| 2021-11-01 13:56:17 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | FLORIDA BUILDING CODE 2020 7TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED |
| | NFPA 70 2017 EDITION |
| | |
| | JAKE LEAHY BN, BU, PX |
| | ELECTRICAL PLANS EXAMINER II |
| | 561-805-6713 |
| | [email protected] |
| | |
| | PLANS NEED TO BE DESIGNED BY AN ENGINEER BECAUSE OF THE |
| | 480 VOLTS, THIS LEVEL OF POWER IS NOT COVERED BY AN |
| | ELECTRICAL CONTRACTORS LICENSE FOR DESIGN. |
| | |
| | 471.003 (H) ANY ELECTRICAL, PLUMBING, AIR-CONDITIONING, |
| | OR MECHANICAL CONTRACTOR WHOSE PRACTICE INCLUDES THE |
| | DESIGN AND FABRICATION OF ELECTRICAL, PLUMBING, |
| | AIR-CONDITIONING, OR MECHANICAL SYSTEMS, RESPECTIVELY, |
| | WHICH SHE OR HE INSTALLS BY VIRTUE OF A LICENSE ISSUED |
| | UNDER CHAPTER 489, UNDER PART I OF CHAPTER 553, OR |
| | UNDER ANY SPECIAL ACT OR ORDINANCE WHEN WORKING ON ANY |
| | CONSTRUCTION PROJECT WHICH: |
| | 1.?REQUIRES AN ELECTRICAL OR PLUMBING OR |
| | AIR-CONDITIONING AND REFRIGERATION SYSTEM WITH A VALUE |
| | OF $125,000 OR LESS; AND |
| | 2.A.?REQUIRES AN AGGREGATE SERVICE CAPACITY OF 600 |
| | AMPERES (240 VOLTS) OR LESS ON A RESIDENTIAL ELECTRICAL |
| | SYSTEM OR 800 AMPERES (240 VOLTS) OR LESS ON A |
| | COMMERCIAL OR INDUSTRIAL ELECTRICAL SYSTEM; |
| | |
| | PLEASE INCLUDE A VOLTAGE DROP CALCULATION FOR THE 550' |
| | OF CONDUCTOR. |
| | |
| | INDICATE VOLTAGE DROP COMPLIANCE WITH FBC ENERGY CODE. |
| | A NOTE WILL SUFFICE. NOTE SHOULD INCLUDE INDICATION OF |
| | SUBMITTAL OF COMPLETION DOCUMENTS PER FBC C405.7.4 FBC |
| | C405.7.3 |