Plan Review Details - Permit 21100750
Plan Review Stops For Permit 21100750
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-11-05 Cont ID  
Sent By cpuell Date 2021-11-05 Time 10:51 Rev Time 0.00
Received By cpuell Date 2021-11-05 Time 10:51 Sent To  
Notes
2021-11-05 10:52:02NORTH HALF ADDRESS BUILDING READDRESSED AS 213
 MARLBOROUGH RD

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-04 Cont ID  
Sent By cpuell Date 2021-11-04 Time 13:14 Rev Time 0.00
Received By cpuell Date 2021-11-04 Time 13:14 Sent To  
Notes
2021-11-04 13:14:46THE NORTH BUILDING HAS A HALF ADDRESS WHICH WILL NEED
 TO BE READDRESSED. PLEASE HAVE THE OWNER CONTACT
 [email protected] OR CALL 561-805-6659 TO READDRESS THE
 HALF ADDRESS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-04 Cont ID  
Sent By jgomez Date 2022-02-04 Time 16:46 Rev Time 0.00
Received By jgomez Date 2022-02-04 Time 14:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jgomez Date 2021-12-27 Time 16:03 Rev Time 0.00
Received By jgomez Date 2021-12-27 Time 11:07 Sent To  
Notes
2021-12-27 16:05:56RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100750
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- SHEET S-01:
 A)DEMOLITION FLOOR PLAN SHOWS WALL ADJACENT TO THE
 STAIRWAY TO BE A BEARING WALL. THIS WALL IS REMOVED FOR
 NEW HANDRAIL. STRUCTURAL PLAN DOESN'T SHOW HOW THIS
 AREA IS REINFORCED SINCE THE BEARING WALL IS GONE.
 PROVIDE DETAILS/SPECIFICATIONS. SEC. R301.1
 FBC-RESIDENTIAL.
  
 B)SPECIFY CONNECTOR AT EACH END OF NEW (3)2X12 BEAMS AT
 DINING ROOM, LIVING ROOM AND OFFICE/DEN SHOWN ON THE
 PROPOSED STRUCTURAL PLAN. SEC. R301.1 FBC-RESIDENTIAL.
  
 C)SPECIFY CONNECTOR AT BOTTOM OF NEW COLUMNS SUPPORTING
 THE NEW BEAMS SHOWN ON THE PROPOSED STRUCTURAL PLAN.
 SEC. R301.1 FBC-RESIDENTIAL.
  
 D)REVISE COMPONENT & CLADDING DESIGN PRESSURES. THERE
 ARE TWO DIFFERENT TYPES OF ROOFS IN THIS HOUSE (FLAT
 AND PITCHED). ALSO, THIS IS A TWO STORY HOUSE. REVISE
 EXPOSURE ADJUSTMENT COEFFICIENT AS REQUIRED BASED ON
 THE MEAN ROOF HEIGHT. TABLE R301.2(3) FBC-RESIDENTIAL.
  
 2- SHEET A-01: PROPOSED BREAKFAST DOORS IS NOT CLEAR.
 FLOOR PLAN SHOWS DOOR D1 AS SLIDING GLASS DOORS, WHILE
 DOOR SCHEDULE SHOWS FRENCH DOORS. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS.
  
 3- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR WINDOW MULLIONS.
 NOTE: CLEARLY SPECIFY MULLION SIZES TO BE INSTALLED TO
 VERIFY COMPLIANCE WIT THE DESIGN PRESSURES.
  
 4-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 5- THIS IS ALTERATION LEVEL 3 NOT LEVEL 2. WORK AREA
 EXCEEDS 50% OF THE BUILDING. REVISE NOTE ON ALL PLANS.
 SEC. 604 FBC-EXISTING BUILDING.
  
 6- REVISE DETAIL S-5 ON SHEET S-02. REVISE THE SIZE OF
 THE STRUCTURAL BUCK SPECIFIED. STRUCTURAL BUCK NEEDS TO
 PROVIDE FULL SUPPORT TO THE DOOR FRAME AND NEED TO
 EXTEND BEYOND THE INTERIOR FACE OF THE WINDOW OR DOOR
 FRAME AS REQUIRED BY SEC. R609.7.2.1 FBC-RESIDENTIAL.
 2X4 BUCK IS SMALLER THAN THE DOOR FRAME. REVISE AS
 REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-01-31 Cont ID  
Sent By mpeterso Date 2022-01-31 Time 09:58 Rev Time 0.00
Received By mpeterso Date 2022-01-31 Time 09:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-01-26 Cont ID  
Sent By mpeterso Date 2022-01-26 Time 14:05 Rev Time 0.00
Received By mpeterso Date 2022-01-26 Time 14:05 Sent To  
Notes
2022-01-26 14:08:05ELECTRIC PLAN REVIEW FAILED
 1) INCORRECTLY SIZED POOL PANEL FEEDER CONDUCTOR NEC
 310.15 (B)(16)
 2) GROUNDING ELECTRODE SYSTEM TO COMPLY WITH NEC 250
 .50 AND NEC 250.32 (A) EXCEPTION, A NOTE WILL SUFFICE
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-07 Cont ID  
Sent By mpeterso Date 2021-12-07 Time 08:51 Rev Time 0.00
Received By mpeterso Date 2021-12-07 Time 08:51 Sent To  
Notes
2021-12-07 09:01:37FAILED ELECTRIC REVIEW, SEE COMMENTS BELOW AND CORRECT
 AS NESSECARY
 1) THERE IS NO RISER DIAGRAM SUBMITTED WITH THIS PERMIT
 AS STATED ON E-01 NEC 215.5
 2) THERE IS NO PANEL SCHEDULES OR LOAD CALCULATIONS
 SUBMITTED WITH THIS PERMIT AS PER NEC 215.5
 3) RECEPTACLE SPACING IN SOME AREAS MAY BE INADEQUATE
 AS PER NEC 210.52
 4) THERE ARE NO NOTES IDENTIFYING 120-VOLT BRANCH
 CIRCUITS TO BE ARC-FAULT PROTECTED AS PER NEC 210.12
 5) THERE IS NO SWITCH SHOWN TO CONTROL FIREPLACE
 SCONCES FBC 107.23

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-11-08 Cont ID  
Sent By ccole Date 2021-11-08 Time 13:44 Rev Time 0.00
Received By ccole Date 2021-11-08 Time 13:44 Sent To  
Notes
2021-11-08 13:45:09GAS UNDER SEPARATE PERMIT PER NOTE ON SHEET P01.

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2022-02-01 Cont ID  
Sent By amhamilt Date 2022-02-01 Time 14:41 Rev Time 0.00
Received By amhamilt Date 2022-02-01 Time 14:41 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-11-12 Cont ID  
Sent By amhamilt Date 2021-11-12 Time 16:10 Rev Time 0.00
Received By amhamilt Date 2021-11-12 Time 16:10 Sent To  
Notes
2021-11-12 16:11:36NEED REVISIONS AS PER OUR DISCUSSION DURING SITE VISIT,
 PARTICULARLY REGARDING REAR SLIDING DOOR ON PLANS.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 561.822.1428
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-04 Cont ID  
Sent By jgomez Date 2022-02-04 Time 16:47 Rev Time 0.00
Received By jgomez Date 2022-01-12 Time 17:07 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By jgomez Date 2021-12-27 Time 16:09 Rev Time 0.00
Received By jgomez Date 2021-11-03 Time 08:28 Sent To I
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By medwards Date 2021-11-05 Time 06:15 Rev Time 0.00
Received By medwards Date 2021-11-05 Time 06:15 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By jgomez Date 2021-12-27 Time 14:24 Rev Time 0.00
Received By jgomez Date 2021-12-27 Time 14:11 Sent To  
Notes
2021-12-27 14:23:44NO A SUBSTANTIAL IMPROVEMENT. IMPROVEMENT VALUE
 $300,000. PALM BEACH COUNTY PROPERTY APPRAISER (2021)
 IMPROVEMENT VALUE $856,342. JG.
  
  
  
 LAST FIVE YEARS PERMIT HISTORY:
 PERMIT #21100750: INTERIOR RENOVATION TO AN EXISTING
 SINGLE FAMILY VALUE: $300000
 PERMIT #17060475: AC CHANGEOUT TEMPSTAR 2 TONS 14 SEER
 5KW. VALUE: $5572
 PERMIT #17041129: REMOVE & REPLACE 14 WINDOWS AND 1
 DOOR IMPACT. VALUE: $19000
 TOTAL VALUE: $324,572

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-13 Cont ID  
Sent By ccole Date 2022-01-13 Time 16:58 Rev Time 0.00
Received By ccole Date 2022-01-13 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-08 Cont ID  
Sent By ccole Date 2021-11-08 Time 13:43 Rev Time 0.00
Received By ccole Date 2021-11-08 Time 13:40 Sent To  
Notes
2021-11-08 13:44:141ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21100750
 11/8/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-02 PLUMBING RISER: THE FIXTURE VENTING IN
 THE POWDER ROOM AND LAUNDRY ROOM IS NOT TO CODE. TWO
 OPTIONS: 1) PROVIDE AN INDIVIDUAL VENT FOR THE WATER
 CLOSET. 2) PROVIDE AN INDIVIDUAL VENT FOR THE UTILITY
 SINK WHICH ALLOWS THE WATER CLOSET TO BE WET VENTED
 WITH THE LAVATORY PROVIDING THE REQUIRED DRY VENT.
 PLEASE NOTE THAT THE FIXTURE DRAIN FOR THE UTILITY SINK
 SHALL CONNECT DOWN STEAM OF THE POWDER ROOM WET VENT-
 SEE SECTIONS P3106.1, P3107.1, AND P3108.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-04 Cont ID  
Sent By jgomez Date 2022-02-04 Time 16:46 Rev Time 0.00
Received By jgomez Date 2022-02-04 Time 16:46 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-12-06 Cont ID  
Sent By mpeterso Date 2021-12-06 Time 14:56 Rev Time 0.00
Received By mpeterso Date 2021-12-06 Time 14:56 Sent To  
Notes
2021-12-06 14:57:14REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED