Plan Review Details - Permit 21100754
Plan Review Stops For Permit 21100754
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 10:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-10 Cont ID  
Sent By jwitmer Date 2021-11-10 Time 15:06 Rev Time 0.00
Received By jwitmer Date 2021-11-10 Time 15:29 Sent To  
Notes
2021-11-10 15:06:27TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
 AWNINGS
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-12-21 Cont ID  
Sent By jwitmer Date 2021-12-21 Time 10:02 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 11:01 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-30 11:01:14WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100754
 ADD: 610 CLEMATIS ST. # 426
 CONT: FLORIDA ALLIED CONTRACTOR SEVICES/ CGC
 TEL: 239-410-2276
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUES. NOV. 30TH/2021
 ACTION: DENIED
  
 1) 2ND REQUEST. THE RESPONSE LETTER INDICATES THE FLOOR
 FINISH IS TO BE DURALUX VINYL FLOORING. THE SUBMITTED
 SPEC ECO-ULTRA QUIET STATES TO BE USED WITH LAMINATE,
 ENGINEERED, BAMBOO AND SOLID HARDWOOD FLOORING NOT
 VINYL FLOORING.
  
 1ST ROUND OF COMMENTS. IN THE SCOPE OF WORK, IT IS NOT
 CLEAR IF IN THE BATHROOMS THE FLOOR TILE IS ALSO BEING
 REMOVED AND REPLACED. 107.2.1.2. ADDITIONAL INFORMATION
 IS REQUIRED. FLOOR INSULATION/ UNDERLAYMENT (FBC-B
 2020) FOR TILE, STONE, MARBLE, VINYL LAMINATE FLOORING
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 1C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1D) COMPLIED.
  
  
 2) COMPLIED
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-10 Cont ID  
Sent By jwitmer Date 2021-11-10 Time 15:29 Rev Time 0.00
Received By jwitmer Date 2021-11-10 Time 15:29 Sent To  
Notes
2021-11-10 15:28:55WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21100745
 ADD: 610 CLEMATIS ST. # 426
 CONT: FLORIDA ALLIED CONTRACTOR SEVICES/ CGC
 TEL: 239-410-2276
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. NOV. 10TH/2021
 ACTION: DENIED
  
 1) IN THE SCOPE OF WORK, IT IS NOT CLEAR IF IN THE
 BATHROOMS THE FLOOR TILE IS ALSO BEING REMOVED AND
 REPLACED. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020)
 FOR TILE, STONE, MARBLE, VINYL LAMINATE FLOORING AND
 WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 1D) PLEASE PROVIDE THE SQUARE FOOTAGE OF FLOORING BEING
 REPLACED. FLOORING VALUATION. THE PERMIT VERIFICATION
 OF VALUE COULD NOT OCCUR THIS REVIEW SINCE THE SQ. FT.
 AREA AND FLOOR PRODUCT NOR UNDERLAYMENT WERE NOT
 PROVIDED.
 109.3 BUILDING PERMIT VALUATION. IF, IN THE OPINION OF
 THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF
 BUILDING OR ALTERATION APPEARS TO BE UNDERESTIMATED ON
 THE APPLICATION, THE PERMIT SHALL BE DENIED.
  
  
 2) IN THE SCOPE OF WORK THE REMOVAL OF TUB AND INSTALL
 NEW SHOWER IT IS NOT MADE CLEAR IF THE EXISTING DRAIN
 IS TO BE USED OR NEW HOLE CORED THROUGH THE FLOOR.
  
 2A) POST TENSION SLAB/ NEW HOLES. THE PLAN IS SILENT AS
 IF THE LOCATION OF THE EXISTING TUB DRAIN IS GOING TO
 BE REUSED IN THE SAME LOCATION. IF NOT, THEN THE FLOOR
 SLAB WILL NEED TO BE X-RAYED TO FIND THE POST TENSION
 CHORD LOCATIONS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2B) THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). IF A NEW FLOOR PENETRATION IS MADE FOR THE
 FUTURE SHOWER DRAIN, THEN YOU NEED TO SHOW COMPLIANCE
 WITH THE 2020 FBC-B SECTION 714.5.1.2.
 THROUGH-PENETRATIONS FIRESTOP SYSTEMS (HORIZONTAL
 ASSEMBLIES). THROUGH PENETRATIONS SHALL BE PROTECTED BY
 A THROUGH PENETRATION FIRESTOP SYSTEM INSTALLED IN
 ACCORDANCE WITH ASTM E814 OR UL 1479. THE SYSTEM SHALL
 HAVE AN F RATING / T RATING OF NOT LESS THAN 1 HOUR BUT
 NOT LESS THAN THE REQUIRED RATING OF THE FLOOR
 PENETRATED.
  
 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 16:02 Rev Time 0.00
Received By jleahy Date 2021-12-14 Time 15:59 Sent To  
Notes
2021-12-14 16:03:00NO ELECTRICAL WORK TO BE DONE PER RESPONSE LETTER TO
 THE CITY... JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 16:42 Rev Time 0.00
Received By jleahy Date 2021-11-15 Time 16:42 Sent To  
Notes
2021-11-15 16:43:29FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 NO ELECTRICAL WORK SHOWN JLEAHY
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-29 Cont ID  
Sent By pleduc Date 2021-11-29 Time   Rev Time 0.00
Received By pleduc Date 2021-11-29 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By pleduc Date 2021-10-22 Time   Rev Time 0.00
Received By pleduc Date 2021-10-22 Time 15:33 Sent To  
Notes
2021-10-22 15:36:36THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED VINYL FLOORING.
  
 VINYL FLOORING IS MANUFACTURED AROUND THE WORLD AND NOT
 ALL ARE TESTED AND MEETING LISTED AND NFPA STANDARDS.
  
 PER NFPA 101
  
 10.2.7.2* FLOOR COVERINGS, OTHER THAN CARPET FOR WHICH
 10.2.2.2
 ESTABLISHES REQUIREMENTS FOR FIRE PERFORMANCE, SHALL
 HAVE A
 MINIMUM CRITICAL RADIANT FLUX OF 0.1 W/CM2.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE PRODUCT
 SPEC SHEETS OF THE PROPOSED FINISHED
 VINYL FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THERE ARE INDICATIONS THAT THE BATHROOM WALLS ARE
 FIRE RATED TENANT/CORRIDOR SEPARATION WALLS.
  
 ENSURE FIRE RATED TENANT SEPARATION WALLS ARE REPAIRED
 TO THE EXISTING FIRE RATED SEPARATION.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 3) FOR THE KITCHEN WORK, PROTECT FIRE SPRINKLERS AND
 FIRE ALARM DEVICES AND EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 PROVIDE AN APPLICABLE NOTE OF ACKNOWLEDGMENT.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-12-21 Time   Rev Time 0.00
Received By aoliver Date 2021-12-17 Time 08:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 16:03 Rev Time 0.00
Received By jleahy Date 2021-11-24 Time 08:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 16:46 Rev Time 0.00
Received By jleahy Date 2021-10-19 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-03 Cont ID  
Sent By lcrespo Date 2021-12-03 Time 17:11 Rev Time 0.00
Received By lcrespo Date 2021-12-03 Time 17:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By lcrespo Date 2021-11-02 Time 06:42 Rev Time 0.00
Received By lcrespo Date 2021-11-02 Time 06:23 Sent To  
Notes
2021-11-02 06:42:1211/02/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THIS BUILDING WAS CONSTRUCTED UNDER THE FAIR HOUSING
 ACT. PLEASE INDICATE ON PLANS WHICH DESIGN
 SPECIFICATION ( ?A? OR ?B? OF THE ACT) WAS USED IN THE
 ORIGINAL DESIGN OF THESE UNITS. TELL US WHICH USABLE
 BATHROOM IN THE DWELLING UNITS AND THE PROPOSED
 ALTERATION IN THE BATHROOM SHALL ALSO COMPLY WITH THE
 FAIR HOUSING ACT. THIS NEEDS TO BE DETERMINED BY
 RESEARCHING WHEN THE BUILDING WAS BUILT AND REQUESTING
 PLANS FROM THIS CITY'S WEBSITE. THIS MAY INCUR A FEE
 AND TIME TO RETRIEVE ALL THIS INFORMATION AND DETERMINE
 IF THE LEVEL OF ACCESSIBILITY IS ALTERED. WE REQUIRE TO
 SHOW THE DIMENSION OF THE CLEAR FLOOR SPACE IN THE
 BATHROOM IN FRONT OF EACH FIXTURE IN THAT BATHROOM.
  
 2. BY LOOKING AND THE PLANS SUBMITTED IN THIS CASE, THE
 BATHROOM SEEMS LIKE SPECIFICATION B, AND IT MAY BE
 CHANGED AS LONG AS IT COMPLIES WITH FHA. WOULD YOU
 PLEASE TELL US WHICH ONE IS THE B AS ONLY ONE NEEDS TO
 COMPLY? THE SHOWER REQUIRES A PARALLEL APPROACH TO IT,
 USUALLY TYPE B AND 30 INCHES BY 48 INCHES. THE VALVE
 MAY NEED TO BE SHOWN ON THE SIDE OF THE APPROACH. THE
 SPECIFICATION B, THE TOP FIXTURE RIM IS A MAXIMUM OF 34
 INCHES AFF, WITH THE APRON AT LEAST 27 INCHES AFF.
 PLEASE NOT ON PLANS WHICH BATHROOM IS TYPE B.
  
 3. THE CITY OF WEST PALM BEACH BUILDING DEPARTMENT
 PROVIDES AN OPTION FOR CHANGING AN FHA COMPLIANCE
 STRUCTURE. THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE
 THAT THE PROPOSED BATHROOM DESIGN DOES NOT MEET THE
 FAIR HOUSING ACCESSIBILITY GUIDELINES REQUIREMENTS. THE
 OWNER AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT
 THE TIME OF SALE IF SO, REQUESTED BY THE BUYER. THIS
 WILL BE IN A LETTER-TYPE FORMAT SIGNED AND NOTARIZED BY
 THE OWNER. WE PROVIDE A SAMPLE LETTER, AND IT MUST BE
 SUBMITTED TO THE BUILDING DEPARTMENT OF THE CITY OF
 WPB. IF THIS OPTION IS CHOSEN, PLEASE SEND AN EMAIL TO
 [email protected], AND I WILL SEND A COPY OF THE FAIR
 HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-14 Cont ID  
Sent By jleahy Date 2021-12-14 Time 16:03 Rev Time 0.00
Received By jleahy Date 2021-12-14 Time 15:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By jleahy Date 2021-11-15 Time 16:45 Rev Time 0.00
Received By jleahy Date 2021-11-15 Time 16:44 Sent To  
Notes
2021-11-15 16:45:58PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1,
 FS 471, 481