| Plan Review Stops For Permit 21100033 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-18 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-18 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2021-10-18 17:01:12 | ADDRESS IS OK FOR NEW BUILD |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-10-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2021-10-09 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2022-02-28 08:48:43 | BUILDING PROVISO | | | PRODUCT APPROVALS FOR THE CONCRETE ROOF TILES, | | | UNDERLAYMENT AND RIDGE METAL ARE BEING DEFERRED. SUBMIT | | | THEM FOR AUDIT AFTER THEY HAVE BEEN APPROVED BY THE | | | DESIGNER OF RECORD AND THE PRIVATE PROVIDER. DO NOT | | | INSTALL UNTIL THE AUDIT HAS BEEN COMPLETED AND THE | | | STAMPED PLANS ARE AT THE SITE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-01-13 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-13 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2022-01-13 16:35:39 | BUILDING AUDIT | | | | | | 1) THE VALUATION APPEARS A LITTLE LOW AND WILL BE | | | CHANGED TO $610,308.00. CITY AMENDMENTS FBC 109.3 | | | | | | 2) THERE IS A DISCREPANCY IN THE SPECIFIED EXPOSURE | | | CATEGORY BETWEEN SHEETS S-2, S-3 AND SHEET A-301. THE | | | STRUCTURAL SHEETS HAVE EXPOSURE C AND THE ARCHITECTURAL | | | SHEET HAS EXPOSURE D. PLEASE COORDINATE THE PLANS AND | | | REVISE THE COMPONENT AND CLADDING PRESSURES AS | | | NECESSARY. FBC R301.2.1.4.3 | | | | | | 3) THE PLANS SPECIFY A VENTED ATTIC WITH R-30 | | | INSULATION AND THE ENERGY CALCULATIONS SPECIFY AN | | | UN-VENTED ATTIC WITH R-20 INSULATION. PLEASE CLARIFY. | | | CITY AMENDMENTS FBC 107.2.1 | | | | | | 4) SUBMIT THE PRODUCT APPROVALS FOR THE CONCRETE TILE | | | ROOF ASSEMBLY THAT HAVE BEEN REVIEWED AND APPROVED BY | | | THE DESIGNER OF RECORD. CITY AMENDMENTS FBC 107.3.4 | | | | | | 5) SUBMIT THE PRODUCT APPROVALS FOR THE BAHAMA / | | | BERMUDA SHUTTERS THAT HAVE BEEN REVIEWED AND APPROVED | | | BY THE DESIGNER OF RECORD. CITY AMENDMENTS FBC 107.3.4 | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-23 |
Time |
07:27 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-23 |
Time |
07:22 |
Sent To |
|
|
| Notes |
| 2022-02-23 07:28:01 | ELECTRICAL AUDIT APPROVED JLEAHY |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-10 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-01-10 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2022-01-10 11:22:51 | ELECTRICAL AUDIT: | | | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | METER HAS A #3 GROUND COMING TO MAIN NOT NEEDED ON | | | SERVICE CONDUCTORS. | | | | | | PANELS FED FROM THE 400A DISCONNECT SHALL OVERCURRENT | | | DEVICES PER 240,21(B)(1)(1)(B). | | | | | | 240.21(A)(1) TAPS NOT OVER 3 M (10 FT) LONG. IF THE | | | LENGTH OF THE TAP | | | CONDUCTORS DOES NOT EXCEED 3 M (10 FT) AND THE TAP | | | CONDUCTORS | | | COMPLY WITH ALL OF THE FOLLOWING: | | | (1) THE AMPACITY OF THE TAP CONDUCTORS IS | | | A. NOT LESS THAN THE COMBINED CALCULATED LOADS ON THE | | | CIRCUITS SUPPLIED BY THE TAP CONDUCTORS, AND | | | B. NOT LESS THAN THE RATING OF THE EQUIPMENT CONTAINING | | | AN OVERCURRENT DEVICE(S) SUPPLIED BY THE TAP CONDUCTORS | | | OR NOT LESS THAN THE RATING OF THE OVERCURRENT | | | PROTECTIVE DEVICE AT THE TERMINATION OF THE TAP | | | CONDUCTORS. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-03-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-03 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-03 |
Time |
12:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-28 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-18 |
Time |
11:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-02-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-02-15 |
Time |
08:25 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-02-03 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2022-02-07 12:34:29 | ZONING PASSED ON 10/22/21. NUMEROUS NEW PAGES WERE | | | SUBMITTED ON 2/2/22 INCLUDING ELEVATIONS, ROUTED BACK | | | TO ZONING SH |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-01-13 |
Time |
17:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-07 |
Time |
09:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-01-06 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-12-16 |
Time |
09:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-22 |
Time |
17:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-15 |
Time |
06:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-03-01 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-03-01 |
Time |
16:31 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-24 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2022-02-28 12:04:02 | RECEIPT MU-2022-008547 - $2404.37 PAID | | 2022-02-24 08:00:02 | 2/24/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-10-12 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2021-10-12 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-12 10:06:30 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-02-23 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-23 |
Time |
07:04 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-23 |
Time |
07:04 |
Sent To |
|
|
| Notes |
| 2022-02-23 07:04:52 | MECHANICAL AUDIT ONLY APPROVED ME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-29 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-12-29 |
Time |
17:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-12-29 |
Time |
17:20 |
Sent To |
|
|
| Notes |
| 2021-12-29 17:23:02 | MECHANICAL AUDIT: | | | THE BARBEQUE GRILL IN THE COVERED PATIO AREA WILL | | | REQUIRE A HOOD ABOVE IT. PLEASE PROVIDE THE HOOD | | | DETAILS ALONG WITH A DETAIL DRAWING SHOWING THE EXHAUST | | | DUCT AND TERMINATION LOCATION. FBC 107.2.1 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-01-10 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-01-10 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2022-01-10 11:18:10 | ADUDIT APPROVED, LAC |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
5 |
Status |
P |
Date |
2022-03-03 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-03-03 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-03-03 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
4 |
Status |
F |
Date |
2022-02-22 |
|
|
Cont ID |
|
| Sent By |
cthroop |
Date |
2022-02-22 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
cthroop |
Date |
2022-02-22 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2022-02-22 16:09:43 | PRIVATE PROVIDER AFFIDAVIT REVIEW | | | | | | CHRISTOPHER S. THROOP, C.B.O., CFM | | | PLANS EXAMINER II PX3169/SFP306 | | | BU1635 BN4338 | | | ASFPM CFM US-21-11935 | | | CITY OF WEST PALM BEACH | | | (561) 805-6726 | | | [email protected] | | | | | | 1ST REVIEW | | | | | | RESULTS: DENIED | | | | | | | | | CODES IN EFFECT: | | | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST | | | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, | | | CHAPTER 1 ADMINISTRATION | | | NFPA 70 2017 EDITION NEC 2017 | | | | | | 3RD REVIEW | | | | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | | | 1. AFFIDAVIT STATES PLANS SHEETS BY KELLY D. YATES, | | | DATED OCTOBER 2021 (10/2021 ON PLANS) | | | THE FOLLOWING PLAN PAGES ARE REV 3 DATED 01/2022; | | | A-201, A-202, A-301, A-401, A-402, E-101 AND S-6. | | | PLEASE CORRECT AFFIDAVIT AND RE-SUBMIT FOR REVIEW. | | | | | | | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2022-01-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-01-10 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-01-10 |
Time |
11:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-01-06 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-01-06 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2022-01-06 12:00:17 | FS553.791 AFFIDAVIT DOES NOT MATCH DATES OF PLANS | | | UPLOADED. FOR EXAMPLE, SEE A101. REFER TO EMAILS SENT | | | TO APPLICANT WITH SCREEN SHOTS. |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
P |
Date |
2021-12-17 |
|
|
Cont ID |
|
| Sent By |
dbattles |
Date |
2021-12-17 |
Time |
13:07 |
Rev Time |
0.00 |
| Received By |
dbattles |
Date |
2021-12-17 |
Time |
13:07 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:45 |
Sent To |
|
|
| Notes |
| 2022-02-28 08:45:52 | PRODUCT APPROVALS FOR THE CONCRETE ROOF TILES, | | | UNDERLAYMENT AND RIDGE METAL ARE BEING DEFERRED. SUBMIT | | | THEM FOR AUDIT AFTER THEY HAVE BEEN APPROVED BY THE | | | DESIGNER OF RECORD AND THE PRIVATE PROVIDER. DO NOT | | | INSTALL UNTIL THE AUDIT HAS BEEN COMPLETED AND THE | | | STAMPED PLANS ARE AT THE SITE. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-01-13 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-13 |
Time |
17:07 |
Sent To |
|
|
| Notes |
| 2022-01-13 17:08:23 | NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOF | | | COVERING. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-02-28 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:49 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-28 |
Time |
08:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-01-13 |
Time |
17:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-13 |
Time |
16:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-18 |
Time |
10:09 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-18 |
Time |
10:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-18 |
|
|
Cont ID |
|
| Sent By |
vbroglia |
Date |
2022-02-14 |
Time |
15:51 |
Rev Time |
0.00 |
| Received By |
vbroglia |
Date |
2022-02-14 |
Time |
15:51 |
Sent To |
|
|
| Notes |
| 2022-02-14 15:56:48 | 2/14/2022 FAILED | | | | | | PLEASE SUBMIT A LANDSCAPE PERMIT TO ALLOW STAFF TO MOVE | | | FOAWARD WITH CURRENT PERMIT | | | | | | VALENTINA BROGLIA | | | ASSOCIATE PLANNER | | | [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
awooten |
Date |
2021-10-22 |
Time |
|
Rev Time |
|
| Received By |
awooten |
Date |
2021-10-22 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-22 11:29:22 | ******ZONING PROVISO********* | | | | | | PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY, | | | THE FOLLOWING CONDITIONS SHALL BE ADDRESSED: | | | | | | 1. A LANDSCAPE PERMIT, WHICH INLUDES A LANDSCAPE PLAN, | | | SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW. | | | | | | 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED | | | LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL | | | LANDSCAPE INSPECTION. | | | | | | THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A | | | SEPARATE PERMIT. | | | | | | ALANA WOOTEN | | | PLANNER | | | 561-22-1449 | | | [email protected] | | | |
|
|