Plan Review Details - Permit 21100214
Plan Review Stops For Permit 21100214
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-31 Cont ID  
Sent By jleahy Date 2021-10-31 Time 09:59 Rev Time 0.00
Received By cpuell Date 2021-10-31 Time 09:59 Sent To  
Notes
2021-10-31 10:00:12HABITABLE STRUCTURE GIVEN ADDRESS OF 241 MURRAY RD

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:36 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 09:18 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-08 Cont ID  
Sent By cthroop Date 2022-01-08 Time 08:11 Rev Time 0.00
Received By cthroop Date 2022-01-08 Time 07:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By cthroop Date 2021-10-25 Time 16:37 Rev Time 0.00
Received By cthroop Date 2021-10-25 Time 16:26 Sent To  
Notes
2021-10-25 16:39:05PLAN REVIEW BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 2017 NEC
  
 1ST REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
  
 1. PROVIDE AN ENERGY SUBMITTAL.
 FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE.
 AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405
 (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE
 COMPLIANCE BY SECTION 405.
  
 2. STATE R-VALUE OF FOIL FACED SEMI-PERMEABLE MASONRY
 WALL INSULATION. SEE PLAN PAGE A4.0.
 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS
 SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH
 107.2.5.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-26 Cont ID  
Sent By jleahy Date 2021-10-26 Time 11:46 Rev Time 0.00
Received By jleahy Date 2021-10-26 Time 11:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-30 Cont ID  
Sent By lmarchan Date 2022-01-30 Time 07:34 Rev Time 0.00
Received By lmarchan Date 2022-01-27 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-08 Cont ID  
Sent By cthroop Date 2022-01-08 Time 09:21 Rev Time 0.00
Received By cpuell Date 2021-12-01 Time 15:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-06 Cont ID  
Sent By lmarchan Date 2021-11-06 Time 17:38 Rev Time 0.00
Received By lmarchan Date 2021-10-25 Time 12:55 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status P Date 2022-02-02 Cont ID  
Sent By lmarchan Date 2022-02-02 Time 16:52 Rev Time 0.00
Received By lmarchan Date 2022-01-31 Time 10:00 Sent To  
Notes
2022-02-02 16:52:53RECEIPT MU-2022-04801 - $6350.41 PAID
2022-01-31 10:00:191/31/22 EMAILED IMPACT OFFICE TO REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2022-01-30 Cont ID  
Sent By lmarchan Date 2022-01-30 Time 07:34 Rev Time 0.00
Received By lmarchan Date 2022-01-08 Time 08:31 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-11-06 Cont ID  
Sent By lmarchan Date 2021-11-06 Time 17:38 Rev Time 0.00
Received By lmarchan Date 2021-11-06 Time 17:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:36 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 10:35 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 07:42 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 07:41 Sent To  
Notes
2021-12-03 07:41:51PLANS FOR THIS PROJECT ARE WITH PERMIT 21081320
  
 PLEASE RESPOND TO 2ND CYCLE REVIEW COMMENTS BELOW.
  
 2ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21081320
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS
 MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE
 PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE
 AND A CABANA-ACCESSORY STRUCTURE.
  
 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A
 CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE
 PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A
 RESCHECK FOR EACH STRUCTURE SEPARATELY.
  
 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY
 SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION
 OUTSIDE OF THE STRUCTURE. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By medwards Date 2021-10-25 Time 17:06 Rev Time 0.00
Received By medwards Date 2021-10-25 Time 17:05 Sent To  
Notes
2021-10-25 17:07:522ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21100214
 RESULTS FOR BOTH MAIN HOUSE AND CABANA
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 2 OF 18 LISTS THE TYPE OF PROJECT AS
 MULTIFAMILY FOR BOTH THE MAIN HOUSE AND THE CABANA. THE
 PERMIT APPLICATION IS FOR A NEW RESIDENTIAL STRUCTURE
 AND A CABANA-ACCESSORY STRUCTURE.
  
 2) THE 2 RESCHECK REPORTS ARE IDENTICAL AND FOR A
 CONDITIONED FLOOR AREA OF 4850 SQ FT. NEITHER OF THESE
 PROJECT HAVE A FLOOR AREA OF THIS SIZE. PLEASE SUBMIT A
 RESCHECK FOR EACH STRUCTURE SEPARATELY.
  
 3) THE CONDENSATE CANNOT TERMINATE IN THE SANITARY
 SYSTEM. PLEASE SHOW THE CONDENSATE TERMINATION LOCATION
 OUTSIDE OF THE STRUCTURE. FBC RES M1411.3
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-11-03 Cont ID  
Sent By lcrespo Date 2021-11-03 Time 06:50 Rev Time 0.00
Received By lcrespo Date 2021-11-03 Time 06:50 Sent To  
Notes
2021-11-03 06:51:11PEMITTED PLANS UNDER 21081320

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-10-25 Cont ID  
Sent By cthroop Date 2021-10-25 Time 16:40 Rev Time 0.00
Received By cthroop Date 2021-10-25 Time 16:26 Sent To  
Notes
2021-10-25 16:41:34PROVISO ON PLAN PAGE A-4: A SEPERATE ROOFING PERMIT IS
 REQUIRED. CT

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-29 Cont ID  
Sent By cthroop Date 2022-01-29 Time 10:36 Rev Time 0.00
Received By cthroop Date 2022-01-29 Time 09:18 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2022-01-08 Cont ID  
Sent By cthroop Date 2022-01-08 Time 08:22 Rev Time 0.00
Received By cthroop Date 2022-01-08 Time 07:13 Sent To  
Notes
2022-01-08 08:25:05SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 2ND REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: MECH., ELECTRICAL & PLUMBING PLANS: DIGITAL
 SIGNATURE HAS BEEN SELF CERTIFIED BY EOR, ANDREW
 SILVERSTEIN, P.E.
 FLORIDA PROFESSIONAL ENGINEERS MAY NOT SELF CERTIFY
 DIGITAL SIGNATURES AND SEALS PER FS 668.003.
 THE DESIGNER OF THE STRUCTURAL SHEETS CANNOT
 SELF-CERTIFY THEIR DIGITAL SIGNATURE. THE SIGNATURE
 MUST BE THIRD PARTY VERIFIED.
 61G15-23.004 F.A.C.
  
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By cthroop Date 2021-10-25 Time 16:39 Rev Time 0.00
Received By cthroop Date 2021-10-25 Time 16:26 Sent To  
Notes
2021-10-25 16:40:30SIGNATURE REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 INSPECTOR BN4338
 BUILDING OFFICIAL BU1635
 ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935
 DEVELOPMENT SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC2017
  
 1ST REVIEW
 RESULTS: DENIED
  
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 RE: PLAN PAGES C-1, C-2, ALL STRUCTURAL PLANS.
  
 NOTICE: DIGITAL SIGNATURE ON STRUCTURAL PLANS HAVE BEEN
 SELF CERTIFIED BY ANDREW SILVERSTEIN, P.E. ENGINEERS
 MAY N OT SELF CERTIFY THEIR DIGITAL SIGNATURES PER RULE
 FS 668.003.
 USE A THIRD PARTY TO CERTIFY DIGITAL SIGNATURE.
  
 1. DOCUMENTS PREPARED BY AN ARCHITECT OR ENGINEER AND
 SUBMITTED FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED,
 DATED ORIGINALS. A SCAN OF A WET SEAL AND SIGNATURE OR
 DIGITAL SIGNATURE IS NOT CONSIDERED A DIGITAL
 SIGNATURE.
  
 2. EITHER UPLOAD A VALID DIGITALLY SIGNED DOCUMENT OR
 DROP OFF (OR MAIL) ONE PAPER ORIGINAL WITH AN ORIGINAL
 WET SEAL AND SIGNATURE TO:
  
 BUILDING DIVISION, FIRST FLOOR
 CITY OF WEST PALM BEACH
 401 CLEMATIS ST
 WEST PALM BEACH, FL 33401
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2021-12-27 Cont ID  
Sent By llouie Date 2021-12-27 Time   Rev Time 0.00
Received By llouie Date 2021-12-27 Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By llouie Date 2021-11-05 Time   Rev Time  
Received By llouie Date 2021-11-05 Time   Sent To  
Notes
2021-11-05 10:36:21** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) APPROVAL OF MASTER PERMIT #21081320 REQUIRED PRIOR
 TO THE APPROVAL OF THIS PERMIT.
  
 2.) THE TOTAL FLOOR AREA OF ALL ROOFED ACCESSORY
 BUILDINGS ON A PROPERTY SHALL NOT EXCEED 75 PERCENT OF
 THE GROSS FLOOR AREA OF THE PRIMARY STRUCTURE WITH A
 MAXIMUM FLOOR AREA OF 1,000 SQUARE FEET. THE PROPOSED
 ACCESSORY STRUCTURE EXCEEDS THIS MAXIMUM ALLOWABLE
 BUILDING SQUARE FOOTAGE. [ZLDR S.94-304(B)(1)]
  
 3.) SHOW DIMENSION ILLUSTRATING THE DISTANCE SEPARATION
 BETWEEN THE ACCESSORY STRUCTURE AND THE PRIMARY
 RESIDENCE TO DEMONSTRATE THAT IT MEETS THE MINIMUM 6
 FT. DISTANCE SEPARATION REQUIREMENT BETWEEN STRUCTURES.
 [ZLDR S.94-304(B.)(3)]
  
 4.) OVERALL HEIGHT OF THE BUILDING (FROM GRADE TO THE
 TALLEST POINT OF THE STRUCTURE) CANNOT EXCEED 27.5 FT.
 TOTAL. THE STRUCTURAL ELEMENTS THAT ARE PERMITTED THE
 10% HEIGHT EXCEPTION ABOVE THE MAXIMUM ALLOWABLE
 BUILDING HEIGHT OF 25 FT. EXCEEDS THE LIMITATION. [ZLD
 S.94-305(B.)(4) AND S.94-306]
  
 5.) MECHANICAL EQUIPMENT MAY NOT ENCROACH MORE THAN 4
 FT. INTO A REQUIRED SETBACK. THERE IS AN A/C COMPRESSOR
 UNIT ON THE SOUTH SIDE OF THE PROPOSED STRUCTURE
 ILLUSTRATED IN THE FLOOR PLAN BUT NOT IN THE SITE PLAN.
 PLANS MUST MATCH FOR CONSISTENCY. ALSO, THE DIMENSION
 OF THE COMPRESSOR PAD TO THE PROPERTY LINE MUST BE
 PROVIDED TO DEMONSTRATE CONSISTENCY WITH THE
 REQUIREMENTS OF THE ZLDRS. [ZLDR S.94-305(B.)(4)]
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF14
  
 * MASTER PERMIT #21081320 (NEW SFR)
  