| 2021-12-16 11:58:52 | SFR ADDITION |
| | REVIEWED BY ROGER MCPHERSON |
| | 561-805-6716 |
| | [email protected] |
| | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| | AMENDMENT |
| | |
| | CORRECTIONS NEEDED - |
| | |
| | 1) PLEASE PROVIDE A SITE DRAINAGE PLAN - FBC R401.3 |
| | DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| | DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| | SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| | SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| | FIRST 10 FEET (3048 MM). |
| | |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| | BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| | PERCENT AWAY FROM THE BUILDING. |
| | |
| | FBC WPB 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS |
| | SUBMITTED WITH THE APPLICATION FOR PERMIT SHALL BE |
| | ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE THE SIZE |
| | AND LOCATION OF NEW CONSTRUCTION AND EXISTING |
| | STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE |
| | ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED |
| | GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS |
| | APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN |
| | FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE |
| | WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE |
| | SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED |
| | WATER RETAINING SWALES) |
| | |
| | 2) DRAWING A-1 SHOWS WIND DESIGN PER ASCE 7-10 - SHOULD |
| | BE ASCE 7-16 PER FBC CHAPTER 35 |
| | |
| | 3) PLEASE SHOW GARAGE FLOOR TO SLOPE PER FBC R309.1 |
| | FLOOR SURFACE. |
| | GARAGE FLOOR SURFACES SHALL BE OF APPROVED |
| | NONCOMBUSTIBLE MATERIAL. |
| | THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR |
| | OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE |
| | MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN |
| | VEHICLE ENTRY DOORWAY. |
| | |
| | 4) PLEASE SHOW ROOF PLYWOOD TYPE/SIZE FBC R803.1 |
| | |
| | 5) PLEASE PROVIDE A SURVEY. |
| | |
| | 6) A SEPARATE DEMO PERMIT IS REQUIRED. |
| | |
| | 7) BUILDING VALUE SHOWN ON THE PERMIT APPLICATION |
| | APPEARS TO BE LOW - PLEASE REVISE THE BUILDING PERMIT |
| | APPLICATION IF NEEDED TO SHOW THE TRUE JOB VALUE - FOR |
| | PERMITTING PURPOSES THE VALUE OF ALL LABOR AND |
| | MATERIALS REQUIRED TO COMPLETE THE PROJECT ARE REQUIRED |
| | TO BE INCLUDED IN THE COST. FBC 109.3 BUILDING PERMIT |
| | VALUATION. FOR PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT VALUE |
| | TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, MECHANICAL, |
| | INTERIOR FINISH, RELATIVE SITE WORK, ARCHITECTURAL AND |
| | DESIGN FEES, MARKETING COST, OVERHEAD AND PROFIT; |
| | EXCLUDING ONLY LAND VALUE. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL ? SWIFT, |
| | MEANS, ETC.) AS PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. FINAL BUILDING PERMIT VALUATION SHALL BE SET |
| | BY THE BUILDING OFFICIAL. |