Plan Review Details - Permit 21100680
Plan Review Stops For Permit 21100680
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 08:37 Rev Time 0.00
Received By rmcphers Date 2021-12-15 Time 08:37 Sent To  
Notes
2021-12-15 08:39:02FLOORING REVISION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE A FLOOR PLAN SHOWING THE TYPE OF
 FLOORING AND THE LOCATION OF THE FLOORING - ALSO SHOW
 THE SQUARE FOOTAGE FOR EACH FLOORING TYPE.
  
 2) PLEASE SHOW THE ADDITIONAL JOB VALUE ON THE PLAN
 REVIEW REQUEST FORM IN THE SPACE PROVIDED.
  
 3) ACUSTICAL TEST REPORT PROVIDED FOR "MAXXIM SIM 90
 UNDERLAYMENT" AND "PROFLEX SSC 70" SHOWS A DROP CEILING
 - TEST REPORT CANNOT INCLUDE A DROP CEILING UNLESS THE
 DROP CEILING DESCRIPTION MATCHES YOUR CEILING.
  
 4) PLEASE PROVIDE A FLAME SPREAD TEST REPORT FOR THE
 WOOD FLOORING - FBC 603.1, ALLOWABLE MATERIALS IN NON
 COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 5) YOU HAVE A FEW DIFFERENT FLOORING UNDERLAYMENTS IN
 PROJECTDOX - ON THE FLOOR PLAN THAT YOU NEED TO PROVIDE
 WRITE THE UNDERLAYMENT NAMES TO BE USED SO THAT I DON'T
 KEEP FAILING THE REVIEW FOR THE SAME DOCUMENTS
 PROVIDED. I WILL REMOVE THE TEST REPORTS FROM
 PROJECTDOX THAT ARE NOT WRITTEN ON THE FLOOR PLAN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 15:00 Rev Time 0.00
Received By rmcphers Date 2021-11-01 Time 15:00 Sent To  
Notes
2021-11-01 15:06:50FLOORING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PROFLEX SSC 70 = CANNOT USE A TEST REPORT THAT
 INCLUDES A DROP CEILING UNLESS THE UNIT BELOW YOU HAS A
 DROP CEILING AND INSULATION THAT MATCHES THE TEST
 REPORT GIVEN.
  
 2) YOU WILL ALSO NEED TO PROVIDE A FLAME SPREAD TEST
 REPORT FOR THE PROFLEX SSC 70 ITSELF OR A TILE AND
 UNDERLAYMENT SYSTEM - FBC 603.1, ALLOWABLE MATERIALS IN
 NON COMBUSTIBLE BUILDINGS, SEE ITEM 2, EXCEPTION 2,
 ACOUSTICAL INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200. SEE 803.1.1, PROVIDE TEST DATA IN
 ACCORDANCE WITH ASTM E 84 OR UL 723.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By pleduc Date 2021-10-22 Time   Rev Time 0.00
Received By pleduc Date 2021-10-22 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-15 Cont ID  
Sent By rmcphers Date 2021-12-15 Time 08:44 Rev Time 0.00
Received By rmcphers Date 2021-12-02 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 15:14 Rev Time 0.00
Received By rmcphers Date 2021-10-18 Time 11:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By rmcphers Date 2021-11-01 Time 15:13 Rev Time 0.00
Received By rmcphers Date 2021-11-01 Time 15:13 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved