Rev No 3 Status N Date 2021-11-19 Cont ID  
Sent By medwards Date 2021-11-19 Time 08:13 Rev Time 0.00
Received By medwards Date 2021-11-18 Time 07:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 12:54 Rev Time 0.00
Received By medwards Date 2021-11-15 Time 14:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 10:20 Rev Time 0.00
Received By medwards Date 2021-11-11 Time 07:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-11-19 Cont ID  
Sent By medwards Date 2021-11-19 Time 08:13 Rev Time 0.00
Received By medwards Date 2021-11-19 Time 08:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-16 Cont ID  
Sent By medwards Date 2021-11-16 Time 11:13 Rev Time 0.00
Received By medwards Date 2021-11-16 Time 11:13 Sent To  
Notes
2021-11-16 12:53:24THE ENERGY CALCULATION SHOW THE SYSTEM SERVES THE WHOLE
 HOUSE, NOT OTHER AND IDENTIFIES THE CORRECT AREA.
 PLEASE IDENTIFY THE CORRECT AREA SERVED BY THIS UNIT.
 THE ENERGY CALCULATIONS SHOW THE LOCATION IS BROWARD
 COUNTY FL. PLEASE CORRECT THIS TO WEST PALM BEACH.
 THE ENERGY CALCULATIONS DO NOT MENTION THE GARAGE DOOR,
 PLEASE SHOW THIS IN THE CALCULATIONS.
 THE ENERGY CALCULATIONS INDICATE THE CONDITIONED AREA
 IS 735 SQ FT AND 1 BEDROOM. IS THIS GARAGE BEING
 CONVERTED TO A BEDROOM?
 THE ENERGY CALCULATION INDICATES THE DESIGN IS FOR
 70DEG HEATING AND 75 DEG FOR COOLING BUT EQUIPMENT TYPE
 IS FOR COOLING-ONLY AIR CONDITIONER.
 THE DUCT DESIGN IS FOR 688 SQ FT BUT THE CONDITIONED
 FLOOR AREA USED IN LOADS IS 735 SQ. FT. PLEASE BE
 CONSISTENT.
 PLEASE SHOW THE SEER RATING IN THE ENERGY CALCULATIONS.
 THE ENERGY CALCULATIONS, UNDER THE RESNET, IT LISTS
 THAT THE FURNACE HEATING EFFICIENCY IS 80 AFUE. WHERE
 IS THIS FURNACE LOCATED?
 PLEASE PROVIDE CODE COMPLIANT DOCUMENTS. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 10:17 Rev Time 0.00
Received By medwards Date 2021-11-12 Time 10:16 Sent To  
Notes
2021-11-12 10:19:27PLEASE PROVIDE THE ENERGY CALCULATIONS. PLEASE PROVIDE
 THE MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE
 PROVIDE A MECHANICAL DRAWING FOR THIS PROJECT SHOWING
 THE LOCATION OF THE INDOOR AND OUTDOOR UNITS ALONG WITH
 THE CONDENSATION TERMINATION LOCATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status N Date 2021-11-19 Cont ID  
Sent By medwards Date 2021-11-19 Time 08:13 Rev Time 0.00
Received By medwards Date 2021-11-19 Time 08:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-11-12 Cont ID  
Sent By medwards Date 2021-11-12 Time 10:20 Rev Time 0.00
Received By medwards Date 2021-11-12 Time 10:20 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved