Plan Review Details - Permit 21100033
Plan Review Stops For Permit 21100033
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-10-18 Cont ID  
Sent By cpuell Date 2021-10-18 Time 16:59 Rev Time 0.00
Received By cpuell Date 2021-10-18 Time 16:59 Sent To  
Notes
2021-10-18 17:01:12ADDRESS IS OK FOR NEW BUILD

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-10-09 Time   Rev Time 0.00
Received By   Date 2021-10-09 Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By rmcdouga Date 2022-02-28 Time 08:48 Rev Time 0.00
Received By rmcdouga Date 2022-02-28 Time 08:48 Sent To  
Notes
2022-02-28 08:48:43BUILDING PROVISO
 PRODUCT APPROVALS FOR THE CONCRETE ROOF TILES,
 UNDERLAYMENT AND RIDGE METAL ARE BEING DEFERRED. SUBMIT
 THEM FOR AUDIT AFTER THEY HAVE BEEN APPROVED BY THE
 DESIGNER OF RECORD AND THE PRIVATE PROVIDER. DO NOT
 INSTALL UNTIL THE AUDIT HAS BEEN COMPLETED AND THE
 STAMPED PLANS ARE AT THE SITE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 16:34 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 16:34 Sent To  
Notes
2022-01-13 16:35:39BUILDING AUDIT
  
 1) THE VALUATION APPEARS A LITTLE LOW AND WILL BE
 CHANGED TO $610,308.00. CITY AMENDMENTS FBC 109.3
  
 2) THERE IS A DISCREPANCY IN THE SPECIFIED EXPOSURE
 CATEGORY BETWEEN SHEETS S-2, S-3 AND SHEET A-301. THE
 STRUCTURAL SHEETS HAVE EXPOSURE C AND THE ARCHITECTURAL
 SHEET HAS EXPOSURE D. PLEASE COORDINATE THE PLANS AND
 REVISE THE COMPONENT AND CLADDING PRESSURES AS
 NECESSARY. FBC R301.2.1.4.3
  
 3) THE PLANS SPECIFY A VENTED ATTIC WITH R-30
 INSULATION AND THE ENERGY CALCULATIONS SPECIFY AN
 UN-VENTED ATTIC WITH R-20 INSULATION. PLEASE CLARIFY.
 CITY AMENDMENTS FBC 107.2.1
  
 4) SUBMIT THE PRODUCT APPROVALS FOR THE CONCRETE TILE
 ROOF ASSEMBLY THAT HAVE BEEN REVIEWED AND APPROVED BY
 THE DESIGNER OF RECORD. CITY AMENDMENTS FBC 107.3.4
  
 5) SUBMIT THE PRODUCT APPROVALS FOR THE BAHAMA /
 BERMUDA SHUTTERS THAT HAVE BEEN REVIEWED AND APPROVED
 BY THE DESIGNER OF RECORD. CITY AMENDMENTS FBC 107.3.4
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By jleahy Date 2022-02-23 Time 07:27 Rev Time 0.00
Received By jleahy Date 2022-02-23 Time 07:22 Sent To  
Notes
2022-02-23 07:28:01ELECTRICAL AUDIT APPROVED JLEAHY

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-01-10 Cont ID  
Sent By jleahy Date 2022-01-10 Time 11:09 Rev Time 0.00
Received By jleahy Date 2022-01-10 Time 11:00 Sent To  
Notes
2022-01-10 11:22:51ELECTRICAL AUDIT:
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
 METER HAS A #3 GROUND COMING TO MAIN NOT NEEDED ON
 SERVICE CONDUCTORS.
  
 PANELS FED FROM THE 400A DISCONNECT SHALL OVERCURRENT
 DEVICES PER 240,21(B)(1)(1)(B).
  
 240.21(A)(1) TAPS NOT OVER 3 M (10 FT) LONG. IF THE
 LENGTH OF THE TAP
 CONDUCTORS DOES NOT EXCEED 3 M (10 FT) AND THE TAP
 CONDUCTORS
 COMPLY WITH ALL OF THE FOLLOWING:
 (1) THE AMPACITY OF THE TAP CONDUCTORS IS
 A. NOT LESS THAN THE COMBINED CALCULATED LOADS ON THE
 CIRCUITS SUPPLIED BY THE TAP CONDUCTORS, AND
 B. NOT LESS THAN THE RATING OF THE EQUIPMENT CONTAINING
 AN OVERCURRENT DEVICE(S) SUPPLIED BY THE TAP CONDUCTORS
 OR NOT LESS THAN THE RATING OF THE OVERCURRENT
 PROTECTIVE DEVICE AT THE TERMINATION OF THE TAP
 CONDUCTORS.

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-03-03 Cont ID  
Sent By rmcphers Date 2022-03-03 Time 14:25 Rev Time 0.00
Received By rmcphers Date 2022-03-03 Time 12:19 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-02-28 Cont ID  
Sent By lmarchan Date 2022-02-28 Time 12:04 Rev Time 0.00
Received By lmarchan Date 2022-02-18 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-02-15 Cont ID  
Sent By shill Date 2022-02-15 Time 08:25 Rev Time 0.00
Received By shill Date 2022-02-03 Time 08:30 Sent To  
Notes
2022-02-07 12:34:29ZONING PASSED ON 10/22/21. NUMEROUS NEW PAGES WERE
 SUBMITTED ON 2/2/22 INCLUDING ELEVATIONS, ROUTED BACK
 TO ZONING SH

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 17:17 Rev Time 0.00
Received By rmcdouga Date 2022-01-07 Time 09:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-06 Cont ID  
Sent By shill Date 2022-01-06 Time 12:00 Rev Time 0.00
Received By shill Date 2021-12-16 Time 09:21 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By shill Date 2021-10-22 Time 17:51 Rev Time 0.00
Received By shill Date 2021-10-15 Time 06:23 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-03-01 Cont ID  
Sent By lmarchan Date 2022-03-01 Time 16:31 Rev Time 0.00
Received By lmarchan Date 2022-02-24 Time 07:59 Sent To  
Notes
2022-02-28 12:04:02RECEIPT MU-2022-008547 - $2404.37 PAID
2022-02-24 08:00:022/24/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date   Cont ID  
Sent By   Date 2021-10-12 Time   Rev Time  
Received By   Date 2021-10-12 Time   Sent To  
Notes
2021-10-12 10:06:30PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-23 Cont ID  
Sent By medwards Date 2022-02-23 Time 07:04 Rev Time 0.00
Received By medwards Date 2022-02-23 Time 07:04 Sent To  
Notes
2022-02-23 07:04:52MECHANICAL AUDIT ONLY APPROVED ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-29 Cont ID  
Sent By medwards Date 2021-12-29 Time 17:20 Rev Time 0.00
Received By medwards Date 2021-12-29 Time 17:20 Sent To  
Notes
2021-12-29 17:23:02MECHANICAL AUDIT:
 THE BARBEQUE GRILL IN THE COVERED PATIO AREA WILL
 REQUIRE A HOOD ABOVE IT. PLEASE PROVIDE THE HOOD
 DETAILS ALONG WITH A DETAIL DRAWING SHOWING THE EXHAUST
 DUCT AND TERMINATION LOCATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2022-01-10 Cont ID  
Sent By lcrespo Date 2022-01-10 Time 11:17 Rev Time 0.00
Received By lcrespo Date 2022-01-10 Time 11:17 Sent To  
Notes
2022-01-10 11:18:10ADUDIT APPROVED, LAC

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-03-03 Cont ID  
Sent By rmcphers Date 2022-03-03 Time 14:24 Rev Time 0.00
Received By rmcphers Date 2022-03-03 Time 14:23 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-02-22 Cont ID  
Sent By cthroop Date 2022-02-22 Time 16:04 Rev Time 0.00
Received By cthroop Date 2022-02-22 Time 14:28 Sent To  
Notes
2022-02-22 16:09:43PRIVATE PROVIDER AFFIDAVIT REVIEW
  
 CHRISTOPHER S. THROOP, C.B.O., CFM
 PLANS EXAMINER II PX3169/SFP306
 BU1635 BN4338
 ASFPM CFM US-21-11935
 CITY OF WEST PALM BEACH
 (561) 805-6726
 [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
  
 CODES IN EFFECT:
 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NFPA 70 2017 EDITION NEC 2017
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. AFFIDAVIT STATES PLANS SHEETS BY KELLY D. YATES,
 DATED OCTOBER 2021 (10/2021 ON PLANS)
 THE FOLLOWING PLAN PAGES ARE REV 3 DATED 01/2022;
 A-201, A-202, A-301, A-401, A-402, E-101 AND S-6.
 PLEASE CORRECT AFFIDAVIT AND RE-SUBMIT FOR REVIEW.
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-01-10 Cont ID  
Sent By shill Date 2022-01-10 Time 11:27 Rev Time 0.00
Received By shill Date 2022-01-10 Time 11:27 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-01-06 Cont ID  
Sent By shill Date 2022-01-06 Time 11:57 Rev Time 0.00
Received By shill Date 2022-01-06 Time 11:57 Sent To  
Notes
2022-01-06 12:00:17FS553.791 AFFIDAVIT DOES NOT MATCH DATES OF PLANS
 UPLOADED. FOR EXAMPLE, SEE A101. REFER TO EMAILS SENT
 TO APPLICANT WITH SCREEN SHOTS.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-12-17 Cont ID  
Sent By dbattles Date 2021-12-17 Time 13:07 Rev Time 0.00
Received By dbattles Date 2021-12-17 Time 13:07 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-02-28 Cont ID  
Sent By rmcdouga Date 2022-02-28 Time 08:45 Rev Time 0.00
Received By rmcdouga Date 2022-02-28 Time 08:45 Sent To  
Notes
2022-02-28 08:45:52PRODUCT APPROVALS FOR THE CONCRETE ROOF TILES,
 UNDERLAYMENT AND RIDGE METAL ARE BEING DEFERRED. SUBMIT
 THEM FOR AUDIT AFTER THEY HAVE BEEN APPROVED BY THE
 DESIGNER OF RECORD AND THE PRIVATE PROVIDER. DO NOT
 INSTALL UNTIL THE AUDIT HAS BEEN COMPLETED AND THE
 STAMPED PLANS ARE AT THE SITE.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 17:07 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 17:07 Sent To  
Notes
2022-01-13 17:08:23NO PRODUCT APPROVALS WERE SUBMITTED FOR THE ROOF
 COVERING.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-28 Cont ID  
Sent By rmcdouga Date 2022-02-28 Time 08:49 Rev Time 0.00
Received By rmcdouga Date 2022-02-28 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 17:09 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 16:35 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2022-02-18 Cont ID  
Sent By vbroglia Date 2022-02-18 Time 10:09 Rev Time 0.00
Received By vbroglia Date 2022-02-18 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2022-02-18 Cont ID  
Sent By vbroglia Date 2022-02-14 Time 15:51 Rev Time 0.00
Received By vbroglia Date 2022-02-14 Time 15:51 Sent To  
Notes
2022-02-14 15:56:482/14/2022 FAILED
  
 PLEASE SUBMIT A LANDSCAPE PERMIT TO ALLOW STAFF TO MOVE
 FOAWARD WITH CURRENT PERMIT
  
 VALENTINA BROGLIA
 ASSOCIATE PLANNER
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By awooten Date 2021-10-22 Time   Rev Time  
Received By awooten Date 2021-10-22 Time   Sent To  
Notes
2021-10-22 11:29:22******ZONING PROVISO*********
  
 PRIOR TO THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY,
 THE FOLLOWING CONDITIONS SHALL BE ADDRESSED:
  
 1. A LANDSCAPE PERMIT, WHICH INLUDES A LANDSCAPE PLAN,
 SHALL BE SUBMITTED TO THE BUILDING DIVISION FOR REVIEW.
  
 2. THE LANDSCAPE MATERIAL SHOWN ON THE APPROVED
 LANDSCAPE PERMIT SHALL BE INSTALLED AND PASS A FINAL
 LANDSCAPE INSPECTION.
  
 THE PROPOSED DRIVEWAY, POOL, AND FENCE REQUIRE A
 SEPARATE PERMIT.
  
 ALANA WOOTEN
 PLANNER
 561-22-1449
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy