| Plan Review Stops For Permit 21100336 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-21 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-21 |
Time |
08:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-21 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-21 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2022-04-21 07:55:10 | PLAN | | | REVIEW COMMENTS | | | 3RD REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE NEW SURVEY THAT WAS SUBMITTED, WITH THE | | | GENERATOR EXHAUST 10' FROM OPENINGS INTO A BUILDING | | | NOTE. HAS THE GENERATOR DRAWN INSIDE THE DWELLING. | | | SUBMIT A CORRECTED SURVEY. FBC 107.2.1 & FBC-R303.5 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-14 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-14 |
Time |
08:27 |
Sent To |
|
|
| Notes |
| 2022-03-14 08:31:41 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) RESOLVED. | | | | | | 2) NOT RESOLVED. [ THE ENGINEER'S DIGITAL SIGNATURE | | | COULD NOT BE RESOLVED. SEE SIGNATURE REVIEW. ] SUBMIT | | | SIGNED AND SEALED SITE SPECIFIC ENGINEERING FOR THE | | | PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2 | | | | | | 3) NOT RESOLVED, [ I DID NOT SEE THE NOTE ON THE | | | SURVEY. ] NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST | | | IS REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A | | | BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-11-17 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-11-17 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2021-11-17 09:49:42 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT THE MANUFACTURER'S SPECIFICATIONS FOR THE | | | GENERATOR. FBC 107.2.1 | | | | | | 2) SUBMIT SIGNED AND SEALED SITE SPECIFIC ENGINEERING | | | FOR THE PRE-FABRICATED GENERATOR PAD. FBC 107.2.1.2 | | | | | | 3) NOTE ON THE SURVEY THAT THE GENERATOR EXHAUST IS | | | REQUIRED TO BE AT LEAST 10 FEET FROM OPENINGS INTO A | | | BUILDING. R303.5.1 INTAKE OPENINGS. MECHANICAL AND | | | GRAVITY OUTDOOR AIR INTAKE OPENINGS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET (3048 MM) FROM ANY HAZARDOUS OR | | | NOXIOUS CONTAMINANT, SUCH AS VENTS, CHIMNEYS, PLUMBING | | | VENTS, STREETS, ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2022-04-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-04-20 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-04-20 |
Time |
11:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-31 |
Time |
10:41 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-31 |
Time |
10:41 |
Sent To |
|
|
| Notes |
| 2022-03-31 10:42:32 | ELECTRIC REVIEW FAILED | | | 1) PREVIOUS COMMENTS NOT ADDRESSED | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-11-06 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-06 |
Time |
16:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-06 |
Time |
16:42 |
Sent To |
|
|
| Notes |
| 2021-11-06 16:45:09 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | NEED A COMPLETE RISER DIAGRAM SHOWING MAIN AND PANEL(S) | | | AND THE LOCATIONS. 215;5 | | | | | | PROVIDE RISER DIAGRAM OF EXISTING SERVICE. NEC 215.5; | | | FBC 107.2.1 | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-14 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-14 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2022-03-14 09:26:33 | GAS PERMIT UNDER 21100573 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-10-19 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-10-19 |
Time |
20:16 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-10-19 |
Time |
19:40 |
Sent To |
|
|
| Notes |
| 2021-10-19 19:44:37 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21100336 | | | 10/19/21 | | | | | | CODES IN EFFECT: | | | | | | FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020 | | | FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH | | | EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH | | | EDITION 2020 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) ADDRESS ON PERMIT APPLICATIONS IS INCORRECT ACTUAL | | | ADDRESS IS 6098 WILDCAT RUN. PLEASE SUBMIT NEW PERMIT | | | APPLICATIONS TO REFLECT THE ACTUAL PROPERTY ADDRESS | | | WHERE THE WORK IS GOING TO BE PERFORMED.WPB AMENDMENTS | | | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS. | | | 2) THE GAS REVIEW IS BEING DONE UNDER PERMIT #21100573 | | | 3) THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?) | | | FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE, | | | EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS | | | OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION | | | INSTRUCTIONS. | | | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION | | | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | | COOPERATION. | | | | | | ATELYO BELISLE | | | PLUMBING INSPECTOR / | | | PLUMBING PLAN REVIEW | | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | | [email protected] | | | 561-805-6695 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-21 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-01 |
Time |
10:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-31 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-03-31 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-03-08 |
Time |
07:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-11-17 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-10-14 |
Time |
06:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
N |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-03-14 |
Time |
09:25 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-03-14 |
Time |
09:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2021-10-19 |
|
|
Cont ID |
|
| Sent By |
abelisle |
Date |
2021-10-19 |
Time |
19:40 |
Rev Time |
0.00 |
| Received By |
abelisle |
Date |
2021-10-19 |
Time |
19:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-04-21 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-04-21 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-04-21 |
Time |
07:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-14 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-14 |
Time |
07:55 |
Sent To |
|
|
| Notes |
| 2022-03-14 07:59:12 | THE ENGINEER'S SIGNATURE ON THE GENERATOR PAD DRAWING | | | COULD NOT BE VERIFIED. COPIES OF ELECTRONICALLY SIGNED | | | PLANS ARE NOT ACCEPTABLE. ELECTRONICALLY SUBMITTED | | | DRAWINGS ARE REQUIRED TO HAVE THE ARCHITECT OR | | | ENGINEER'S DIGITAL SIGNATURE ON THEM. YOU ALSO HAVE THE | | | OPTION TO SUBMIT THE SIGNED AND SEALED PAPER VERSION OF | | | DRAWINGS. AFTER THE ELECTRONIC PLANS HAVE BEEN | | | APPROVED, YOU CAN SUBMIT THE CORRESPONDING PAPER | | | DRAWINGS AT THE BUILDING DEPARTMENT TO BE VERIFIED. THE | | | ARCHITECT OR ENGINEER'S ORIGINAL HANDWRITTEN SIGNATURE | | | AND SEAL IS REQUIRED TO BE ON THE DRAWINGS. NO | | | PHOTOCOPY OR OTHER FACSIMILES OF THE SIGNATURE ARE | | | ACCEPTABLE. FS 487 & 61G1 OR FS 471 & 61G15 |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-11-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-11-17 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-11-17 |
Time |
09:36 |
Sent To |
|
|
| Notes |
| 2021-11-17 09:37:50 | ELECTRONICALLY SUBMITTED DRAWINGS ARE REQUIRED TO HAVE | | | THE ARCHITECT OR ENGINEER'S DIGITAL SIGNATURE ON THEM. | | | YOU ALSO HAVE THE OPTION TO SUBMIT THE SIGNED AND | | | SEALED PAPER VERSION OF DRAWINGS. AFTER THE ELECTRONIC | | | PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT THE | | | CORRESPONDING PAPER DRAWINGS AT THE BUILDING DEPARTMENT | | | TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S ORIGINAL | | | HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO BE ON THE | | | DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF THE | | | SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 & | | | 61G15 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-04-08 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-04-08 |
Time |
|
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-04-08 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
asangele |
Date |
2022-03-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
asangele |
Date |
2022-03-14 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-10-27 |
|
|
Cont ID |
|
| Sent By |
aaponte |
Date |
2021-10-27 |
Time |
|
Rev Time |
|
| Received By |
rthermid |
Date |
2021-10-27 |
Time |
|
Sent To |
I |
|
| Notes |
| 2021-10-27 10:47:46 | ON THE SUBMITTED SURVEY, PROVIDE THE SETBACKS OF THE | | | PROPOSED GENERATOR TO ALL PROPERTY LINES. PER THE CITY | | | ZONING CODE, MECHANICAL EQUIPMENT CANNOT ENCROACH MORE | | | THAN 4 FEET INTO A REQUIRED SETBACK. | | | | | | RAFAELA THERMIDOR, ASSOCIATE PLANNER | | | [email protected] | | | |
|
|