Plan Review Details - Permit 21100241
| Plan Review Stops For Permit 21100241 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-04-05 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-05 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2022-04-05 16:51:54 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-04-05 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-05 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2022-04-05 16:51:14 | GENERATOR | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE STRUCTURAL DRAWINGS SHOWING THE | | | SLAB DETAIL AND GENERATOR FOUNDATION ATTACHMENT. FBC | | | WPB 107.2.1 | | | | | | 2) PLEASE SHOW THE WIND DESIGN DATA USED FOR THE DESIGN | | | PER FBC 1603.1.4 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-04-06 |
Time |
08:18 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-04-06 |
Time |
08:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
clfranci |
Date |
2022-02-18 |
Time |
|
Rev Time |
0.00 |
| Received By |
clfranci |
Date |
2022-02-18 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-02-18 14:52:03 | THIS PLAN WAS REVIEWED AND PASSED BY CAITLIN L. | | | FRANCIS, FIRE INVESTIGATOR, WITH THE FOLLOWING COMENT: | | | 1) ALL FIRE ALARM DEVICES WILL BE TESTED DURING FIELD | | | INSPECTION. | | | CAITLIN L. FRANCIS | | | FIRE INVESTIGATOR | | | 561-804-4728 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-04-06 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2022-04-06 |
Time |
08:19 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2022-02-17 |
Time |
11:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-16 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-16 |
Time |
16:18 |
Sent To |
|
|
| Notes |
| 2022-03-16 16:24:17 | MECHANICAL APROVED WITH PRIVISO BELOW. | | | THERE MUST BE A SEPARATE REVIEW AND PERMIT FOR THE | | | DIESEL GENERATOR INSTALL. ME |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-04-05 |
Time |
16:52 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-04-05 |
Time |
16:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-25 |
Time |
12:26 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-25 |
Time |
12:26 |
Sent To |
|
|
| Notes |
| 2022-02-25 12:28:49 | 2/25/2022 **** FAILED **** | | | | | | PLEASE PROVIDE A SITEPLAN/SURVEY THAT INDICATES THE | | | MECHANICAL EQUIPTMENT'S LOCATION, PLEASE NOTE THE | | | SETBACKS FOR EACH MECHANICAL EQUIPMENT | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
|