Plan Review Details - Permit 21100101
Plan Review Stops For Permit 21100101
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-05 Cont ID  
Sent By cpuell Date 2021-10-05 Time 12:16 Rev Time 0.00
Received By cpuell Date 2021-10-05 Time 12:16 Sent To  
Notes
2021-10-05 12:16:36ADDRESS OK FOR NEW SFH

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-02-10 Cont ID  
Sent By jgomez Date 2022-02-10 Time 09:48 Rev Time 0.00
Received By jgomez Date 2022-02-10 Time 08:55 Sent To  
Notes
2022-02-10 09:52:51BUILDING PROVISO:
 1- PROVISO: LOT DRAINAGE:
 PROVIDE DETAIL FOR DRAINAGE RETAINING LOW WALL ON EAST
 AND SOUTH SIDE OF PROPERTY UNDER A SEPARATE PERMIT.
 2- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVALS FOR:
 ENTRY DOOR WITH TRANSOM, ALL WINDOW TYPES, ALL DOOR
 TYPES, WINDOW MULLIONS (AND SPECIFY SIZE), ROOF TILE,
 ROOF TILE ADHESIVE (SPECIFY SIZE), SHUTTERS IF
 DOORS/WINDOWS DON'T HAVE IMPACT GLASS(AND COMPLETE
 INSTALLATION SCHEDULE), DECORATIVE SHUTTERS SHOWN ON
 PLANS (AND COMPLETE INSTALLATION SCHEDULE),BALCONY
 UNDERLAYMENT FOR FINISH TILE AS SPECIFIED ON PLANS.
 ETC.
 3-ARCHITECT TO REVIEW/APPROVE ALL PRODUCT APPROVALS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-09 Cont ID  
Sent By jgomez Date 2022-02-09 Time 16:55 Rev Time 0.00
Received By jgomez Date 2022-02-09 Time 15:11 Sent To  
Notes
2022-02-09 17:05:41NEW SINGLE FAMILY RESIDENCE (R3)THIRD REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100101
  
 ORIGINAL COMMENT:
 1-ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 RESPONSE:
 REPEAT COMMENT. ENERGY CALCULATIONS WERE NOT SIGNED AT
 THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER.
  
 2- PROVISO: LOT DRAINAGE:
 PROVIDE DETAIL FOR DRAINAGE RETAINING LOW WALL ON EAST
 AND SOUTH SIDE OF PROPERTY UNDER A SEPARATE PERMIT.
  
 3-11 OK.
  
 12- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR: ENTRY DOOR WITH
 TRANSOM ABOVE AS SHOWN ON PLANS, ALL WINDOW TYPES SHOWN
 ON PLANS, ALL DOORS SHOWN ON PLANS, WINDOW MULLIONS
 (AND SPECIFY SIZE), ROOF TILE, ROOF TILE ADHESIVE IF
 USED (SPECIFY SIZE), SHUTTERS IF DOORS/WINDOWS DON'T
 HAVE IMPACT GLASS(AND COMPLETE INSTALLATION SCHEDULE),
 DECORATIVE SHUTTERS SHOWN ON PLANS (AND COMPLETE
 INSTALLATION SCHEDULE),BALCONY UNDERLAYMENT FOR FINISH
 TILE AS SPECIFIED ON PLANS. ETC.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE ALL
 PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 CITY
 AMENDMENTS.
  
 14-17 OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-18 Cont ID  
Sent By jgomez Date 2022-01-18 Time 13:54 Rev Time 0.00
Received By jgomez Date 2022-01-18 Time 10:57 Sent To  
Notes
2022-01-18 13:55:42NEW SINGLE FAMILY RESIDENCE (R3)SECOND REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100101
  
 ORIGINAL COMMENT:
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 RESPONSE:
 A)ENERGY CALCULATIONS FORM IS REQUIRED TO BE CERTIFIED
 AT THE BOTTOM OF THE FORM BY THE OWNER, THE OWNER'S
 ARCHITECT OR OTHER AUTHORIZED AGENT LEGALLY DESIGNED BY
 THE OWNER PRIOR TO RECEIVE THE PERMIT AS REQUIRED BY
 SEC. R103.1.1.2 FBC-ENERGY CONSERVATION.
  
 B)BUILDER TO SIGN AND COMPLETE THE ENERGY PERFORMANCE
 LEVEL (EPL) DISPLAY CARD. SEC. R405.4.3 FBC- ENERGY
 CONSERVATION.
  
 ORIGINAL COMMENT:
 2- LOT DRAINAGE:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: PROPOSED HOUSE FOOTPRINT IS BIGGER THAN EXISTING
 HOUSE. ALSO, PLANS CALL FOR FUTURE POOL EQUIPMENT.
 NEIGHBORS ON THE EAST AND SOUTH SIDES ARE GOING TO BE
 AFFECTED. SITE/DRAINAGE PLAN SUBMITTED DOESN'T SHOW ANY
 GRADE ELEVATIONS. ALSO, DRAINAGE PLAN SUBMITTED DOESN'T
 SHOW HOW TO KEEP THE SURFACE WATER AWAY FROM ADJACENT
 NEIGHBORS. PROVIDE COMPLETE DRAINAGE PLAN WITH GRADE
 ELEVATIONS.
  
 RESPONSE:
 *FINISHED FLOOR ELEVATION SHOWN ON THE HOUSE IS LOWER
 THAN THE EXTERIOR GRADE ELEVATION. REVISE/CLARIFY AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
 **NOTE: BASED ON ZONING COMMENTS, BUILDING SETBACK ON
 THE EAST SIDE NEEDS TO BE 10'-0". DRAINAGE AND ALL
 PLANS NEED TO BE REVISED ACCORDINGLY. SEC. 107.2.1 CITY
 AMENDMENTS.
 ***PROVIDE DETAIL FOR DRAINAGE RETAINING LOW WALL ON
 EAST AND SOUTH SIDE OF PROPERTY. NOTE: SEPARATE FENCE
 PERMIT APPLICATION WILL BE REQUIRED FOR THIS LOW WALL.
  
 3- SHEET SP-1:
 A)OK.
  
 ORIGINAL COMMENT:
 B)SPECIFY ROOF TRUSSES DEAD AND LIVE LOADS. CLEARLY
 SPECIFY TOP AND BOTTOM LOADS. INCLUDING THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 SEE FOOTNOTES "B" AND "G".
  
 RESPONSE:
 CLEARLY SPECIFY TRUSS TOP AND BOTTOM CHORD LIVE AND
 DEAD LOADS. WHAT IS THE DEAD LOAD FOR THE ROOF TILE?
 AND WHAT IS THE BOTTOM CHORD DEAD LOAD.? . SEC. R301.1
 FBC-RESIDENTIAL.
  
 4-11 OK.
  
 12- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR: ENTRY DOOR WITH
 TRANSOM ABOVE AS SHOWN ON PLANS, ALL WINDOW TYPES SHOWN
 ON PLANS, ALL DOORS SHOWN ON PLANS, WINDOW MULLIONS
 (AND SPECIFY SIZE), ROOF TILE, ROOF TILE ADHESIVE IF
 USED (SPECIFY SIZE), SHUTTERS IS DOORS/WINDOWS DON'T
 HAVE IMPACT GLASS(AND COMPLETE INSTALLATION SCHEDULE),
 DECORATIVE SHUTTERS SHOWN ON PLANS (AND COMPLETE
 INSTALLATION SCHEDULE),BALCONY UNDERLAYMENT FOR FINISH
 TILE AS SPECIFIED ON PLANS. ETC.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14-16 OK.
  
 ORIGINAL COMMENT:
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN AREAS AS REQUIRED BY SEC. R302.12
 FBC-RESIDENTIAL.
  
 RESPONSE:
 DRAFSTOPPING AND FIREBLOCKING ARE TWO DIFFERENT
 REQUIREMENTS. 2ND FLOOR FRAMING PLAN HAS A NOTE TO
 "PROVIDE DRAFSTOPPING BELOW STAIRS AT STAIR OPENING".
 FIREBLOCKING IS REQUIRED IN STAIRS CONCEALED SPACES.
 SEE SEC. R302.11 FBC-RESIDENTIAL. ON THE OTHER HAND
 DRAFSTOPPING IS ONLY REQUIRED IN FLOOR-CEILING
 ASSEMBLIES. SEE SEC. R302.12 FBC-RESIDENTIAL. REVISE AS
 REQUIRED.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By jgomez Date 2021-11-23 Time 14:16 Rev Time 0.00
Received By jgomez Date 2021-11-23 Time 11:27 Sent To  
Notes
2021-11-23 14:18:33NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21100101
  
 1-PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 R101.5 FBC-ENERGY CONSERVATION.
 NOTE: PLEASE MAKE SURE FORM IS PROPERLY SIGNED BY ALL
 REQUIRED PARTIES AND IS COORDINATED WITH PLANS TO AVOID
 CONFLICTS/DELAYS.
  
 2- LOT DRAINAGE:
 PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE
 FOLLOWING: R401.3 FBC-RESIDENTIAL. SEC. 107.2.5 CITY
 AMENDMENTS.
 SEC. 110.9 CITY AMENDMENTS.
 NOTE: PROPOSED HOUSE FOOTPRINT IS BIGGER THAN EXISTING
 HOUSE. ALSO, PLANS CALL FOR FUTURE POOL EQUIPMENT.
 NEIGHBORS ON THE EAST AND SOUTH SIDES ARE GOING TO BE
 AFFECTED. SITE/DRAINAGE PLAN SUBMITTED DOESN'T SHOW ANY
 GRADE ELEVATIONS. ALSO, DRAINAGE PLAN SUBMITTED DOESN'T
 SHOW HOW TO KEEP THE SURFACE WATER AWAY FROM ADJACENT
 NEIGHBORS. PROVIDE COMPLETE DRAINAGE PLAN WITH GRADE
 ELEVATIONS.
  
 3- SHEET SP-1:
 A)NEED TO SPECIFY THE LIVE AND DEAD LOADS FOR SECOND
 FLOOR TRUSSES. SEC. R301.4 AND SEC. R301.5
 FBC-RESIDENTIAL.
  
 B)SPECIFY ROOF TRUSSES DEAD AND LIVE LOADS. CLEARLY
 SPECIFY TOP AND BOTTOM LOADS. INCLUDING THE ATTIC LIVE
 LOAD AS REQUIRED BY TABLE R301.5 FBC-RESIDENTIAL.
 SEE FOOTNOTES "B" AND "G".
  
 4- SHEET A-1:
 A)FIRST FLOOR: SPECIFY SIZE OF ATTIC ACCESS. SEC.
 R807.1 FBC-RESIDENTIAL.
  
 B)SECOND FLOOR: SPECIFY LOCATION AND SIZE OF ATTIC
 ACCESS AT THE MASTER BEDROOM WING AREA AND AT GARAGE
 WING AREA. SEC. R807.1 FBC-RESIDENTIAL.
  
 5- ATTIC ACCESS DETAIL 1/A-4 ON SHEET A-5 SPECIFIES
 21-1/2" CLEAR OPENING. THIS DOESN'T COMPLY WITH SEC.
 R807.1 FBC-RESIDENTIAL. MIN. SIZE IS 22" BY 30" REVISE
 AS REQUIRED.
  
 6- SHEET A-4:
 A)TWO STORY WALL SECTION: THERE IS A CONCERN ABOUT THE
 SUPPORT OF THE SECOND FLOOR TRUSSES. STRUCTURAL LEDGER
 SUPPORTING THE FLOOR TRUSSES IS ANCHORED TO THE WALL
 WITH 5/8" REDHEADS @32" O.C. PROVIDE CALCULATIONS
 SHOWING THAT THE SPECIFIED FASTENER SIZE AND SPACING IS
 ADEQUATE TO SUPPORT THE STRUCTURAL LOAD. SEC. 107.2.1.2
 CITY AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS,
 INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE
 STRUCTURAL WALL.
  
 B)ROOF TRUSSES STRUCTURAL SUPPORT SPECIFIED ON THE TWO
 STORY WALL SECTION: DETAIL DOESN'T MATCH TRUSS LAYOUT
 SHOWN ON SECOND FLOOR LOW ROOF FRAMING PLAN ON SHEET
 S-2 FOR ROOF ABOVE MASTER BEDROOM WING. ON THE OTHER
 HAND, IF THIS IS A TYPICAL DETAIL FOR THE ROOF ABOVE
 GARAGE WING, THEN, THERE IS A CONCERN ABOUT THE SUPPORT
 OF THE ROOF TRUSSES. STRUCTURAL LEDGER SUPPORTING THE
 ROOF TRUSSES IS ANCHORED TO THE WALL WITH 1/4" TAPCONS
 @16" O.C. PROVIDE CALCULATIONS SHOWING THAT THE
 SPECIFIED FASTENER SIZE AND SPACING IS ADEQUATE TO
 SUPPORT THE STRUCTURAL LOAD. SEC. 107.2.1.2 CITY
 AMENDMENTS. SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: PROVIDE COMPLETE FASTENER SPECIFICATIONS,
 INCLUDING REQUIRED FASTENER EMBEDMENT INTO THE
 STRUCTURAL WALL.
  
 C)EAST ELEVATION SPECIFIES "DECORATIVE ALUM. RAILING".
 THIS IS NOT A DECORATIVE RAILING. THIS IS A FUNCTIONAL
 BALCONY GUARDRAIL NOT A DECORATIVE ONE. REVISE AS
 REQUIRED TO AVOID CONFLICTS/DELAYS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5
 FBC-RESIDENTIAL AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: THIS APPLIES TO ALL EXTERIOR ELEVATIONS SHOWING
 THE BALCONY GUARDRAIL.
  
 7- SCHEMATIC HANDRAIL DETAILS ON SHEET A-5:
 A) DETAILS ARE NOT CLEAR. IT LOOKS LIKE THE DETAILS ARE
 APPLICABLE TO COMMERCIAL BUILDINGS NOT FOR SINGLE
 FAMILY RESIDENCE. ALSO, THEY DON'T MATCH HANDRAILS
 SHOWN ON PLANS. REVISE AS REQUIRED. PROVIDE DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R311.7.8
 FBC-RESIDENTIAL.
 NOTE: DETAILED STAIR PLAN SPECIFIES "DECORATIVE
 RAILING". THIS IS NOT A DECORATIVE RAILING. THIS IS A
 FUNCTIONAL GUARDRAIL NOT A DECORATIVE ONE. REVISE AS
 REQUIRED TO AVOID CONFLICTS/DELAYS. PROVIDE COMPLETE
 DETAILS AND SPECIFICATIONS FOR THE CONSTRUCTION OF THE
 GUARDRAIL SHOWING COMPLIANCE WITH TABLE R301.5
 FBC-RESIDENTIAL AND SEC. R312.1 FBC-RESIDENTIAL.
 NOTE: DEFERRED SUBMITTAL. SUBMIT HANDRAIL AND GUARDRAIL
 SHOP DRAWINGS REVIEWED BY THE DESIGNER OF RECORD PRIOR
 TO CONSTRUCTION TO AVOID CONFLICTS/DELAYS.
  
 B)REFERENCE CORRECT CODE SECTIONS. SEE CURRENT 2020
 FBC-RESIDENTIAL AND REVISE AS REQUIRED.
 SEC. 553 F.S.
  
 8- SHEET S-1: CLARIFY WHY FOOTER F-2 IS SMALLER THAN
 FOOTER F3 IF FOOTER F-3 IS FOR THE ONE STORY SECTION OF
 THE BUILDING AND FOOTING F-2 IS FOR TWO STORY SECTION
 OF THE BUILDING. SEC. 107.2.1 CITY AMENDMENTS. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 9-SHEET S-2:
 A)SPECIFY CONNECTOR AT BOTH ENDS OF TRUSS GIRDER SHOWN
 ON THE 2ND FLOOR LOW ROOF FRAMING PLAN ABOVE MASTER
 BEDROOM WING, GARAGE WING AND ABOVE COVERED LANAI. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 B)SPECIFY UPLIFT TRUSS CONNECTOR FOR TRUSSES RESTING ON
 SECOND FLOOR WALL BY THE GARAGE WING. SEC. R301.1
 FBC-RESIDENTIAL.
  
 C)REVISE ROOF NAILING ZONES SPECIFICATIONS SPECIFIED ON
 SHEET S-2 AND S-3. ROOF SHEATHING NEEDS TO BE NAILED AT
 4 INCHES O.C. IN THE FIELD AND EDGES AS REQUIRED BY
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
  
 D) REVISE STRUCTURAL LEDGER FASTENING SPECIFICATIONS
 SHOWN ON TYPICAL INTERMEDIATE SECTION-1. SEE COMMENT
 #6(A) ABOVE. SEC. R301.1 FBC-RESIDENTIAL.
  
 10- SPECIFY CONNECTOR AT BOTH ENDS OF TRUSS GIRDERS
 SHOWN ON THE UPPER ROOF FRAMING PLAN ON SHEET S-3. SEC.
 R301.1 FBC-RESIDENTIAL.
  
 11- PROVIDE ICC EVALUATION REPORT FOR THE ICYNENE R-20
 INSULATION TO VERIFY COMPLIANCE WITH SEC. R316
 FBC-RESIDENTIAL.
 NOTE: ARCHITECT TO REVIEW AND APPROVE THE REPORT IN
 WRITING PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 12- DEFERRED SUBMITTAL: PROVIDE PRODUCT APPROVAL AS
 REQUIRED BY FAC 61G20-3.001 FOR: ENTRY DOOR WITH
 TRANSOM ABOVE AS SHOWN ON PLANS, ALL WINDOW TYPES SHOWN
 ON PLANS, ALL DOORS SHOWN ON PLANS, WINDOW MULLIONS
 (AND SPECIFY SIZE), ROOF TILE, ROOF TILE ADHESIVE IF
 USED (SPECIFY SIZE), SHUTTERS IS DOORS/WINDOWS DON'T
 HAVE IMPACT GLASS(AND COMPLETE INSTALLATION SCHEDULE),
 DECORATIVE SHUTTERS SHOWN ON PLANS (AND COMPLETE
 INSTALLATION SCHEDULE), ETC.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- PROVIDE COMPLETE GARAGE DOOR STRUCTURAL BUCK DETAIL
 AND SPECIFICATIONS. SEC. R301.2.1 FBC-RESIDENTIAL.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 BALCONY FINISH FLOORING. SEC. 107.2.1 CITY AMENDMENTS.
  
 16- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 FIREBLOCKING IN AREAS AS REQUIRED BY SEC. R302.11
 FBC-RESIDENTIAL.
  
 17- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 DRAFSTOPPING IN AREAS AS REQUIRED BY SEC. R302.12
 FBC-RESIDENTIAL.
  
 18- NEED SEPARATE DEMO PERMIT FOR THE DEMOLITION OF
 EXISTING HOUSE. SEC. 105.1 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 13:46 Rev Time 0.00
Received By jleahy Date 2021-11-05 Time 13:46 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 15:58 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 15:58 Sent To  
Notes
2021-10-22 15:59:03GAS PLAN REVIEW, A GAS PLAN HAS NOT BEEN INCLUDED IN
 THIS SUBMITTAL PACKAGE, AND A GAS PLAN REVIEW HAS NOT
 BEEN PERFORMED AT THIS TIME. A SEPARATE GAS PERMIT AND
 PLANS WILL BE REQUIRED FOR A CONTRACTOR TO PERFORM THE
 RELATED WORK. PROVIDE COMPLETE PLANS AND GAS RISER THAT
 REFLECTS THE ENTIRE SCOPE OF GAS WORK TO BE DONE PER
 THE WPB AMENDMENTS TO FBC SEC. 107.2.1.
  
 A SUB GAS PERMIT IS REQUIRED BY A LICENSED CONTRACTOR
 FOR THE SCOPE OF WORK PER THE WPB AMENDMENTS TO THE FBC
 SEC. 105.1.
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-10 Cont ID  
Sent By jgomez Date 2022-02-10 Time 11:19 Rev Time 0.00
Received By jgomez Date 2022-02-10 Time 08:54 Sent To  
Notes
2022-02-10 08:55:15JIM PAINE EMAILED ENERGY CALCULATIONS. JG.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-02-09 Cont ID  
Sent By jgomez Date 2022-02-09 Time 17:34 Rev Time 0.00
Received By jgomez Date 2022-01-24 Time 11:24 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-18 Cont ID  
Sent By jgomez Date 2022-01-18 Time 13:59 Rev Time 0.00
Received By jgomez Date 2021-12-27 Time 08:33 Sent To I
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By jgomez Date 2021-11-23 Time 14:35 Rev Time 0.00
Received By jgomez Date 2021-10-05 Time 06:53 Sent To I
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By lmarchan Date 2022-02-28 Time 08:58 Rev Time 0.00
Received By lmarchan Date 2022-02-14 Time 09:04 Sent To  
Notes
2022-02-27 07:38:40RECEIPT - MU-2022-008434 - $2491.56 PAID
2022-02-14 09:05:282/14/22 EMAILED IMPACT FOR REVIEW AO

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By jgomez Date 2021-11-23 Time 14:26 Rev Time 0.00
Received By jgomez Date 2021-11-23 Time 14:26 Sent To  
Notes
2021-11-23 14:29:34IMPACT FEES
 PLANS NEED TO BE REVIEWED BY PALM BEACH COUNTY FOR
 IMPACT FEE ASSESSMENT.
 PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT (IF ANY), PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2021-12-29 Cont ID  
Sent By medwards Date 2021-12-29 Time 11:19 Rev Time 0.00
Received By medwards Date 2021-12-29 Time 11:19 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By medwards Date 2021-10-13 Time 15:29 Rev Time 0.00
Received By medwards Date 2021-10-13 Time 15:18 Sent To  
Notes
2021-10-13 15:34:30PLEASE PROVIDE THE ENERGY CALCULATIONS. FBC EC
 101.5.1.1.2
 PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS. FBC EC R403.7
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 15:59 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 15:59 Sent To  
Notes
2021-10-22 15:59:3210/22/21 REVIEWED FOR CODE COMPLIANCE (PLUMBING)
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS, OR THEIR REPRESENTATIVES
 FROM THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL,
 STATE, AND NATIONAL CODES AND STANDARDS IN EFFECT AT
 THE TIME OF PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK
 OF EVERY ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2021-11-23 Cont ID  
Sent By jgomez Date 2021-11-23 Time 14:19 Rev Time 0.00
Received By jgomez Date 2021-11-23 Time 14:19 Sent To  
Notes
2021-11-23 14:21:08NO ROOF PRODUCT APPROVALS SUBMITTED. PROVIDE COMPLETE
 INFORMATION WHEN SUBMITTING FOR THE ROOFING SUB-PERMIT.
 JG.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-10 Cont ID  
Sent By jgomez Date 2022-02-10 Time 11:19 Rev Time 0.00
Received By jgomez Date 2022-02-10 Time 10:15 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-02-09 Cont ID  
Sent By jgomez Date 2022-02-09 Time 17:34 Rev Time 0.00
Received By jgomez Date 2022-02-09 Time 17:34 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-18 Cont ID  
Sent By jgomez Date 2022-01-18 Time 13:59 Rev Time 0.00
Received By jgomez Date 2022-01-18 Time 13:58 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-23 Cont ID  
Sent By jgomez Date 2021-11-23 Time 14:35 Rev Time 0.00
Received By jgomez Date 2021-11-23 Time 14:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-02-10 Cont ID  
Sent By vbroglia Date 2022-02-09 Time 12:33 Rev Time 0.00
Received By vbroglia Date 2022-02-09 Time 12:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-01-03 Cont ID  
Sent By ajones Date 2022-01-03 Time 16:25 Rev Time 0.00
Received By ajones Date 2022-01-03 Time 16:25 Sent To  
Notes
2022-01-03 16:30:321/3/22- FAILED- THE FRONT OF THIS PROPERTY IS ALONG
 SOUTH OLIVE AVENUE, THEREFORE; THE REAR SETBACK IS 10
 FEET (15 FEET OR 10% OF THE LOT DEPTH, WHICHEVER IS
 LESS).
 REVISE SITE PLAN TO SHOW CORRECT REAR SETBACK.
  
 ANGELLA VANN
 561-822-1441
 [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By rthermid Date 2021-11-05 Time 10:15 Rev Time 0.00
Received By ajones Date 2021-11-05 Time 10:15 Sent To  
Notes
2021-11-05 10:19:4511/5/21- FAILED. PLEASE SHOW THE FOLLOWING ON A REVISE
 PLAN:
 1. ONLY ONE 20 FOOT WIDE OR TWO 10-FOOT WIDE CURB CUTS
 ARE PERMITTED FOR A SINGLE FAMILY HOUSE.
 2. THE REAR SETBACK FOR THE HOUSE IS 8 FEET. PLEASE
 INDICATE IT ON THE SITE PLAN.
 3. SEPERATE PERMITS ARE REQUIRED FOR LANDSCAPING, POOL,
 FENCE/WALLS, DRIVEWAYS.
  