Plan Review Details - Permit 21100336
Plan Review Stops For Permit 21100336
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-21 Cont ID  
Sent By rmcdouga Date 2022-04-21 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2022-04-21 Time 08:20 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-04-21 Cont ID  
Sent By rmcdouga Date 2022-04-21 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2022-04-21 Time 07:55 Sent To  
Notes
2022-04-21 07:55:10PLAN
 REVIEW COMMENTS
 3RD REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE NEW SURVEY THAT WAS SUBMITTED, WITH THE
 GENERATOR EXHAUST 10' FROM OPENINGS INTO A BUILDING
 NOTE. HAS THE GENERATOR DRAWN INSIDE THE DWELLING.
 SUBMIT A CORRECTED SURVEY. FBC 107.2.1 & FBC-R303.5

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 08:27 Sent To  
Notes
2022-03-14 08:31:41PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) RESOLVED.
  
 2) NOT RESOLVED. [ THE ENGINEER'S DIGITAL SIGNATURE
 COULD NOT BE RESOLVED. SEE SIGNATURE REVIEW. ] SUBMIT
 SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE
 PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2
  
 3) NOT RESOLVED, [ I DID NOT SEE THE NOTE ON THE
 SURVEY. ] NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST
 IS REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A
 BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By rmcdouga Date 2021-11-17 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2021-11-17 Time 09:56 Sent To  
Notes
2021-11-17 09:49:42PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE
 GENERATOR. FBC 107.2.1
  
 2) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING
 FOR THE PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2
  
 3) NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST IS
 REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A
 BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND
 GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED
 NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR
 NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING
 VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS.
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-04-20 Cont ID  
Sent By jleahy Date 2022-04-20 Time 13:15 Rev Time 0.00
Received By jleahy Date 2022-04-20 Time 11:46 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By mpeterso Date 2022-03-31 Time 10:41 Rev Time 0.00
Received By mpeterso Date 2022-03-31 Time 10:41 Sent To  
Notes
2022-03-31 10:42:32ELECTRIC REVIEW FAILED
 1) PREVIOUS COMMENTS NOT ADDRESSED
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-06 Cont ID  
Sent By jleahy Date 2021-11-06 Time 16:42 Rev Time 0.00
Received By jleahy Date 2021-11-06 Time 16:42 Sent To  
Notes
2021-11-06 16:45:09ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED A COMPLETE RISER DIAGRAM SHOWING MAIN AND PANEL(S)
 AND THE LOCATIONS. 215;5
  
 PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5;
 FBC 107.2.1
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By lcrespo Date 2022-03-14 Time 09:25 Rev Time 0.00
Received By lcrespo Date 2022-03-14 Time 09:25 Sent To  
Notes
2022-03-14 09:26:33GAS PERMIT UNDER 21100573

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By abelisle Date 2021-10-19 Time 20:16 Rev Time 0.00
Received By abelisle Date 2021-10-19 Time 19:40 Sent To  
Notes
2021-10-19 19:44:371ST REVIEW FBC-2020 PLUMBING
 PERMIT-21100336
 10/19/21
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) ADDRESS ON PERMIT APPLICATIONS IS INCORRECT ACTUAL
 ADDRESS IS 6098 WILDCAT RUN. PLEASE SUBMIT NEW PERMIT
 APPLICATIONS TO REFLECT THE ACTUAL PROPERTY ADDRESS
 WHERE THE WORK IS GOING TO BE PERFORMED.WPB AMENDMENTS
 TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2) THE GAS REVIEW IS BEING DONE UNDER PERMIT #21100573
 3) THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?)
 FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-21 Cont ID  
Sent By rmcdouga Date 2022-04-21 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2022-04-01 Time 10:25 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-31 Cont ID  
Sent By mpeterso Date 2022-03-31 Time 10:42 Rev Time 0.00
Received By mpeterso Date 2022-03-08 Time 07:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-17 Cont ID  
Sent By rmcdouga Date 2021-11-17 Time 09:56 Rev Time 0.00
Received By rmcdouga Date 2021-10-14 Time 06:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2022-03-14 Cont ID  
Sent By lcrespo Date 2022-03-14 Time 09:25 Rev Time 0.00
Received By lcrespo Date 2022-03-14 Time 09:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-10-19 Cont ID  
Sent By abelisle Date 2021-10-19 Time 19:40 Rev Time 0.00
Received By abelisle Date 2021-10-19 Time 19:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-21 Cont ID  
Sent By rmcdouga Date 2022-04-21 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2022-04-21 Time 07:55 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rmcdouga Date 2022-03-14 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2022-03-14 Time 07:55 Sent To  
Notes
2022-03-14 07:59:12THE ENGINEER'S SIGNATURE ON THE GENERATOR PAD DRAWING
 COULD NOT BE VERIFIED. COPIES OF ELECTRONICALLY SIGNED
 PLANS ARE NOT ACCEPTABLE. ELECTRONICALLY SUBMITTED
 DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR
 ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE
 OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF
 DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN
 APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER
 DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE
 ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE
 AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO
 PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE
 ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-17 Cont ID  
Sent By rmcdouga Date 2021-11-17 Time 09:36 Rev Time 0.00
Received By rmcdouga Date 2021-11-17 Time 09:36 Sent To  
Notes
2021-11-17 09:37:50ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE
 THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM.
 YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND
 SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC
 PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE
 CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT
 TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL
 HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE
 DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE
 SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15

Review Stop Z ZONING
Rev No 3 Status P Date 2022-04-08 Cont ID  
Sent By asangele Date 2022-04-08 Time   Rev Time 0.00
Received By asangele Date 2022-04-08 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By asangele Date 2022-03-14 Time   Rev Time 0.00
Received By asangele Date 2022-03-14 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-27 Cont ID  
Sent By aaponte Date 2021-10-27 Time   Rev Time  
Received By rthermid Date 2021-10-27 Time   Sent To I
Notes
2021-10-27 10:47:46ON THE SUBMITTED SURVEY, PROVIDE THE SETBACKS OF THE
 PROPOSED GENERATOR TO ALL PROPERTY LINES. PER THE CITY
 ZONING CODE, MECHANICAL EQUIPMENT CANNOT ENCROACH MORE
 THAN 4 FEET INTO A REQUIRED SETBACK.
  
 RAFAELA THERMIDOR, ASSOCIATE PLANNER
 [email protected]
  