Plan Review Details - Permit 21100616
Plan Review Stops For Permit 21100616
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By ccole Date 2022-04-13 Time 08:36 Rev Time 0.00
Received By ccole Date 2022-04-13 Time 08:36 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 13:33 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-01-26 13:33:35COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-22 Cont ID  
Sent By jwitmer Date 2021-12-22 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2021-12-22 Time 13:41 Sent To  
Notes
2021-12-22 13:58:48COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-26 Cont ID  
Sent By jwitmer Date 2022-01-26 Time 13:36 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-12-22 Cont ID  
Sent By jwitmer Date 2021-12-22 Time 13:57 Rev Time 0.00
Received By jwitmer Date 2021-12-22 Time 13:40 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-28 Cont ID  
Sent By jleahy Date 2022-01-28 Time 13:58 Rev Time 0.00
Received By jleahy Date 2022-01-28 Time 13:57 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-06 Cont ID  
Sent By jleahy Date 2022-01-06 Time 14:47 Rev Time 0.00
Received By jleahy Date 2022-01-06 Time 14:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-25 Cont ID  
Sent By pleduc Date 2022-01-25 Time   Rev Time 0.00
Received By pleduc Date 2022-01-25 Time 13:45 Sent To  
Notes
2022-01-25 13:46:27FIRE PROVISO
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-11-17 Cont ID  
Sent By pleduc Date 2021-11-17 Time   Rev Time 0.00
Received By pleduc Date 2021-11-16 Time 11:20 Sent To  
Notes
2021-11-17 16:45:09FIRE PROVISO
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ANY WORK ON THE FIRE SPRINKLER & FIRE ALARM, INCLUDING
 DEMO, SHALL BE DONE UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-04-13 Time   Rev Time 0.00
Received By aoliver Date 2022-03-28 Time 13:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-15 Cont ID  
Sent By medwards Date 2022-02-15 Time 07:26 Rev Time 0.00
Received By medwards Date 2022-01-24 Time 09:24 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-06 Cont ID  
Sent By jleahy Date 2022-01-06 Time 14:47 Rev Time 0.00
Received By jleahy Date 2021-11-11 Time 09:43 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By medwards Date 2022-04-13 Time 06:02 Rev Time 0.00
Received By medwards Date 2022-04-13 Time 06:01 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-15 Cont ID  
Sent By medwards Date 2022-02-15 Time 07:14 Rev Time 0.00
Received By medwards Date 2022-02-15 Time 07:14 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-06 Cont ID  
Sent By medwards Date 2021-12-06 Time 08:19 Rev Time 0.00
Received By medwards Date 2021-12-06 Time 07:41 Sent To  
Notes
2021-12-06 08:19:581ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100616
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OCCUPANCY CLASSIFICATION FOR THE
 PRE-OP, PROCEDURE AND POST-OP ROOMS. FBC M 407
  
 2) THE EXHAUST TRUNK HAS A BRANCH EXTENSION OUTSIDE OF
 THE EX-TOILET TO THE RIGHT OF THE LAB. IS THIS
 EXTENSION FOR THE STORAGE AREA OUTSIDE OF THE LAB?
  
 3) THE EXISTING HP-2 APPEARS TO HAVE A DAMPER FOR A
 RETURN IN EXAM 3 BUT THERE IS NO DUCT TIED TO THE
 RETURN GRILLE.
  
 4) THE EXISTING HP-5 HAS A DAMPER FOR A RETURN AIR DUCT
 AT THE END OF THE 8 X 12 DUCT BUT IT DOESN?T CONNECT TO
 A RETURN AIR GRILLE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By ccole Date 2022-04-13 Time 08:34 Rev Time 0.00
Received By ccole Date 2022-04-13 Time 07:56 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By lcrespo Date 2022-01-27 Time 08:07 Rev Time 0.00
Received By lcrespo Date 2022-01-27 Time 08:07 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-14 Cont ID  
Sent By lcrespo Date 2021-12-14 Time 11:59 Rev Time 0.00
Received By lcrespo Date 2021-12-14 Time 09:44 Sent To  
Notes
2021-12-14 12:00:0912/14/21 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. ON SHEET AG2.01;
  
 A.UNGER GENERAL NOTES NUMBER 3 REFERS TO THE ADA
 STANDARD AND THE CODE REFERENCE THAT SHOULD BE USED IS
 THE 2020 FLORIDA BUILDING CODE ACCECIBILTY 7 TH EDITION
 PER THE WPB AMENDMENTS TO FBC 102.3 APPLICATION OF
 REFERENCES. WOULD PLEASE4 REFER TO THE FOLLOWING IF
 PREFERRED HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA. ITEM
 FOUR IS NOT REQUIRED.
  
 B. GRAB BARS SHALL BE INSTALLED HORIZONTALLY PER THE
 2020 FBC ACC SEC. 609.4.
  
 C. THE TOILET GRAB BAR SAYS 6 INCHES FROM THE WALL,
 WHICH IS NOT AN ACTUAL NUMBER AS THE TOILET IS 16
 INCHES TO 18 INCHES TO THE CENTER, AND THAT NUMBER MAY
 CONFUSE THE INSTALLER. WOULD YOU PLEASE CORRECT PER THE
 2020 FBC ACC SEC. 604.2 LOCATION AND WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS?
  
 D. THE TOILET SEATS NEED TO BE 17 INCHES TO 19 INCHES
 MAXIMUM MEASURED TO THE TOP OF THE SEAT PER THE 2020
 FBC ACC SEC. 604.4 SEATS.
  
 E. A MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED PER
 THE 2020 ACC FBC SEC. 211.2 AND FBC P SEC. 410.3.
  
 F. SEATS OF WATER CLOSETS SHALL BE OPEN-FRONT TYPE PER
 2020 FBC P 425.3 WATER CLOSET SEATS.
  
 2. SUBMIT LISTED FIRE-STOPPING DETAILS FOR THE PIPPING
 THROUGH RATED WALLS OR THE FLOORS. PLEASE SUBMIT THE
 COMPLETE ASSEMBLY DETAILS FOR THE SYSTEMS PER THE WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 3. ON SHEET LS1.01;
  
 A. IT HAS THE CODE REFERENCE SAYING 2017 FOR PLUMBING.
 WOULD YOU PLEASE REMOVE PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 B. UNDER PLUMB=ING FIXTURE CALCULATION, IT REQUIRES A
 SERVICE SINK, AND I DON'T SEE ANY LOCATION NEARBY.
 WOULD YOU PLEASE CLARIFY PER THE WPB AMENDMENTS TO THE
 FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. ON SHEET P0.01;
  
 A. UNDER PLUMBING SPECIFICATIONS 2.1, THE 2018
 INTERNATIONAL PLUMBING CODE IS REFERENCED, AND WE GO BY
 THE 2020 FLORIDA PLUMBING CODE PER THE WPB AMENDMENTS
 TO FBC 102.3 APPLICATION OF REFERENCES.
  
 B. THERE IS A REQUIREMENT IN THE FLORIDA ENERGY CODE
 SEC. C404.6.1. B. HOT WATER LINES LOOPED FOR THE
 RECIRCULATING SYSTEM ARE NOT IN A CONTINUOUS LOOP.
 THERE IS A TABLE THAT LIMITS THE BETWEEN THE SOURCE AND
 THE OUTLET; PLEASE REFER TO TABLE 404.5.1 FOR THE
 MAXIMUM ALLOWABLE PIPE LENGTH METHOD AND SIZE
 ACCORDANTLY.
  
 C. ON ISOMETRIC, THE DRINKING FOUNTAIN DOES NOT SHOW A
 HAMMER ARRESTOR PER THE 2020 FBC SEC. P604.9.
  
 D. FIXTURES UNDER THE COFFEE MAKER/ICE MAKER REQUIRE AN
 INLINE VACUUM BREAKER THAT COMPLIES WITH THE ASSE 1024
 NON-CARBONATED PER THE 2020 FBC SEC. 608.17.1.2.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION,
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By medwards Date 2022-04-13 Time 06:02 Rev Time 0.00
Received By medwards Date 2022-04-13 Time 06:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-02-15 Cont ID  
Sent By medwards Date 2022-02-15 Time 07:22 Rev Time 0.00
Received By medwards Date 2022-02-15 Time 07:22 Sent To  
Notes
2022-02-15 07:26:11THE FOLLOWING DRAWINGS MUST HAVE THE REQUIRED DIGITAL
 SIGNATURES. FS 471/481
  
 M1.00
 M2.00
 P0.01
 P1.00
 P2.00
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By jleahy Date 2022-01-06 Time 14:44 Rev Time 0.00
Received By jleahy Date 2022-01-06 Time 14:32 Sent To  
Notes
2022-01-06 14:46:53ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NOT DIGITALLY SIGNED JLEAHY