Plan Review Details - Permit 21100717
Plan Review Stops For Permit 21100717
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-01 Cont ID  
Sent By rmcdouga Date 2021-11-01 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2021-11-01 Time 14:21 Sent To  
Notes
2021-11-01 14:09:52ELEVATION CERTIFICATE
 REVIEW COMMENTS
 145 BLOOMFIELD DRIVE
  
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CORRECTED.
  
 2) CORRECTED.
  
 3) CORRECTED.
  
 4) CORRECTED.
  
 5) THE NET AREA OF THE FLOOD OPENINGS IN ITEM A9(C)
 NEEDS TO BE CORRECTED TO LIST THE AREA OF THE SMART
 VENTS AND ITEM A9(D) NEEDS TO BE CHANGED TO YES BECAUSE
 THE SMART VENTS ARE ENGINEERED FLOOD OPENINGS.
  
 6) CORRECTED.
  
 7) CORRECTED.
  
 8) CORRECTED.
  
 9) CORRECTED.
  
 10) CORRECTED.
  
 11) CORRECTED.
  
 12) CORRECTED.
  
 13) CORRECTED.
  
 14) [ THE PRODUCT APPROVAL/EVALUATION IS FOR SMART VENT
 ENGINEERED FLOOD VENTS. THESE ARE NOT THE ONES THAT ARE
 SPECIFIED ON THE PLANS. THE PLANS WILL NEED TO BE
 REVISED TO SHOW THE SMART VENTS AND THEIR LOCATIONS. ]
 SUBMIT THE SPECIFICATIONS, EVALUATION REPORT, PRODUCT
 APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE USED.
 THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS THAN
 THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE PLANS.
  
 15) CORRECTED.
  
 16) CORRECTED.
  
 17) CORRECTED.
  
 18) CORRECTED.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-10-29 Cont ID  
Sent By rmcdouga Date 2021-10-29 Time 11:36 Rev Time 0.00
Received By rmcdouga Date 2021-10-29 Time 08:25 Sent To  
Notes
2021-10-29 10:25:59ELEVATION CERTIFICATE
 REVIEW COMMENTS
 145 BLOOMFIELD DRIVE
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) CORRECTED.
  
 2) CORRECTED.
  
 3) CORRECTED.
  
 4) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION.
 THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE,
 WHICH IS ITEM A9.] THERE ARE (4) FLOOD OPENINGS
 SPECIFIED ON THE PLANS AND SHOWN IN THE PHOTOGRAPHS.
 ITEM A9 B) LISTS 0.
  
 5) [THIS INFORMATION WAS ENTERED IN THE WRONG LOCATION.
 THE FLOOD OPENINGS ARE LOCATED IN THE ATTACHED GARAGE,
 WHICH IS ITEM A9. THE PRODUCT EVALUATIONS THAT WERE
 SUBMITTED ARE FOR SMART VENTS. THE INFORMATION FOR THE
 SMART VENTS NEEDS TO BE PROVIDED RATHER THAN THE
 CALCULATIONS FOR THE GREENHECK LOUVERS SHOWN ON THE
 ORIGINAL BUILDING PLANS. THE FLOOD OPENINGS ARE
 REQUIRED TO BE LOCATED NO HIGHER THAN 1.0 FOOT ABOVE
 THE HIGHER OF THE EXTERIOR OR INTERIOR GRADE OR FLOOR
 IMMEDIATELY BELOW THE OPENING. IF THE INTERIOR GRADE
 ELEVATION IS USED, NOTE THIS IN THE COMMENTS AREA OF
 SECTION D. IT SHOULD ALSO BE NOTED IN THE COMMENTS AREA
 OF SECTION D THAT ENGINEERED SMART VENTS ARE INSTALLED.
 ] A9 C) LISTS THE NET AREA OF FLOOD OPENINGS AS 0.0
 SQIN. SHEET A-1.0 OF THE PLANS HAS CALCULATIONS
 SPECIFYING THAT 7448 SQIN OF NET OPENING AREA WILL BE
 PROVIDED.
  
 6) CORRECTED.
  
 7) CORRECTED.
  
 8) CORRECTED.
  
 9) CORRECTED.
  
 10) CORRECTED.
  
 11) [ VERIFY THE CORRECT ELEVATION AND SPECIFY IT ON
 BOTH DOCUMENTS. ] ITEM C2 D) LISTS THE ELEVATION FOR
 THE TOP OF GARAGE SLAB AS 6.6 FT. THE TIE IN SURVEY
 SPECIFIES THE GARAGE ELEVATION AS 6.21' FT. THESE
 ELEVATIONS NEED TO BE CONSISTENT.
  
 12) [ THE EQUIPMENT WILL HAVE TO BE RAISED SO THAT IT
 IS ABOVE THE DFE WHICH IS 8.0' NAVD. ] ITEM C2 E) LISTS
 THE LOWEST ELEVATION OF THE EQUIPMENT SERVICING THE
 BUILDING AS 7.5 FT. THE EQUIPMENT IS REQUIRED TO BE AT
 OR ABOVE THE DFE WHICH IS 8' NAVD.
  
 13) [ ENTER THIS INFORMATION IN THE COMMENTS AREA OF
 SECTION D. ] THE METHOD USED TO DETERMINE LATITUDE AND
 LONGITUDE IS TO BE INDICATED IN THE COMMENTS AREA OF
 SECTION D.
  
 14) [ THE PRODUCT APPROVAL/EVALUATION IS FOR SMART VENT
 ENGINEERED FLOOD VENTS. THESE ARE NOT THE ONES THAT ARE
 SPECIFIED ON THE PLANS. THE PLANS WILL NEED TO BE
 REVISED TO SHOW THE SMART VENTS AND THEIR LOCATIONS. ]
 SUBMIT THE SPECIFICATIONS, EVALUATION REPORT, PRODUCT
 APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE USED.
 THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS THAN
 THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE PLANS.
  
 15) [ PHOTOS OF ELEVATIONS SHOWING THE FLOOD OPENINGS
 ARE REQUIRED. ] NEW PHOTOS OF THE BUILDING SHOWING THE
 FINISH GRADES ARE REQUIRED.
  
 16) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
 17) NEW COMMENT. THE BUILDING OWNER'S NAME IN ITEM A1
 IS 145 BLOOMFIELD TRUST. THE CITY'S AND PROPERTY
 APPRAISER'S RECORD HAVE THE OWNER AS PAMELA LOMBA.
 PLEASE CORRECT.
  
 18) NEW COMMENT. ITEM C2 HAS GPS FOR BENCHMARK
 UTILIZED. FEMA'S EC INSTRUCTIONS STATE THAT FOR A GPS
 SURVEY, INDICATE THE BENCHMARK USED FOR THE BASE
 STATION, THE CONTINUOUSLY OPERATING REFERENCE STATIONS
 (CORS) SITES USED FOR AN ON-LINE POSITIONING USER
 SERVICE (OPUS) SOLUTION (ALSO ATTACH THE OPUS REPORT),
 OR THE NAME OF THE REAL TIME NETWORK USED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By cthroop Date 2021-10-26 Time 13:22 Rev Time 0.00
Received By rmcdouga Date 2021-10-26 Time 07:08 Sent To  
Notes
2021-10-26 11:04:21ELEVATION CERTIFICATE
 REVIEW COMMENTS
 145 BLOOMFIELD DRIVE
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE LATITUDE AND LONGITUDE FOR ITEM A5 ARE INCORRECT
 AND ARE REQUIRED TO BE AT LEAST 5 DECIMAL PLACES.
 CHANGE TO LATITUDE 26.65871 AND LONGITUDE -80.04876.
  
 2) FOR ITEM A7 THE BUILDING DIAGRAM NUMBER SHOULD BE 1B
 FOR A RAISED SLAB ON GRADE.
  
 3) THE PLANS SPECIFY THE ATTACHED GARAGE IS 535 SQFT.
 ITEM A9 A) HAS 500 SQFT.
  
 4) THERE ARE (4) FLOOD OPENINGS SPECIFIED ON THE PLANS
 AND SHOWN IN THE PHOTOGRAPHS. ITEM A9 B) LISTS 0.
  
 5) A9 C) LISTS THE NET AREA OF FLOOD OPENINGS AS 0.0
 SQIN. SHEET A-1.0 OF THE PLANS HAS CALCULATIONS
 SPECIFYING THAT 7448 SQIN OF NET OPENING AREA WILL BE
 PROVIDED.
  
 6) IN ITEM B3 THE 2-LETTER STATE ABBREVIATION SHOULD BE
 ENTERED. FLORIDA SHOULD NOT BE SPELLED OUT.
  
 7) THE DATE OF THE FIRM IN ITEM B6 IS INCORRECT. THE
 CORRECT DATE IS 10-05-2017.
  
 8) THE EFFECTIVE DATE OF THE FIRM PANEL IN ITEM B7 IS
 ALSO INCORRECT. THE CORRECT DATE IS 10-05-2017.
  
 9) THE FLOOD ZONES IN B8 SHOULD BE X500 & AE.
  
 10) FINISHED CONSTRUCTION IS MARKED IN ITEM C1. THE
 PHOTOS DO NOT APPEAR TO SHOW THAT THE GRADING AROUND
 THE BUILDING IS COMPLETE WHICH IS REQUIRED FOR THE
 FINAL E. C.
  
 11) ITEM C2 D) LISTS THE ELEVATION FOR THE TOP OF
 GARAGE SLAB AS 6.6 FT. THE TIE IN SURVEY SPECIFIES THE
 GARAGE ELEVATION AS 6.21' FT. THESE ELEVATIONS NEED TO
 BE CONSISTENT.
  
 12) ITEM C2 E) LISTS THE LOWEST ELEVATION OF THE
 EQUIPMENT SERVICING THE BUILDING AS 7.5 FT. THE
 EQUIPMENT IS REQUIRED TO BE AT OR ABOVE THE DFE WHICH
 IS 8' NAVD.
  
 13) THE METHOD USED TO DETERMINE LATITUDE AND LONGITUDE
 IS TO BE INDICATED IN THE COMMENTS AREA OF SECTION D.
  
 14) SUBMIT THE SPECIFICATIONS, EVALUATION REPORT,
 PRODUCT APPROVAL, ETC. FOR THE FLOOD OPENINGS THAT WERE
 USED. THE PHOTOS APPEAR TO SHOW DIFFERENT FLOOD VENTS
 THAN THE GREENHECK LOUVERS THAT ARE SPECIFIED ON THE
 PLANS.
  
 15) NEW PHOTOS OF THE BUILDING SHOWING THE FINISH
 GRADES ARE REQUIRED.
  
 16) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2021-11-03 Cont ID  
Sent By rmcdouga Date 2021-11-03 Time 15:04 Rev Time 0.00
Received By rmcdouga Date 2021-11-03 Time 15:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 15:29 Rev Time 0.00
Received By rmcdouga Date 2021-11-01 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-01 Cont ID  
Sent By rmcdouga Date 2021-11-01 Time 14:24 Rev Time 0.00
Received By rmcdouga Date 2021-11-01 Time 08:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status F Date 2021-10-29 Cont ID  
Sent By rmcdouga Date 2021-10-29 Time 14:06 Rev Time 0.00
Received By rmcdouga Date 2021-10-28 Time 16:13 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-26 Cont ID  
Sent By rmcdouga Date 2021-10-26 Time 13:23 Rev Time 0.00
Received By rmcdouga Date 2021-10-19 Time 07:32 Sent To  
Notes
***NONE***

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status P Date 2021-12-13 Cont ID  
Sent By cthroop Date 2021-12-13 Time 14:13 Rev Time 0.00
Received By cthroop Date 2021-12-13 Time 12:43 Sent To  
Notes
2021-12-13 14:14:07FINISHED CONSTRUCTION EC PEER REVIEW BY CT. APPROVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 15:10 Sent To  
Notes
2021-11-02 15:24:32THE FINAL SURVEY AND ELEVATION CERTIFICATE HAS BEEN
 REVIEWED AND APPROVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By rmcdouga Date 2021-11-01 Time 14:21 Rev Time 0.00
Received By rmcdouga Date 2021-11-01 Time 14:21 Sent To  
Notes
2021-11-01 14:24:15NEED A CORRECTED FINAL E.C.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-11-03 Cont ID  
Sent By rmcdouga Date 2021-11-03 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2021-11-03 Time 15:03 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 15:10 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 15:10 Sent To  
Notes
2021-11-02 15:23:04SEALED PAPER ELEVATION CERTIFICATE WAS SUBMITTED. THE
 SURVEYOR'S SIGNATURE APPEARS TO BE A COPY AND NOT AN
 ORIGINAL SIGNATURE.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-01 Cont ID  
Sent By rmcdouga Date 2021-11-01 Time 14:22 Rev Time 0.00
Received By rmcdouga Date 2021-11-01 Time 14:21 Sent To  
Notes
2021-11-01 14:23:03THE SURVEYOR'S ORIGINAL HANDWRITTEN SIGNATURE IS
 REQUIRED ON PAPER DOCUMENTS. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-10-29 Cont ID  
Sent By rmcdouga Date 2021-10-29 Time 08:24 Rev Time 0.00
Received By rmcdouga Date 2021-10-29 Time 08:24 Sent To  
Notes
2021-10-29 08:24:53ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By rmcdouga Date 2021-10-26 Time 07:10 Rev Time 0.00
Received By rmcdouga Date 2021-10-26 Time 07:10 Sent To  
Notes
2021-10-26 07:18:28THE SURVEYOR'S SIGNATURE IS A COPY.