| Plan Review Stops For Permit 21100029 |
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-01-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-01-11 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-01-11 |
Time |
15:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-10-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-16 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-16 |
Time |
08:30 |
Sent To |
|
|
| Notes |
| 2021-10-16 08:31:36 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS | | | REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | | | | UPLOAD THE ASBESTOS ACKNOWLEDGEMENT LETTER WHEN | | | RESUBMITTING. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-01-13 |
Time |
16:12 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-01-13 |
Time |
16:12 |
Sent To |
|
|
| Notes |
| 2022-01-13 16:16:10 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW APPROVED, AS PERMIT # 22010414 IS FOR | | | THE WINDOWS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-10-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-16 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-16 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2021-10-16 08:34:07 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. FBC 107, UNDER AN INTERIOR DEMOLITION PERMIT, YOU | | | CANNOT REMOVE EXTERIOR COMPONENTS. THE PLAN PROPOSES TO | | | REMOVE WINDOWS, DOORS. REVISE THE PLAN TO REMOVE THIS | | | SCOPE. REMOVAL OF EXTERIOR COMPONENTS NEEDS TO BE UNDER | | | A SEPARATE PERMIT THAT INCLUDES RESTORING THE BUILDING | | | ENVELOPE. THE INTENT OF AN INTERIOR DEMO PERMIT IS TO | | | ALLOW DEMOLITION OF INTERIOR COMPONENTS ONLY. | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-01-13 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-01-13 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-01-13 |
Time |
16:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-18 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-18 |
Time |
13:11 |
Sent To |
|
|
| Notes |
| 2021-10-18 13:17:08 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | WEST PALM BEACH PLAN REVIEW NEEDS AN ELECTRICAL PERMIT | | | APPLICATION FOR APPROVAL. PLEASE EMAIL THE ELECTRICAL | | | PERMIT APPLICATION TO [email protected], [email protected], | | | AND [email protected] SO WE RECEIVE IT ALSO. WHEN THIS | | | EMAIL IS RECEIVED ONE OF THE REVIEWERS WILL APPROVE THE | | | PLAN REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-10-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-10-18 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-01 |
Time |
12:48 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-01-11 |
|
|
Cont ID |
|
| Sent By |
pvalenti |
Date |
2022-01-11 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
pvalenti |
Date |
2022-01-11 |
Time |
15:15 |
Sent To |
|
|
| Notes |
| 2022-01-11 15:20:15 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | SIGNATURE REVIEW APPROVED BY ORIGINAL SIGNED/SEALED | | | PAPER SUBMITTALS (PAGE D-1 & D-1.1 BY SANDRA PUERTA | | | DATED 9/29/21). THESE (2) PAGES HAVE ALREADY BEEN | | | SCANNED INTO PROJECT DOX. THE OWNER TOOK PAPER PLANS | | | BACK AFTER CONFIRMATION OF MATCHING PLANS IN PROJECT | | | DOX. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-10-16 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-10-16 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-16 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2021-10-16 08:36:27 | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS. A SCAN OF A SIGNED | | | PLAN IS NOT CONSIDERED AN ORIGINAL. | | | | | | THE DOCUMENTS PREPARED BY SANDRA PUERTA, ARCHITECT, | | | APPEARS TO BE A SCAN OF A HAND SIGNED SIGNATURE. THIS | | | IS NOT A DIGITAL SIGNATURE. | | | | | | WHEN RESUBMITTING, UPLOAD DIGITALLY SIGNED DOCUMENTS, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION | | | AFTER ALL REVIEWS HAVE PASSED. SIGNATURE DOCUMENTS ARE | | | TYPICALLY REVIEWED WITHIN TWO BUSINESS DAYS AFTER | | | SUBMITTAL; DIGITALLY SIGNED DOCUMENTS ARE PREFERRED. | | | |
|
|