Plan Review Details - Permit 21100604
| Plan Review Stops For Permit 21100604 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2021-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-12-03 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-12-03 |
Time |
10:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-10-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-26 |
Time |
14:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-26 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2021-10-26 14:56:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC R 311, 314, 315, REVISE PLAN TO SHOW ROOM | | | DESIGNATION. IT APPEARS THAT THIS CANNOT BE A SLEEPING | | | ROOM BECAUSE THE WINDOWS DO NOT APPEAR TO MEET | | | EMERGENCY ESCAPE AND RESCUE OPENING REQUIREMENTS. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2021-12-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-11 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-12-11 |
Time |
12:43 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-03 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-03 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2021-11-03 14:17:50 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) FBC R314 SMOKE ALARM IS REQUIRED PER FBC. | | | | | | PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED PER | | | CODE. SHOW ON PLAN ALL EXISTING ALARMS. IF NONE ARE | | | EXISTING OR NOT TO CODE, SHOW AS NEW INSTALLATIONS. FBC | | | R314.3, FBC 107.2.1 | | | | | | 2) LIGHTING OUTLET IS REQUIRED BY 210.70 OF THE NEC | | | | | | 210.70(A)(1) HABITABLE ROOMS. AT LEAST ONE WALL | | | SWITCH?CONTROLLED | | | LIGHTING OUTLET SHALL BE INSTALLED IN EVERY HABITABLE | | | ROOM, | | | KITCHEN, AND BATHROOM. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-12-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-11 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-30 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-03 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-27 |
Time |
06:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-06 |
Time |
06:12 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-06 |
Time |
06:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-12-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-12-03 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-12-03 |
Time |
10:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-11-03 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-03 |
Time |
14:18 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-03 |
Time |
14:18 |
Sent To |
|
|
| Notes |
| 2021-11-03 14:19:10 | PLAN IS REQUIRED TO BE SIGNED AND SEALED BY THE DESIGN | | | PROFESSIONAL RESPONSIBLE FOR THE DESIGN. FBC 107.2.1, | | | FS 471, 481 |
|
|
|