE MUST BE
 USED AND NOT THE EGRESS OCCUPANT COUNT.
  
  
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By medwards Date 2021-11-30 Time 10:57 Rev Time 0.00
Received By medwards Date 2021-11-30 Time 08:43 Sent To  
Notes
2021-11-30 10:57:261ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100762
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-2.2.1: PLEASE ADD A NOTE ON THE DRAWING
 STATING THAT THE GENERATOR WILL REQUIRE A SEPARATE
 PERMIT APPLICATION AND PLAN REVIEW AS IT WILL NOT BE
 REVIEWED UNDER THIS PERMIT.
  
 2) SHEET M-2.2.5: PLEASE SHOW THE MECHANICAL UNITS WILL
 BE A MINIMUM OF 10 FEET FROM THE ROOFS EDGE OR MEET THE
 GUARDS REQUIREMENT IN FBC M 304.11
  
 3) THE DUCT WORK SERVING THE ELECTRICAL ROOMS ON EACH
 FLOOR IS PENETRATING A FIRE RATED WALL, PLEASE SHOW THE
 FIRE DAMPER FOR THESE PENETRATIONS ON EACH FLOOR. FBC M
 607
  
 4) PLEASE PROVIDE THE NATURAL VENTILATION CALCULATIONS
 FOR EACH UNIT. FBC M 402.2 AND 402.3
  
 5) PLEASE SHOW THE EXHAUST TERMINATION LOCATIONS ARE 3
 FEET FROM OPERABLE OPENINGS. FBC M 501.3
  
 6) SHEET M-4.2.1: UNIT MICRO, UNIT A2, UNIT A3, UNIT
 A4- PLEASE SHOW WHERE THE NATURAL VENTILATION SOURCE
 WILL BE IN THESE UNITS AS I DO NOT SEE ANY OPERABLE
 WINDOWS. FBC 402.2 AND 402.3
  
 7) SHEET M-4.2.2: UNIT C3, UNIT C3.2- PLEASE SHOW WHERE
 THE NATURAL VENTILATION SOURCE WILL BE IN THESE UNITS
 AS I DO NOT SEE ANY OPERABLE WINDOWS. FBC 402.2 AND
 402.3
  
 8) SHEET M-4.2.3: UNIT C4, UNIT C5- PLEASE SHOW WHERE
 THE NATURAL VENTILATION SOURCE WILL BE IN THESE UNITS
 AS I DO NOT SEE ANY OPERABLE WINDOWS. FBC 402.2 AND
 402.3
  
 9) SHEET M-4.1.2: UNIT B1 DRYER DUCT INDICATES A TOTAL
 OF 4 90 DEGREE ELBOWS AND 2 45 DEGREE ELBOWS. THE DRYER
 DUCT CHART SHOWN ON THE DRAWING DOES NOT PROVIDE A
 LENGTH FOR THIS DESIGN. PLEASE PROVIDE INFORMATION FROM
 THE DRYER MANUFACTURER SHOWING A DESIGN FOR THIS MANY
 90?S AND 45?S.
  
 10) SHEET M-4.1.2: PLEASE SHOW WHERE THE NATURAL
 VENTILATION SOURCE WILL BE IN UNITS B1 MASTER BEDROOM,
 UNIT C3 BOTH BEDROOMS. . FBC M 402.2 AND 402.3
  
 11) SHEET M-6.2.3: PLEASE PROVIDE OUTDOOR AIR
 CALCULATIONS BY IDENTIFYING EACH USE OF SPACE INCLUDING
 CORRIDORS BASED ON THE OCCUPANCY CLASSIFICATIONS OF FBC
 M TABLE 403.3.1.1 AND 403.3.1.1.
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-12-13 Cont ID  
Sent By abelisle Date 2021-12-13 Time 21:01 Rev Time 0.00
Received By abelisle Date 2021-12-13 Time 17:44 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-03-09 Cont ID  
Sent By rmcphers Date 2022-03-09 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-03-09 Time 14:02 Sent To  
Notes
2022-03-09 14:03:06ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By rmcphers Date 2021-12-21 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2021-12-21 Time 14:44 Sent To  
Notes
2021-12-21 14:45:08SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 13:26 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-09 Cont ID  
Sent By rmcphers Date 2022-03-09 Time 14:31 Rev Time 0.00
Received By rmcphers Date 2022-03-09 Time 14:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-21 Cont ID  
Sent By rmcphers Date 2021-12-21 Time 15:32 Rev Time 0.00
Received By rmcphers Date 2021-12-21 Time 15:32 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2022-05-06 Cont ID  
Sent By dbattles Date 2022-05-06 Time 11:17 Rev Time 0.00
Received By dbattles Date 2022-05-06 Time 11:17 Sent To  
Notes
2022-05-06 11:17:25RECEIVED THRESHOLD DOCUMENTATION.
 PACKET UPLOADED TO FILENET AND ORIGINAL TO STORAGE.

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2022-04-26 Cont ID  
Sent By rmcphers Date 2022-04-26 Time 13:19 Rev Time 0.00
Received By rmcphers Date 2022-04-26 Time 13:19 Sent To  
Notes
2022-04-26 13:21:03THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 A) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 B) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 C) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
  
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2022-03-09 Cont ID  
Sent By rmcphers Date 2022-03-09 Time 14:08 Rev Time 0.00
Received By rmcphers Date 2022-03-09 Time 14:08 Sent To  
Notes
2022-03-09 14:09:38THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
  
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By rmcphers Date 2021-12-21 Time 14:45 Rev Time 0.00
Received By rmcphers Date 2021-12-21 Time 14:45 Sent To  
Notes
2021-12-21 14:47:27THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
  
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2022-05-17 Cont ID  
Sent By aaponte Date 2022-05-17 Time 10:56 Rev Time 0.00
Received By aaponte Date 2022-05-17 Time 10:56 Sent To  
Notes
2022-05-17 10:58:48PROVISO:
 STREET LIGHT INCLUDED IN SHEET L8-401 SHALL BE CHANGED
 TO COMPLY WITH DOWNTOWN LIGHT STANDARDS.
 LANDSCAPE NOT INCLUDED IN THIS APPROVAL.
 MECHANICAL EQUIPMENT ON ROOF SHALL BE SCREENED WITH A
 WALL OR SCREENING AS TALL AS THE EQUIPMENT.

Review Stop Z ZONING
Rev No 3 Status F Date 2022-03-24 Cont ID  
Sent By aaponte Date 2022-03-24 Time   Rev Time 0.00
Received By aaponte Date 2022-02-24 Time   Sent To  
Notes
2022-03-24 09:01:481. SATISFIED. COMMENT FOR NORTH BUILDING - PREVIOUS
 COMMENT:SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSSED
 GARAGE DRIVEWAYS ON 8TH AND EUCALYPTUS. PLEASE INCLUDE
 DETAILS IN CIVIL DRAWINGS TO ENSURE COMPLIANCE.
 2. SATISFIED. A PORTION OF THE PUBLIC OPEN SPACE NEEDS
 TO BE INDICATED AS PRIVATE TO COMPLY WITH 25% REQUIRED.
 THE SPACE COULD REMAIN AS PART OF THE PUBLIC OPEN SPACE
 DESIGN, IT JUST NEEDS TO BE SHOWN IN THE CLASSIFICATION
 OF THE PRIVATE TO CONFIRM COMPLIANCE (SHEET A-03)
 3. SATISFIED. ALL CALCULATIONS AND INFORMATION ABOUT
 COMPLIANCE WITH THE OPEN SPACE REQUIREMENTS SHALL BE
 INCLUDED IN THE LANDSCAPE SUBMITTAL.
 4. SATISFIED. PLEASE PROVIDE PHOTOMETRICS TO CONFIRM
 THE 0.6 FOOTCANDLE MINIMUM REQUIRED AT THE CURB ONE
 FOOT ABOVE GRADE IS MET.
 5. SATISFIED. PLEASE ENSURE THE SFX SLIPFITTER IS BEING
 USED.- PREVIOUS COMMENT:PROPOSE STREET LIGHT FIXTURE
 DOES NOT MATCH DOWNTOWN STANDARD. LIGHT FIXTURE TO BE
 INSTALLED ALONG THE STREET SHALL MATCH THE DOWNTOWN
 STANDARD. PLEASE ADJUST.
 6. SATISFIED - COMMENT FOR NORTH BUILDING - PARKING
 SPACES FOR GUEST AND RETAIL SHALL BE INDICATED ON
 DRAWINGS AND SIGNS SHALL BE PROVIDED IN GARAGE. HOW DO
 GUESTS AND RETAIL CLIENTS GET ACCESS THROUGH THE GATE?
 7. SATISFIED.- PLEASE PROVIDE A COMPLETE ELEVATION OF
 THE BRIDGE.
 8. SATISFIED - PLEASE PROVIDE INFORMATION ON THE FDOT
 APPROVAL OF THE PROPOSED CHANGES ALONG DIXIE HIGHWAY.
 9. PARTIALLY SATISFIED - . 93.3 LF OF SEATING REQUIRED
 IN THE POS, PLEASE INDICATE HOW IS THE SEATING IS
 PROVIDED - PREVIOUS COMMENT:PLEASE PROVIDE INFORMATION
 ABOUT THE SEATING WITHN THE PUBLIC OPEN SPACE AND ANY
 PRIVATE OPEN SPACE LOCATED ALONG THE STREET.
 10. SATISFIED - PLEASE CONFIRM THAT THE SCORE LINE
 PATTERN INCLUDED IN THE SITE PLAN APPROVAL IS
 MAINTAINED.
 11. SATISFIED - PLEASE PROVIDE AN EXHIBIT INDICATING
 THE LOCATION OF ALL ABOVE GROUND UTILITY CONNECTIONS
 LOCATED ALONG THE FRONTAGE LINE. NO ABOVE GROUND
 UTILITIES CAN BE LOCATED WITHIN THE MINIMUM SETBACK.
 12.SATISFIED - A SEPARATE PERMIT SHALL BE SUBMITTED FOR
 LANDSCAPE, IRRIGATION AND STREET LIGHTS.
 13.SATISFIED - COMMENTS FOR NORTH BUILDING- PLEASE
 PROVIDE INFORMATION ABOUT THE PROPOSED LIGHTING INSIDE
 THE GARAGE TO CONFIRM THE SOURCE IS HIDDEN FROM
 EXTERIOR VIEW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  

Review Stop Z ZONING
Rev No 2 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-14 Cont ID  
Sent By aaponte Date 2022-01-14 Time 15:59 Rev Time 0.00
Received By aaponte Date 2022-01-14 Time 15:59 Sent To  
Notes
2022-01-14 16:01:361. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSSED
 GARAGE DRIVEWAYS ON 8TH AND EUCALYPTUS. PLEASE INCLUDE
 DETAILS IN CIVIL DRAWINGS TO ENSURE COMPLIANCE.
 2. A PORTION OF THE PUBLIC OPEN SPACE NEEDS TO BE
 INDICATED AS PRIVATE TO COMPLY WITH 25% REQUIRED. THE
 SPACE COULD REMAIN AS PART OF THE PUBLIC OPEN SPACE
 DESIGN, IT JUST NEEDS TO BE SHOWN IN THE CLASSIFICATION
 OF THE PRIVATE TO CONFIRM COMPLIANCE (SHEET A-03)
 3. ALL CALCULATIONS AND INFORMATION ABOUT COMPLIANCE
 WITH THE OPEN SPACE REQUIREMENTS SHALL BE INCLUDED IN
 THE LANDSCAPE SUBMITTAL.
 4. PLEASE PROVIDE PHOTOMETRICS TO CONFIRM THE 0.6
 FOOTCANDLE MINIMUM REQUIRED AT THE CURB ONE FOOT ABOVE
 GRADE IS MET.
 5. PROPOSE STREET LIGHT FIXTURE DOES NOT MATCH DOWNTOWN
 STANDARD. LIGHT FIXTURE TO BE INSTALLED ALONG THE
 STREET SHALL MATCH THE DOWNTOWN STANDARD. PLEASE
 ADJUST.
 6. PARKING SPACES FOR GUEST AND RETAIL SHALL BE
 INDICATED ON DRAWINGS AND SIGNS SHALL BE PROVIDED IN
 GARAGE. HOW DO GUESTS AND RETAIL CLIENTS GET ACCESS
 THROUGH THE GATE?
 7. PLEASE PROVIDE A COMPLETE ELEVATION OF THE BRIDGE.
 8. PLEASE PROVIDE INFORMATION ON THE FDOT APPROVAL OF
 THE PROPOSED CHANGES ALONG DIXIE HIGHWAY.
 9. PLEASE PROVIDE INFORMATION ABOUT THE SEATING WITHN
 THE PUBLIC OPEN SPACE AND ANY PRIVATE OPEN SPACE
 LOCATED ALONG THE STREET.
 10. PLEASE CONFIRM THAT THE SCORE LINE PATTERN INCLUDED
 IN THE SITE PLAN APPROVAL IS MAINTAINED.
 11. PLEASE PROVIDE AN EXHIBIT INDICATING THE LOCATION
 OF ALL ABOVE GROUND UTILITY CONNECTIONS LOCATED ALONG
 THE FRONTAGE LINE. NO ABOVE GROUND UTILITIES CAN BE
 LOCATED WITHIN THE MINIMUM SETBACK.
 12. A SEPARATE PERMIT SHALL BE SUBMITTED FOR LANDSCAPE,
 IRRIGATION AND STREET LIGHTS.
 13. PLEASE PROVIDE INFORMATION ABOUT THE PROPOSED
 LIGHTING INSIDE THE GARAGE TO CONFIRM THE SOURCE IS
 HIDDEN FROM EXTERIOR VIEW.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439