Plan Review Details - Permit 21100347
Plan Review Stops For Permit 21100347
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-12-30 Cont ID  
Sent By rmcphers Date 2021-12-30 Time 10:22 Rev Time 0.00
Received By rmcphers Date 2021-12-30 Time 10:22 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 16:31 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 16:13 Sent To  
Notes
2021-11-15 16:32:01PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-12-30 Cont ID  
Sent By rmcphers Date 2021-12-30 Time 10:22 Rev Time 0.00
Received By rmcphers Date 2021-12-30 Time 10:22 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 16:32 Rev Time 0.00
Received By rmcphers Date 2021-11-15 Time 16:13 Sent To  
Notes
2021-11-15 16:38:29OFFICE ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) ACCESSIBLE RESTROOM - FOR THE MIRROR LOCATION -
 PLEASE USE "REFLECTIVE SURFACE" IN PLACE OF MIRROR OR
 GLASS FBC 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-25 Cont ID  
Sent By jleahy Date 2021-10-25 Time 08:26 Rev Time 0.00
Received By jleahy Date 2021-10-25 Time 08:26 Sent To  
Notes
***NONE***

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 2 Status P Date 2022-02-03 Cont ID  
Sent By jleahy Date 2022-02-03 Time 16:00 Rev Time 0.00
Received By jleahy Date 2022-02-03 Time 16:00 Sent To  
Notes
2022-02-03 16:01:04PHONE AND DATA JLEAHY

Review Stop E-LOWVOLT ELECTRICAL LOW VOLTAGE
Rev No 1 Status P Date 2021-10-25 Cont ID  
Sent By jleahy Date 2021-10-25 Time 08:33 Rev Time 0.00
Received By jleahy Date 2021-10-25 Time 08:33 Sent To  
Notes
2021-10-25 08:33:24VOICE AND DATA JLEAHY

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-12-29 Cont ID  
Sent By clfranci Date 2021-12-29 Time   Rev Time 0.00
Received By clfranci Date 2021-12-29 Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-12 Cont ID  
Sent By pleduc Date 2021-10-12 Time   Rev Time 0.00
Received By pleduc Date 2021-10-12 Time 14:22 Sent To  
Notes
2021-10-12 14:23:13FIRE PROVISO:
  
 THE FIRE SPRINKLER & FIRE ALARM SYSTEMS SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-03 Cont ID  
Sent By lcrespo Date 2022-01-03 Time 15:27 Rev Time 0.00
Received By lcrespo Date 2021-12-27 Time 16:07 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-15 Cont ID  
Sent By rmcphers Date 2021-11-15 Time 16:38 Rev Time 0.00
Received By rmcphers Date 2021-10-08 Time 13:24 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-29 Cont ID  
Sent By medwards Date 2021-12-29 Time 13:13 Rev Time 0.00
Received By medwards Date 2021-12-29 Time 13:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By medwards Date 2021-10-19 Time 06:29 Rev Time 0.00
Received By medwards Date 2021-10-19 Time 06:29 Sent To  
Notes
2021-10-19 06:30:181ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100347
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M 2.1: PLEASE PROVIDE DUCT SIZES FOR ALL
 DUCTWORK IN THIS PROJECT.
  
 2) SHEET A120 INDICATES A 1 HR TENANT SEPARATION WALL
 AT THE SOUTH END OF THIS BUILDING BUT SHEET M 2.1
 INDICATES A 12 X 12 O/A INTAKE LOCATED IN THE OTHER
 TENANT?S SPACE. PLEASE SHOW THIS O/A INTAKE GOING TO
 THE EXTERIOR OF THE BUILDING AND PROVIDE A FIRE DAMPER
 AT THE PENETRATION OF THIS DUCT AT THE 1 HR RATED WALL.
 FBC M 403.2.1, 607
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE IN THIS TENANT SPACE ACCORDING TO FBC M
 403.3.1.1 AND TABLE 403.3.1.1
  
 4) PLEASE SHOW THAT THE BATHROOM EXHAUST MEETS THE 10
 FT. DISTANCE FROM THE EXTERIOR BREAK ROOM ENTRY DOOR.
 FBC M 501.3.1
  
 5) PLEASE SHOW THE BATH EXHAUST TERMINATION LOCATION
 FOR RESTROOM 119. FBC M 501.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-01-03 Cont ID  
Sent By lcrespo Date 2022-01-03 Time 15:26 Rev Time 0.00
Received By lcrespo Date 2022-01-03 Time 13:48 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-02 Cont ID  
Sent By cthroop Date 2021-11-02 Time 08:52 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:19 Sent To  
Notes
2021-11-02 08:53:09CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21100347 5670 CORPORATE WAY # 13
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS OR
 OTHER ITEMS NOTED ON ARCHITECTURAL PLANS MUST BE
 SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE FINISH
 FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19 INCHES
 (485 MM) MAXIMUM MEASURED TO THE TOP OF THE SEAT, NOT
 THE FIXTURE RIM. SEATS SHALL NOT BE SPRUNG TO RETURN TO
 A LIFTED POSITION PER FBC ACC 604.4.
  
 2.PER WPB FBC 107.2.1, PROVIDE FINISH WALL SCHEDULE FOR
 REMODELED BATHROOM AND FOR JANITOR SINK CLOSET. REFER
 TO FBC PL 310.3 AND FBC 1210.2.2. WALLS AND PARTITIONS
 WITHIN 2 FEET (610 MM) OF SERVICE SINKS, URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE, TO A HEIGHT OF NOT LESS THAN 4 FEET (1219 MM)
 ABOVE THE FLOOR, AND EXCEPT FOR STRUCTURAL ELEMENTS,
 THE MATERIALS USED IN SUCH WALLS SHALL BE OF A TYPE
 THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. PLEASE NOTE
 THAT FBC 1210.2.2 STIPULATES THAT THE MATERIAL BE
 "HARD." THE INTENT OF THIS SECTION IS THAT THE
 SURROUNDING MATERIAL SHOULD NOT BE OF A TYPE THAT IS
 EASILY DAMAGED SUCH THAT THE MATERIAL COULD BECOME
 ABSORBENT AND THUS, NOT READILY CLEANABLE AND
 SANITIZED. PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS, DOES NOT MEET THE INTENT OF
 SECTION 1210.2.2. THE TYPICAL MATERIALS USED FOR THIS
 APPLICATION ARE CERAMIC TILE, FIBERGLASS REINFORCED
 PLASTIC (FRP) PANELS, PHENOLIC PANELS, LAMINATED
 PLASTIC PANELS, PAINTED STEEL AND STAINLESS STEEL.
  
 3.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 4.PER FBC PL 909.1, PROVIDE A VENT FOR THE WATER
 CLOSET. PLEASE NOTE THAT IF PROVIDING A WET VENT FOR
 THE WATER CLOSET, PER FBC PL 912.1, ONLY THE LAVATORY
 MAY BE INSTALLED ON THE WET VENT. IF INDIVIDUALLY VENT
 IN ACCORDANCE WITH FBC PL 910.1. THE VENT MUST RISE
 VERTICALLY ABOVE THE CENTERLINE OF THE DRAIN TO A POINT
 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE WATER CLOSET
 PER FBC PL 905.3 AND 905.4.
  
 5.RE: P0.1/WATER HEATER DETAIL: PER WPB FBC 107.2.1,
 PROVIDE THE FOLLOWING
 ?A) SPECIFICATION FOR THE EXPANSION VALVE (LEAD FREE)
 ?B) DIRECTION FOR EXPANSION VALVE DISCHARGE INCLUDING
 TERMINATION.
 ?C) SPECIFIC DIRECTION FOR RELIEF VALVE DISCHARGE AND
 PAN DRAIN (INCLUDING TERMINATION); COMPLY WITH FBC PL
 504.6(1-14) AND 504.7.2. PLEASE NOTE THAT A WASTE
 RECEPTOR BY DEFINITION (FBC PL SECTION 202) IS A FLOOR
 SINK, STANDPIPE, HUB DRAIN OR FLOOR DRAIN THAT RECEIVES
 THE DISCHARGE OF ONE OR MORE INDIRECT WASTE PIPES. A
 MOP BASIN DOES NOT FIT THIS DESCRIPTION.
  
 6.IT IS NOTED THAT THE HOT WATER TO THE BREAK ROOM SINK
 HAS AN ISOLATION VALVE IN THE LINE. THIS IS A
 RECIRCULATED LINE WHICH WILL NOT FUNCTION IF THE
 ISOLATION VALVE IS CLOSED. PLEASE NOTE THAT THE
 REQUIREMENT FOR A FULL OPEN VALVE AS NOTED IN FBC PL
 606.1(5) IS NOT APPLICABLE AS WPB BUILDING FOLLOWS THE
 INTERPRETATION OF IBC PLUMBING COMMENTARY 606.1(5)
 WHICH STATES A WATER PIPE EXTENDING VERTICALLY THROUGH
 ONE OR MORE FLOORS AND CONVEYING WATER VERTICALLY
 DOWNWARD IS CONSIDERED A DOWN-FEED. VALVES AT THE TOP
 OF DOWN-FEEDS ARE HELPFUL FOR SERVICING MULTI-STORY
 BUILDING SO THAT ONLY SMALL AREAS OF THE BUILDING WILL
 BE WITHOUT WATER TO FACILITATE REPAIRS IN ONE AREA.
  
 7.PER WPB FBC 107.2.1, INDICATE HOW THE PLUMBING FOR
 THE TOILET ROOM THAT IS NOT BEING REMODELED IS
 INTEGRATED WITH THE NEW WORK.
 ?A) DOES EXISTING SANITARY TIE INTO NEW SANITARY
 (INDICATE POINTS OF CONNECTION) OR THE OTHER WAY AROUND
 OR SEPARATE TO BUILDING SEWER
 ?B) DOES EXISTING WATER (HOT AND COLD) CONNECT TO NEW
 (INDICATE POINTS OF CONNECTION) OR THE OTHER WAY AROUND
 OR SEPARATE TO WATER MAIN.
 ?C) EXISTING BACKFLOW PREVENTER, NEW BACKFLOW
 PREVENTER? PROVIDE NOTE. SPECIFY AND PROVIDE DETAIL IF
 APPLICABLE
  
 7.RE: P2.0/KEY NOTE 1; PER WPB FBC 107.2.1, AMEND NOTE
 TO STATE NEW TOILET TO BE LOCATED AS REQUIRED BY
 FLORIDA ACCESSIBILITY CODE 604.2
  
 8.RE: P3.0/KEY NOTE 1; PER WPB FBC 107.2.1, AMEND NOTE
 TO STATE NEW TOILET TO BE LOCATED AS REQUIRED BY
 FLORIDA ACCESSIBILITY CODE 604.2
  
 9.AC CONDENSATE APPEARS TO BE EXISTING ACCORDING TO
 M0.1/SPECIAL NOTE TO HVAC CONTRACTOR. P0.1 PROVIDES
 DETAIL FOR A CONDENSATE DRY WELL, A CONDENSATE PUMP IS
 SCHEDULED AND THERE ARE MATERIAL SPECIFICATIONS. PER
 WPB FBC 107.2.1, PLEASE CLARIFY.
  
 10.PER WPB FBC 107.2.1, SCHEDULE AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3 AS REQUIRED BY FBC PL 419.5 FOR THE
 SCHEDULED ADA LAVATORY AND PROVIDE A DETAIL FOR THE
 SAME.
  
 11.PER WPB FBC 107.2.1, PROVIDE FIXTURE SCHEDULE WITH
 DFU AND DRAIN SIZE/WSFU AND CONNECTION SIZE
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21100347 5670 CORPORATE WAY # 13
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-12-30 Cont ID  
Sent By rmcphers Date 2021-12-30 Time 10:22 Rev Time 0.00
Received By rmcphers Date 2021-12-30 Time 10:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 14:31 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 14:31 Sent To  
Notes
2021-10-25 14:36:30IT APPEARS ARCHITECH, STEVEN MYOTT'S, DIGITAL SIGNATURE
 ON PLAN TITLED,006 A120- EGRESS & FURNITURE PLAN, IS
 COMING BACK INVALID. PLEASE CORRECT THIS ISSUE BY
 FOLLOWING THE DIRECTIONS BELOW.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
  