Plan Review Details - Permit 21100551
Plan Review Stops For Permit 21100551
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By jleahy Date 2021-11-01 Time 13:49 Rev Time 0.00
Received By jleahy Date 2021-11-01 Time 13:49 Sent To  
Notes
2021-11-01 13:56:17ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS NEED TO BE DESIGNED BY AN ENGINEER BECAUSE OF THE
 480 VOLTS, THIS LEVEL OF POWER IS NOT COVERED BY AN
 ELECTRICAL CONTRACTORS LICENSE FOR DESIGN.
  
 471.003 (H) ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING,
 OR MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE
 DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING,
 AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY,
 WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED
 UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR
 UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY
 CONSTRUCTION PROJECT WHICH:
 1.?REQUIRES AN ELECTRICAL OR PLUMBING OR
 AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE
 OF $125,000 OR LESS; AND
 2.A.?REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600
 AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL
 SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A
 COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM;
  
 PLEASE INCLUDE A VOLTAGE DROP CALCULATION FOR THE 550'
 OF CONDUCTOR.
  
 INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY CODE.
 A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE INDICATION OF
 SUBMITTAL OF COMPLETION DOCUMENTS PER FBC C405.7.4 FBC
 C405.7.3

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-01 Cont ID  
Sent By jleahy Date 2021-11-01 Time 14:00 Rev Time 0.00
Received By jleahy Date 2021-10-13 Time 13:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-01 Cont ID  
Sent By jleahy Date 2021-11-01 Time 14:01 Rev Time 0.00
Received By jleahy Date 2021-11-01 Time 14:01 Sent To  
Notes
2021-11-01 14:02:07PLAN NEEDS TO BE SIGNED BY AN ENGINNER
  
 471.003 (H) SEE ELECTRICAL COMMENTS