| Plan Review Stops For Permit 21100662 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-31 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-31 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-26 |
Time |
14:09 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-26 |
Time |
14:03 |
Sent To |
|
|
| Notes |
| 2022-01-26 14:04:15 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 2ND REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A COMPLETE SET OF THE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS FOR THE PROPSED BBQ GRILL | | | INSERT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-12-08 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-12-08 |
Time |
06:57 |
Sent To |
|
|
| Notes |
| 2021-12-08 09:14:21 | BUILDING PLAN REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. PROVIDE A COMPLETE SET OF THE MANUFACTURERS | | | INSTALLATION INSTRUCTIONS FOR THE PROPSED BBQ GRILL | | | INSERT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 2. PROVIDE STRUCTURAL DETAIL OF MASONRY WALL. INCLUDE | | | FOUNDATION TO WALL CONNECTION. VERTICAL REINFORCING IS | | | REQUIRED ON EACH SIDE OF A MASONRY OPENING. TERMINATE | | | VERTICAL STEEL INTO LINTEL. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 3. PROVIDE PRODUCT APPROVAL FOR LINTELS. | | | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE | | | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. | | | | | | 4. PROVIDE COUNTER TOP DETAILS. SPECIFY COUNTER TOP | | | MATERIAL. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | 5. IDENTIFY SIZE AND LOCATION OF THE COMBUSTION AIR | | | OPENING PER MANUF. INSTALLATION INSTRUCTIONS. THIS WILL | | | BE BASED ON THE BTU'S OF THE INSETRT. | | | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS | | | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH | | | 107.2.5. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-31 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-31 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-12-09 |
Time |
19:28 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-12-09 |
Time |
18:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-11-08 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-11-08 |
Time |
22:22 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-11-08 |
Time |
21:37 |
Sent To |
|
|
| Notes |
| 2021-11-08 22:22:04 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | 1. HOW CAN ELECTRICAL BE EXISTING WHEN KITCHEN IS BEING | | | BUILT IS BRAND NEW? PROVIDE ELECTRICAL PLAN FOR REVIEW | | | SIGNED BY ELECTRFICAL CONTRACTOR QUAILFIER FS | | | 471.003(2)(H); 471.025; WPB FBC 107.2.1, 107.3.5 | | | | | | END OF COMMENTS. | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | | PREVIOUSLY REVIEWED SHEETS. | | | CODES IN EFFECT: | | | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | | UILDING-PERMIT-FORMS | | | | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | FRANK GIAQUINTO III | | | ELECTRICAL INSPECTOR | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | [email protected] | | | CELL: 561-805-6744 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
N |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
rwbrown |
Date |
2022-02-16 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
rwbrown |
Date |
2022-02-16 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2022-02-16 11:27:08 | NOT REQUIRED PER THE 1ST REVIEWER'S COMMENTS. 2ND | | | REVIEW SHOULD HAVE REFLECTED THE SAME. CORRECTION MADE | | | BY RYAN BROWN. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-01-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2022-01-29 |
Time |
15:11 |
Sent To |
|
|
| Notes |
| 2022-01-29 16:49:05 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21100662 | | | 1/29/2022 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH | | | EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH | | | EDITION 2020 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. | | | FGC SEC.305.1, FBC-RES. SEC.G2408.1. | | | 2. A GAS GRILL IS LABELED FOR OUTSIDE USE AND IT SEEMS | | | TO BE IN A COVERED PATIO, IF SO PLEASE PROVIDE | | | MANUFACTURES RECOMMENDATION FOR A VENTILATION HOOD, | | | 2020 FBC FG SEC.G2408.1. | | | 3. TYPE OF GAS (LP OR NATURAL). WPB AMENDMENTS TO THE | | | FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 4. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. | | | A LISTED SHUTOFF VALVE SHALL BE INSTALLED IMMEDIATELY | | | AHEAD OF EACH MP REGULATOR. 2020 FBC FUEL GAS SEC. | | | 409.4, FBC FUEL GAS RES. SEC. G2420.4. | | | 5. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU | | | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE | | | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING | | | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING | | | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING | | | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS | | | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH | | | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH | | | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF | | | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE | | | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE | | | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE | | | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE | | | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES | | | 2020 FBC FUEL GAS SECS. 401.4, 401.8, 402.1, 402.2, | | | 402.3 OR 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, | | | G2413.1, G2413.2, G2413.3. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-22 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-11-22 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2021-11-22 09:42:18 | PERMIT FOR GAS UNDER 00061116, GAS LINES SHALL NOT BE | | | MOVE OR ALTERED. | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
P |
Date |
2022-01-31 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-31 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-28 |
Time |
15:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-26 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-26 |
Time |
11:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-12-08 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2021-12-08 |
Time |
09:37 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2021-10-18 |
Time |
05:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-01-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2022-01-29 |
Time |
15:11 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-11-22 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-11-22 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-01-28 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-28 |
Time |
15:40 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-28 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2022-01-28 15:42:19 | | | | REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS AND | | | DOCUMENTS APPROVED AND PLANS ROUTED TO STORAGE/CLC | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-01-26 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-01-26 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2022-01-26 14:07:05 | SIGNATURE REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | INSPECTOR BN4338 | | | BUILDING OFFICIAL BU1635 | | | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 | | | DEVELOPMENT SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NEC2017 | | | | | | 2ND REVIEW | | | RESULTS: DENIED | | | | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | RE: PLAN PAGE 1 OF 3 SUBMITTED ON 1-26-22. | | | | | | 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND | | | SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, | | | DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR | | | DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL | | | SIGNATURE. | | | | | | 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR | | | DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL | | | WET SEAL AND SIGNATURE TO: | | | | | | BUILDING DIVISION, FIRST FLOOR | | | CITY OF WEST PALM BEACH | | | 401 CLEMATIS ST | | | WEST PALM BEACH, FL 33401 | | | | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-10-18 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-10-18 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2021-10-18 10:44:11 | PASSED SIGNATURE WITHSEAL AND WET SIGNATURE |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-11-02 |
|
|
Cont ID |
|
| Sent By |
rthermid |
Date |
2021-11-02 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-11-02 |
Time |
|
Sent To |
I |
|
| Notes |
|
|