Plan Review Details - Permit 21100568
Plan Review Stops For Permit 21100568
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By cpuell Date 2021-10-29 Time 16:51 Rev Time 0.00
Received By cpuell Date 2021-10-29 Time 16:51 Sent To  
Notes
2021-10-29 16:52:207113 S FLAGLER DR ADDRESS ASSIGNED FOR THIS BUILDING

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 13:22 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 10:46 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2021-12-04 Cont ID  
Sent By cthroop Date 2021-12-04 Time 10:04 Rev Time 0.00
Received By cthroop Date 2021-12-04 Time 07:23 Sent To  
Notes
2021-12-04 10:18:27BUILDING PLAN REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 4TH REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE: PLAN PAGE A-1.1 STATES GARAGE HAS 665 SF.
  
 1. DESIGNER SHALL INDICATE ON ICC-ES REPORT THE MODEL
 OF THE FLOOD VENTS TO BE INSTALLED.
 THIS INFORMATION IS ALSO REQUIRED IN SECTION D,
 COMMENTS, OF THE ELEVATION CERTIFICATE. (SEE NFIP
 REVIEW)
 FBC 107.3.4 PRODUCTS WHICH ARE REGULATED BY FAC RULE
 9N-3 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD.
  
 2. PLAN PAGE A-1.1 INDICATES GARAGE HAS 665 SF. FLOOD
 VENTS LISTED ON ELEVATION CERTIFICATE INDICATE EACH
 VENT SHALL COVER 200SF. 4 FLOOD VENTS ARE REQUIRED.
 REVISE PLAN PAGE A-1.1.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 3. INDICATE ON PLAN PAGE A-1.1 THE TYPE OF FLOOD VENTS
 TO BE INSTALLED. THE LEGED "P" ON PLAN PAGE A-4.2
 STATES "FLOOD PANEL".
 THIS INFORMATION IS ALSO REQUIRED IN SECTION D,
 COMMENTS, OF THE ELEVATION CERTIFICATE. (SEE NFIP
 REVIEW)
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-19 Cont ID  
Sent By cthroop Date 2021-11-19 Time 09:34 Rev Time 0.00
Received By cthroop Date 2021-11-18 Time 16:57 Sent To  
Notes
2021-11-19 09:35:37PENDING APPROVAL OF NFIP REVIEW. CT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By cthroop Date 2021-11-09 Time 16:07 Rev Time 0.00
Received By cthroop Date 2021-11-09 Time 16:07 Sent To  
Notes
2021-11-09 16:08:46PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 2ND REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 NOTICE:
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE, REVIEWED
 AND APPROVED, IS REQUIRED PRIOR TO PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:10 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 09:31 Sent To  
Notes
2021-10-29 16:13:23PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PROVIDE SOILS REPORT. (NOT ADDRESSED)
 FBC 1803.1 GENERAL. GEOTECHNICAL INVESTIGATIONS SHALL
 BE CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND
 REPORTED IN ACCORDANCE WITH SECTION 1803.6.
  
 NOTICE:
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE, REVIEWED
 AND APPROVED, IS REQUIRED PRIOR TO PERMIT.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:33 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 09:31 Sent To  
Notes
2021-10-29 16:34:26SEE ELECTRICAL REVIEW UNDER 21060673 BY JL. CT

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-04 Cont ID  
Sent By cthroop Date 2021-12-04 Time 10:31 Rev Time 0.00
Received By cthroop Date 2021-12-04 Time 10:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-19 Cont ID  
Sent By cthroop Date 2021-11-19 Time 09:35 Rev Time 0.00
Received By cthroop Date 2021-11-15 Time 14:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-05 Cont ID  
Sent By ajones Date 2021-11-05 Time 14:01 Rev Time 0.00
Received By ajones Date 2021-10-14 Time 12:14 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-01-05 Cont ID  
Sent By lmarchan Date 2022-01-05 Time 08:40 Rev Time 0.00
Received By lmarchan Date 2022-01-05 Time 08:40 Sent To  
Notes
2022-01-05 08:40:56SEE 21060673

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:42 Rev Time 0.00
Received By cthroop Date 2021-10-29 Time 16:42 Sent To  
Notes
2021-10-29 16:43:27IMPACT FEE QUESTIONNAIRE
  
 PALM BEACH COUNTY IMPACT FEES - DIGITAL SUBMITTALS
  
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECT DOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. OUR PERMIT
 LIBRARIANS WILL SEND THE IMPACT FEE QUESTIONNAIRE TO
 THE PALM BEACH COUNTY IMPACT FEE OFFICE ON YOUR BEHALF.
 THE FORM CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZ
 B/ADMINISTRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
 UPON APPROVAL AND PAYMENT OF FEES, PLEASE UPLOAD THE
 RECEIPT TO PROJECT DOX OR EMAIL IT TO
 [email protected]
  
  

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 13:23 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 10:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 09:47 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 09:47 Sent To  
Notes
2021-12-03 09:49:09THE ENERGY CALCULATIONS AND EQUIPMENT SIZING
 CALCULATIONS SUBMITTED UNDER THE MASTER PERMIT,
 21060673, HAS THE WRONG ADDRESS. PLEASE RESUBMIT WITH
 THE CORRECT ADDRESS FOR THE COTTAGE.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-19 Cont ID  
Sent By medwards Date 2021-11-19 Time 09:07 Rev Time 0.00
Received By medwards Date 2021-11-19 Time 09:07 Sent To  
Notes
2021-11-19 09:07:52PLANS SUBMITTED UNDER PERMIT NUMBER 21060673.
  
 PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE GUEST APARTMENT MECHANICAL SYSTEM.
 FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By medwards Date 2021-10-26 Time 08:00 Rev Time 0.00
Received By medwards Date 2021-10-26 Time 08:00 Sent To  
Notes
2021-10-26 08:04:15PLANS SUBMITTED UNDER PERMIT NUMBER 21060673.
  
 PLEASE SUBMIT THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE GUEST APARTMENT MECHANICAL SYSTEM.
 FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 5 Status N Date 2022-01-05 Cont ID  
Sent By cthroop Date 2022-01-05 Time 13:21 Rev Time 0.00
Received By cthroop Date 2022-01-05 Time 10:46 Sent To  
Notes
2022-01-05 13:22:45DFE OF 2 STORY CABANA/GARAGE IS 8.0' NAVD. FF ELEVATION
 OF CABANA IS 8'6" NAVD. EC NOT REQUIRED. CT

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 4 Status F Date 2021-12-04 Cont ID  
Sent By cthroop Date 2021-12-04 Time 10:18 Rev Time 0.00
Received By cthroop Date 2021-12-04 Time 09:12 Sent To  
Notes
2021-12-04 10:30:38PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 4TH REVIEW
 RESULTS: FAILED
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE.
 (CABANA/GARAGE)
  
 1. SECTION A2. ADDRESS IS 7113 S FLAGLER DRIVE
  
 2. SECTION A9 (A). DATA ENTERED IS 560 SF. PLAN PAGE
 A-1.1 INDICATES GARAGE HAS 665 SF.
  
 3. SECTION A9 (B). BASED ON PLAN PAGE A-1.1 AND
 ALLOWING 200 SF PER VENT, 4 VENTS WILL BE REQUIRED.
  
 4. SECTION A9 (C). ASSUMING FLOOD VENTS INSTALLED WILL
 BE 8" X 16", IT IS CUSTOMARY TO ALLOT 128 SQ. IN. PER
 VENT.
  
 5. SECTION D, COMMENTS. INCLUDE TYPE AND MODEL NUMBER
 OF FLOOD VENTS INSTALLED.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
  
 GENERAL INFORMATION:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD.
 MAIN DWELLING UNIT IS LOCATED IN FLOOD ZONE AE 7 . BFE
 IS 7.0' NAVD. DFE SHALL NOT BE LESS THAN 9.0 FEET NAVD.
 FREE STANDING CABANA/GARAGE IS LOCATED IN FLOOD ZONE AE
 6. BFE IS 6.0' NAVD. DFE SHALL NOT BE LESS THAN 8.0'
 NAVD.
  
  
 NOTICE:
  
 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
 SUBMIT TO BUILDING DEPARTMENT FOR REVIEW.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
 NOTICE: A SEPERATE PERMIT AND ELEVATION CERTIFICATE ARE
 REQUIRED FOR THE MAIN RESIDENCE. (SEE PERMIT 21060673)
  
 NOTICE: PROVISO ON PLAN PAGE S-1.1
  
 NOTICE: PRINT HOLD FOR CONSTRUCTION DRAWING EC
  
 NOTICE: C/O HOLD FOR FINISHED CONSTRUCTION EC
  
 NOTICE: COMMENTS TO BE ADDED TO INSPECTION SCREEN AFTER
 INSPECTION HOLDS REMOVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 3 Status F Date 2021-11-18 Cont ID  
Sent By cthroop Date 2021-11-18 Time 16:58 Rev Time 0.00
Received By cthroop Date 2021-11-18 Time 16:57 Sent To  
Notes
2021-11-18 17:03:44PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 3RD REVIEW
 RESULTS: FAILED
  
 RE: CONSTRUCTION DRAWING ELEVATION CERTIFICATE.
 (CABANA/GARAGE)
  
 1. SECTION A7. BUILDING DIAGRAHM NUMBER SHOULD BE 1B.
 SEE DETAIL 1/S-1 PLAN PAGE S-1.1.
 CORRECT AND RE-SUBMIT.
  
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD.
 MAIN DWELLING UNIT IS LOCATED IN FLOOD ZONE AE 7 . BFE
 IS 7.0' NAVD. DFE SHALL NOT BE LESS THAN 9.0 FEET NAVD.
 FREE STANDING CABANA/GARAGE IS LOCATED IN FLOOD ZONE AE
 6. BFE IS 6.0' NAVD. DFE SHALL NOT BE LESS THAN 8.0'
 NAVD.
  
  
 NOTICE:
  
 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
 SUBMIT TO BUILDING DEPARTMENT FOR REVIEW.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
 NOTICE: A SEPERATE PERMIT AND ELEVATION CERTIFICATE ARE
 REQUIRED FOR THE MAIN RESIDENCE. (SEE PERMIT 21060673)
  
 NOTICE: PROVISO ON PLAN PAGE S-1.1
  
 NOTICE: PRINT HOLD FOR CONSTRUCTION DRAWING EC
  
 NOTICE: C/O HOLD FOR FINISHED CONSTRUCTION EC
  
 NOTICE: COMMENTS TO BE ADDED TO INSPECTION SCREEN AFTER
 INSPECTION HOLDS REMOVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By cthroop Date 2021-11-09 Time 16:04 Rev Time 0.00
Received By cthroop Date 2021-11-09 Time 16:04 Sent To  
Notes
2021-11-09 16:07:07PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 4TH REVIEW
  
  
 NOTICE: PROVIDE A CONSTRUCTION DRAWING ELEVATION
 CERTIFICATE.
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD.
 MAIN DWELLING UNIT IS LOCATED IN FLOOD ZONE AE 7 . BFE
 IS 7.0' NAVD. DFE SHALL NOT BE LESS THAN 9.0 FEET NAVD.
 FREE STANDING CABANA/GARAGE IS LOCATED IN FLOOD ZONE AE
 6. BFE IS 6.0' NAVD. DFE SHALL NOT BE LESS THAN 8.0'
 NAVD.
  
  
 NOTICE:
  
 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
 SUBMIT TO BUILDING DEPARTMENT FOR REVIEW.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
  
 NOTICE: A SEPERATE PERMIT AND ELEVATION CERTIFICATE ARE
 REQUIRED FOR THE MAIN RESIDENCE. (SEE PERMIT 21060673)
  
 NOTICE: PROVISO ON PLAN PAGE S-1.1
  
 NOTICE: PRINT HOLD FOR CONSTRUCTION DRAWING EC
  
 NOTICE: C/O HOLD FOR FINISHED CONSTRUCTION EC
  
 NOTICE: COMMENTS TO BE ADDED TO INSPECTION SCREEN AFTER
 INSPECTION HOLDS REMOVED.

Review Stop NFIP NFIP REVIEW ACTIVITY
Rev No 1 Status F Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:44 Rev Time 0.00
Received By cthroop Date 2021-10-29 Time 16:43 Sent To  
Notes
2021-10-29 16:45:46PLAN REVIEW / NFIP
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 CITY ORDINANCE NO. 4658-16
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 NOTICE:
  
 PROPERTY IS LOCATED IN A SPECIAL FLOOD HAZARD AREA
 (SFHA). IT IS LOCATED IN FLOOD ZONE AE WITH BASE FLOOD
 ELEVATIONS OF 6.0 FEET AND 7.0 FEET NAVD.
 DESIGN FLOOD ELEVATION OF MAIN DWELLING UNIT SHALL NOT
 BE LESS THAN 9.0 FEET NAVD. FREE STANDING GARAGE,
 LOCATED IN SFHA W/BFE 6.0' NAVD.
  
  
 3 ELEVATION CERTIFICATES (EC) ARE REQUIRED
  
 A CONSTRUCTION DRAWING ELEVATION CERTIFICATE IS
 REQUIRED AT TIME OF PERMIT APPLICATION.
  
 A BUILDING UNDER CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AT PLACEMENT OF 1ST FLOOR.
 SUBMIT TO BUILDING DEPARTMENT FOR REVIEW.
  
 A FINISHED CONSTRUCTION ELEVATION CERTIFICATE IS
 REQUIRED AND SHALL BE SUBMITTED FOR REVIEW AND APPROVAL
 PRIOR TO THE ISSUANCE OF THE CERTIFICATE OF OCCUPANCY.
 NOTE: YOU MAY SUBMIT THIS EC FOR REVIEW AFTER FINAL
 GRADE AND PLACEMENT OF EQUIPMENT SERVICING THE
 BUILDING.
  
 NOTICE: PRINT HOLD FOR CONSTRUCTION DRAWING EC
  
 NOTICE: C/O HOLD FOR FINISHED CONSTRUCTION EC
  
 NOTICE: COMMENTS TO BE ADDED TO INSPECTION SCREEN AFTER
 INSPECTION HOLDS REMOVED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:34 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 09:31 Sent To  
Notes
2021-10-29 16:35:06SEE PLUMBING REVIEW UNDER 21060673 BY LC. CT

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:40 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 09:31 Sent To  
Notes
2021-10-29 16:41:23PROVISO ON PLAN PAGE A-3.1:
 A SEPERATE ROOFING PERMIT IS REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-12-04 Cont ID  
Sent By cthroop Date 2021-12-04 Time 09:12 Rev Time 0.00
Received By cthroop Date 2021-12-04 Time 09:12 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-19 Cont ID  
Sent By cthroop Date 2021-11-19 Time 09:35 Rev Time 0.00
Received By cthroop Date 2021-11-18 Time 16:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By cthroop Date 2021-10-29 Time 16:41 Rev Time 0.00
Received By cthroop Date 2021-10-26 Time 09:31 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By av Date 2021-11-05 Time 14:01 Rev Time 0.00
Received By ajones Date 2021-11-05 Time 14:01 Sent To  
Notes
***NONE***