| 2021-10-15 07:24:58 | 10/15/21 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. THE CITY OF WEST PALM BEACH HAS NO RECORD OF |
| | EXISTING GAS PERMITS WITH INSPECTIONS OF THE CURRENT |
| | SYSTEM. A COMPLETE EVALUATION OF ALL GAS SYSTEMS AND |
| | EQUIPMENT WILL BE DONE AT THE FIELD, AND IF NOT TO |
| | CODE, IT MAY NEED TO BE BOUT UP TO CODE COMPLIANCE AT |
| | THE OWNER?S EXPENSE. PLEASE INCLUDE THE CURRENT AND NEW |
| | GAS SYSTEM AND EQUIPMENT IN THIS PERMIT FOR THIS SCOPE |
| | OF WORK PER THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 2. INDICATE ON THE PLAN IF THE TANK-LESS WATER HEATER |
| | IS THE ONLY GAS APPLIANCE IN THIS SYSTEM? IF NOT, |
| | SUBMIT A COMPLETE GAS RISER SHOWING ALL PIPE SIZES, |
| | TYPE OF PIPE, THE DEVELOPED LENGTH TO THE FURTHEST GAS |
| | OUTLET, THE BTU LOAD OF EACH APPLIANCE, THE PSI OF THE |
| | SYSTEM, THE TYPE OF GAS, AND THE TOTAL BTU LOAD ON THE |
| | SYSTEM. THESE REQUIREMENTS ALSO APPLY TO A NEW GAS |
| | SYSTEM PER THE WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 |
| | (12) RESIDENTIAL GAS |
| | |
| | 3. WOULD YOU PLEASE SHOW THE LOCATION OF ALL MP |
| | (STEP-DOWN) REGULATORS? A LISTED SHUTOFF VALVE SHALL BE |
| | INSTALLED IMMEDIATELY AHEAD OF EACH MP REGULATOR. 2020 |
| | FBC FG SEC. 409.4 OR 2020 FBC RES. SEC. G2420.4. |
| | |
| | 4. SHOW THE DISTANCE FROM THE POINT OF DELIVERY (GAS |
| | METER / MP REGULATOR / LP TANK) TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER THE 2020 FBC |
| | RES. SEC. G2413.4.1. |
| | |
| | 5. WOULD YOU PLEASE SUBMIT TWO COPIES OF THE SIZING |
| | TABLE USED IN THE DESIGN FOR THE GAS SYSTEM OR PLACE A |
| | NOTE ON BOTH SETS OF PLANS LISTING THE SIZING TABLES |
| | FROM GAS CODES OR ANOTHER STANDARD THAT WERE USED IN |
| | THE DESIGN OF THIS SYSTEM PER THE 2020 FBC FG SEC. |
| | 402.3 OR 2020 FBC RES. SEC. G2413.3. |
| | |
| | 6. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| | INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| | SHALL BE ONSITE AT THE TIME OF INSPECTION PER THE 2020 |
| | FBC RES. SEC. G2413.2 AND G2404.3. |
| | |
| | 7. WOULD YOU PLEASE SHOW AND LABEL ALL UNIONS IN FRONT |
| | OF REGULATOR 1' OF EITHER SIDE PER THE 2020 FBC RES. |
| | SEC G2421.2. |
| | |
| | 8. WOULD YOU PLEASE SHOW AND LABEL THE SHUTOFF VALVE ON |
| | GAS ISOMERIC PER THE 2020 FBC RES. SEC. G2420.5. |
| | |
| | 9. THE SHUT OFF INSIDE SHALL BE ACCESSIBLE WITHOUT |
| | MOVING THE EQUIPMENT PER THE 2020 FBC SEC. G2403 (202) |
| | GD, ACCESS. |
| | |
| | 10. WOULD YOU PLEASE SHOW AND LABEL DRIP LEG ON |
| | EQUIPMENT INSTALLED, EXCEPT FOR APPLIANCES, RANGE, |
| | DRYERS & OD GRILLS PER THE 2020 FBC RES. SEC. G2419.2. |
| | |
| | 11. THIS TANK-LESS UNIT CALL FOR A 10.5" WATER COLUMN, |
| | AND THE SERVICE METER DISCHARGES IS A 12" WATER COLUMN |
| | REQUIRING A REGULATOR FOR THIS UNIT AS PER THE |
| | MANUFACTURER'S SPECIFICATION. SUBMIT MANUFACTURER?S |
| | SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| | INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| | APPROVED FOR OUTDOOR INSTALLATION PER THE 2020 FBC RES. |
| | SEC. G2421.1 OR 410.1. |
| | |
| | 12. WOULD YOU PLEASE INDICATE THE SYSTEM'S DELIVERY |
| | PRESSURE (PSI) ON THE PLAN PER THE 2020 FBC FG SEC. |
| | 402.2 OR 2020 FBC RES. SEC. G2413.2. |
| | |
| | 13. WOULD YOU PLEASE SUBMIT A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANK-LESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER? THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE |
| | HAND-DRAWN PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 14. WOULD YOU PLEASE SHOW THE TYPE OF PIPE MATERIAL |
| | BEING INSTALLED, ALL PIPE SIZES, AND THE CORRESPONDING |
| | EHD NUMBER OF THE CORRUGATED STAINLESS-STEEL TUBING (IF |
| | APPLICABLE) FOR EACH PIPE SIZE PER THE WPB AMENDMENTS |
| | TO THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 15. PLEASE HAVE A SIGNATURE ON THE ISOMETRIC DRAWING OF |
| | THE PERSON DESIGNING THE SYSTEM, NOT IN ACCORDANCE WITH |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.001, FLORIDA |
| | STATUTE 471 PER THE WPB AMENDMENTS TO THE FBC SEC. |
| | 107.1 GENERAL. |
| | |
| | 16. GAS UNITS MAY REQUIRE CONDENSATE, AND IF SO, IT |
| | NEEDS TO BE 1' AWAY FROM THE STRUCTURE PER THE 2017 FBC |
| | SEC R318.5. |
| | |
| | 17. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 18. WOULD YOU PLEASE PROVIDE MANUFACTURES |
| | SPECIFICATIONS FOR ALL EQUIPMENT PER THE WPB AMENDMENTS |
| | TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 19. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR THE |
| | SOURCE OF IGNITION PER THE WPB AMENDMENTS TO THE FBC |
| | SEC. 105.1 |
| | . |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION, |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |