Plan Review Details - Permit 21100004
Plan Review Stops For Permit 21100004
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-05 Cont ID  
Sent By cpuell Date 2021-12-05 Time 11:45 Rev Time 0.00
Received By cpuell Date 2021-12-05 Time 11:45 Sent To  
Notes
2021-12-05 11:46:22FLOOR PLANS PROVIDED, UPDATED THE RELVANT DATABASES.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By cpuell Date 2021-11-19 Time 13:06 Rev Time 0.00
Received By cpuell Date 2021-11-19 Time 13:06 Sent To  
Notes
2021-11-19 13:08:22SUITE 1750 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR,
 SINCE WORK IS TO BE DONE ON THE 18TH FLOOR PLEASE
 PROVIDE A FLOOR PLAN FOR THAT FLOOR TOO. PLEASE EMAIL
 TO [email protected] FOR FURTHER QUESTIONS YOU CAN ALSO
 CALL 561-805-6659

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2022-01-27 Cont ID  
Sent By rmcphers Date 2022-01-27 Time 14:30 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 14:30 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By rmcphers Date 2021-11-19 Time 14:15 Rev Time 0.00
Received By rmcphers Date 2021-11-19 Time 11:49 Sent To  
Notes
2021-11-19 14:16:12PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY.
  
 ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS
 CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 15:29 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 15:29 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 10:21 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 10:21 Sent To  
Notes
2022-02-15 10:27:48OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE DOOR (18078) LOCATED IN THE FIRE
 RATED WALLS TO BE FIRE RATED PER FBC 716
  
 2) DRAWING (A2-31) DETAIL H SHOWS (18") FOR THE CENTER
 OF THE TOILET PAPER HOLDER TO THE FACE OF THE TOILET -
 PLEASE CORRECT - ACCESSIBLE RESTROOMS - DRAWING A0-00D
 - PLEASE SHOW THE DIMENSION OF THE TOILET PAPER HOLDER
 FROM THE FACE OF THE TOILET TO THE CENTER OF THE TOILET
 PAPER HOLDER - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3) PLEASE USE THE WORDS "REFLECTING OR REFLECTIVE"
 SURFACE - ACCESSIBLE RESTROOM - DRAWING A0-00D - FOR
 THE MIRROR PLEASE SHOW THE DIMENSION FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACE FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) PLEASE PROVIDE THE ROOF TOP MECHANICAL SCREENING
 DETAILS FROM A DESIGN PROFESSIONAL TO MEET THE WIND
 LOADS FBC 1609
 ROOF TOP SCREENING DETAILS MAY BE DEFERRED SUBMITTALS
 BY LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE
 PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-27 Cont ID  
Sent By rmcphers Date 2022-01-27 Time 14:29 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 13:52 Sent To  
Notes
2022-01-27 14:16:06OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED
 WALLS TO BE FIRE RATED PER FBC 716 (SUCH AS DOORS
 17029, 18075, 18074, 18070, 18069, 18068)
  
 2) ACCESSIBLE RESTROOMS - DRAWING A0-00D - PLEASE SHOW
 THE DIMENSION OF THE TOILET PAPER HOLDER FROM THE FACE
 OF THE TOILET TO THE CENTER OF THE TOILET PAPER HOLDER
 - FBC A 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 3) ACCESSIBLE RESTROOM - DRAWING A0-00D - FOR THE
 MIRROR PLEASE SHOW THE DIMENSION FROM THE FINISHED
 FLOOR TO THE REFLECTIVE SURFACE FBC A 603.3 MIRRORS.
 MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL
 BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING
 SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.
  
 4) ACCESSIBLE RESTROOM - DRAWING A0-00D - THE VERTICAL
 GRAB BAR SHOWN IS NOT A REQUIREMENT OF THE FBC
 ACCESSIBILITY - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE
 THE VERTICAL GRAB BAR PER FBC A 609.3 THE SPACE BETWEEN
 THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12
 INCHES (305 MM) MINIMUM.
  
 5) PLEASE PROVIDE THE ROOF TOP MECHANICAL SCREENING
 DETAILS FROM A DESIGN PROFESSIONAL TO MEET THE WIND
 LOADS FBC 1609
  
 6) ROOF TOP SCREENING DETAILS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS.
 FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS
 ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE
 NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT
 ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By rmcphers Date 2021-11-19 Time 14:16 Rev Time 0.00
Received By rmcphers Date 2021-11-19 Time 11:49 Sent To  
Notes
2021-11-19 14:14:39OFFICE BUILD OUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE DETAILS FOR THE RAISED FLOOR (NON
 CUMBUSTIBLE) PER FBC 603.1
  
 2) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW THE FIRE
 RATED WALLS PER SCHEDULE MARKINGS. - PLEASE CLARIFY THE
 FIRE RATED WALLS.
  
 3) PLEASE SHOW THE HOURLY FIRE RATING AND THE FIRE
 RATING PROTECTION TYPE FOR THE STEEL STAIR AND LANDING
 CONSTRUCTION PER FBC 601
  
 4) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW A RATED
 ELEVATOR LOBBY - ARE THE ELEVATOR HOIST WAYS
 PRESSURIZED? - PLEASE SHOW THE ELEVATOR HOIST WAY
 PROTECTION PER FBC 3006.3
  
 5) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED
 WALLS TO BE FIRE RATED PER FBC 716
  
 6) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING
 AND LATCHING PER FBC 716.5.9
  
 7) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION
 DIMENSIONS FOR THE TOILET GRAB BARS, FIXTURE CLEAR
 FLOOR SPACE, TOILET PAPER DISPENSER, MIRRORS ETC PER
 FBC ACCESSIBILITY CHAPTER 6.
  
 8) PLEASE SHOW THE FLOOR RAMP SLOPES AND ANY REQUIRED
 RAMP HAND RAILS PER FBC ACCESSIBILITY 405

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-02-04 Cont ID  
Sent By jleahy Date 2022-02-04 Time 15:24 Rev Time 0.00
Received By jleahy Date 2022-02-02 Time 15:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-20 Cont ID  
Sent By jleahy Date 2021-11-20 Time 17:10 Rev Time 0.00
Received By jleahy Date 2021-11-19 Time 16:45 Sent To  
Notes
2021-11-20 17:35:21ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NO LOAD CALCULATION SHOWN PLEASE SHOW HOW
 DISTRIBUTION WAS SIZED. 215.5
  
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL BE
 PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH
 A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE
 BUILDING OR
 OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL
 CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE
 DEMAND FACTORS USED,
 THE CALCULATED LOAD AFTER APPLYING DEMAND FACTORS, AND
 THE SIZE AND TYPE OF CONDUCTORS TO BE USED.
  
  
 2) POWER PLAN DOES NOT SHOW OUTLETS IN INDIVIDUAL
 OFFICES. THEY ARE SHOWN IN THE DETAILS PLEASE INDICATE
 OR COME UP WITH A SCHEDULE OF OFFICES AND WHAT TYPE OF
 POWER REQUIREMENTS ARE TO BE SUPPLIED.
  
 3) SEVERAL CONFERENCE ROOMS ARE SHOWN WHICH WILL HAVE
 TO MEET THE REQUIREMENTS OF 210.71(A)(B)
  
 210.71 MEETING ROOMS.
 (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2
 (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE
 OUTLETS FOR
 NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE
 RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH 210.71(B). WHERE
 A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S),
 EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION
 IN THE POSITION
 THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM.
 INFORMATIONAL NOTE NO. 1: FOR THE PURPOSES OF THIS
 SECTION,
 MEETING ROOMS ARE TYPICALLY DESIGNED OR INTENDED FOR
 THE GATHERING OF SEATED OCCUPANTS FOR SUCH PURPOSES AS
 CONFERENCES,
 DELIBERATIONS, OR SIMILAR PURPOSES, WHERE PORTABLE
 ELECTRONIC EQUIPMENT SUCH AS COMPUTERS, PROJECTORS, OR
 SIMILAR EQUIPMENT
 IS LIKELY TO BE USED. INFORMATIONAL NOTE NO. 2:
 EXAMPLES OF ROOMS THAT ARE NOT MEETING ROOMS INCLUDE
 AUDITORIUMS, SCHOOLROOMS,
 AND COFFEE SHOPS.
 (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF
 RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND
 RECEPTACLE OUTLETS IN
 FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED
 IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE
 PERMITTED TO BE LOCATED AS
 DETERMINED BY THE DESIGNER OR BUILDING OWNER. (1)
 RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE OUTLETS
 SHALL
 BE INSTALLED IN ACCORDANCE WITH 210.52(A)(1) THROUGH
 (A)(4). (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM
 THAT IS AT LEAST
 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF AT
 LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE
 RECEPTACLE OUTLET LOCATED IN THE
 FLOOR AT A DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY
 FIXED WALL FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF
 FLOOR SPACE.
  
 4) SAME AS NOTE TWO FOR THE DATA AND PHONE WIRING.
 SEPARATE PERMIT REQUIRED
  
 5) FAULT CURRENT CALCULATIONS REQUIRED FOR THE
 DISTRIBUTION SYSTEM ON 17 AND 18. 110.9, 110.10
  
 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN
 INTERRUPTING RATING AT NOMINAL
 CIRCUIT VOLTAGE AT LEAST EQUAL TO THE CURRENT THAT IS
 AVAILABLE AT THE LINE TERMINALS OF THE EQUIPMENT.
  
  
 6) RISER NOTE SHALL BE REQUIIRED ON PLAN TO SHOW WHERE
 POWER IS RECEIVED FROM FOR ALL PANELS ON THE 17TH AND
 18TH FLOORS PER 408.4(B)
  
 408.4(B) SOURCE OF SUPPLY. ALL SWITCHBOARDS,
 SWITCHGEAR, AND PANELBOARDS SUPPLIED BY A FEEDER(S) IN
 OTHER THAN ONE- OR TWO-FAMILY
 DWELLINGS SHALL BE PERMANENTLY MARKED TO INDICATE EACH
 DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES. THE
 LABEL SHALL BE
 PERMANENTLY AFFIXED, OF SUFFICIENT DURABILITY TO
 WITHSTAND THE ENVIRONMENT INVOLVED, AND NOT HANDWRITTEN

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-12 Cont ID  
Sent By pleduc Date 2022-01-12 Time   Rev Time 0.00
Received By pleduc Date 2022-01-11 Time 13:04 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By pleduc Date 2021-10-25 Time   Rev Time 0.00
Received By pleduc Date 2021-10-25 Time 14:28 Sent To  
Notes
2021-10-25 14:52:15THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET A0 -17 - THERE IS AN INDICATION OF COMMENT Z1
 1HR WATER CURTAIN EQUIVALENT.
  
 THERE IS A DOUBLE DOOR ALSO INDICATED WHICH CAN NOT BE
 WITHIN THE PROPOSED RATED WALL WITH A WINDOW SPRINKLER.
  
 THIS IS A MIS-APPLICATION OF A WATER CURTAIN.
  
 8.15.26* SPRINKLER-PROTECTED GLAZING.
  
 WHERE SPRINKLERS ARE USED IN COMBINATION WITH GLAZING
 AS AN ALTERNATIVE TO A REQUIRED FIRERATED
 WALL OR WINDOW ASSEMBLY, THE SPRINKLER-PROTECTED
 ASSEMBLY SHALL COMPLY WITH THE
 FOLLOWING:
 (1) SPRINKLERS SHALL BE LISTED AS SPECIFIC APPLICATION
 WINDOW SPRINKLERS UNLESS THE STANDARD
 SPRAY SPRINKLERS ARE SPECIFICALLY PERMITTED BY THE
 BUILDING CODE.
 (2) SPRINKLERS SHALL BE SUPPLIED BY A WET-PIPE SYSTEM.
 (3) GLAZING SHALL BE HEAT-STRENGTHENED, TEMPERED, OR
 GLASS CERAMIC AND SHALL BE FIXED.
 (4) WHERE THE ASSEMBLY IS REQUIRED TO BE PROTECTED FROM
 BOTH SIDES, SPRINKLERS SHALL BE
 INSTALLED ON BOTH SIDES OF THE GLAZING.
 (5) THE USE OF SPRINKLER-PROTECTED GLAZING SHALL BE
 LIMITED TO NON-LOAD-BEARING WALLS.
 (6) THE GLAZED ASSEMBLY SHALL NOT HAVE ANY HORIZONTAL
 MEMBERS THAT WOULD INTERFERE WITH UNIFORM
 DISTRIBUTION OF WATER OVER THE SURFACE OF THE GLAZING,
 AND THERE SHALL BE NO OBSTRUCTIONS
 BETWEEN SPRINKLERS AND GLAZING THAT WOULD OBSTRUCT
 WATER DISTRIBUTION.
 (7) THE WATER SUPPLY DURATION FOR THE DESIGN AREA THAT
 INCLUDES THE WINDOW SPRINKLERS SHALL
 NOT BE LESS THAN THE REQUIRED RATING OF THE
 ASSEMBLYAPPLICATION OF A WINDOW SPRINKLER WHICH CAN BE
 USED PER NFPA 13
  
 PLEASE REVIEW AND CORRECT
  
  
  
 2) SHEET A0 -18 - THERE IS AN INDICATION OF COMMENT Z3
 AREA OF REFUGE
  
 I AM NOT UNDERSTANDING THIS COMMENT OF WHAT IT
 REPRESENTED PURPOSE.
  
 FOR CLARIFICATION PURPOSES, WHAT IS THE CODE REFERNCE
 FOR THE REQUIERMENT?
  
 WHAT IS THE INTENT OF THE COMMENT/OCCUPANCY AND THIS
 PROPOSED AREA OF REFUGE?
  
  
 3) SHEET SP-001 - THE FIRE SPRINKLE SYSTEM SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ALL FIRE SPRINKLER WORK. INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGMENT TO THE SHEET.
  
  
  
 4) SHEET SP-001 - THE FIRE ALARM SYSTEM SHALL BE
 MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS
  
 ALL FIRE ALARM WORK. INCLUDING DEMO, SHALL BE DONE
 UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
 PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGMENT TO THE SHEET.
  
  
  
 5) ELECTICAL SHEETS INFORMATION - IF THERE IS ANY
 PROPOSED CARD READERS/ACCESS CONTROL ON ANY FLOOR IT
 SHALL BE INSTALLED UNDER SEPARATE PERMITS & SHOP
 DRAWINGS.
  
 IF APPLICABLE, PROVIDE A NOTE OF ACKNOWLEDEMENT.
  
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2022-02-16 Time   Rev Time 0.00
Received By aoliver Date 2022-02-14 Time 09:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-02-10 Cont ID  
Sent By lmarchan Date 2022-02-10 Time 15:15 Rev Time 0.00
Received By lmarchan Date 2022-01-10 Time 14:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-20 Cont ID  
Sent By jleahy Date 2021-11-20 Time 17:35 Rev Time 0.00
Received By jleahy Date 2021-10-20 Time 08:26 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2021-11-19 Cont ID  
Sent By rmcphers Date 2021-11-19 Time 14:17 Rev Time 0.00
Received By rmcphers Date 2021-11-19 Time 14:17 Sent To  
Notes
2021-11-19 14:18:09NO CHANGE OF OCCUPANCY

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-02-14 Cont ID  
Sent By medwards Date 2022-02-14 Time 16:20 Rev Time 0.00
Received By medwards Date 2022-02-14 Time 16:20 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-01-20 Cont ID  
Sent By medwards Date 2022-01-20 Time 16:19 Rev Time 0.00
Received By medwards Date 2022-01-20 Time 16:19 Sent To  
Notes
2022-01-20 16:20:22PLEASE PROVIDE PROVIDE THE OUTDOOR AIR CALCULATIONS
 ASKED FOR IN COMMENT 3 BELOW OF THE PREVIOUS MECHANICAL
 REVIEW.
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE FOR THESE TENANT SPACES. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-10 Cont ID  
Sent By medwards Date 2021-11-10 Time 16:15 Rev Time 0.00
Received By medwards Date 2021-11-09 Time 12:58 Sent To  
Notes
2021-11-10 16:15:411ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21100004
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COVER SHEET: PLEASE REFERENCE THE ASHRAE 62.1- 2016
 AS THIS IS THE EDITION REFERENCED IN THE 2020 FBC
 MECHANICAL CODE.
  
 2) PLEASE PROVIDE A DETAIL OF THE ROOF CONDENSING UNIT
 STAND AND THE APPLIANCE TIE DOWN METHOD. FBC 107.2.1
  
 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE FOR THESE TENANT SPACES. FBC M 403.3.1.1
 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-02-16 Cont ID  
Sent By ccole Date 2022-02-16 Time 16:27 Rev Time 0.00
Received By ccole Date 2022-02-16 Time 16:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By ccole Date 2022-02-14 Time 18:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-01-25 Cont ID  
Sent By ccole Date 2022-01-25 Time 17:32 Rev Time 0.00
Received By ccole Date 2022-01-25 Time 12:44 Sent To  
Notes
2022-01-25 17:32:482ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21100004
 1/25/22
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS.
  
 1) FAILED. SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED
 SERVICE SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND
 SHOW THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P.
 LOCATIONS OF SERVICE SINKS NOT SHOWN.
  
 7) FAILED. P-600: PROVIDE UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAILS FOR SEALING THE ANNULAR
 SPACES AROUND PLUMBING PIPING PENETRATING THE SLABS-
 SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. NOT
 PROVIDED.
  
 8) FAILED. A2-30 & A2-31: REFER TO SECTION 213 AND
 PROVIDE THE FOLLOWING FBC ACCESSIBILITY COMPLIANCE
 DETAILS: THE RESPONSE NARRATIVE REFERENCES SHEETS
 A0-00D & A5-40. SHEET A00-00D SHOWS STANDARD ADA
 DETAILS SOME OF WHICH ARE NOT CONSISTENT WITH THE FBC
 ACC WHICH IS THE GOVERNING CODE IN THE STATE OF
 FLORIDA. SHEET A5-40 PROVIDES ONLY KNEE AND TOE
 CLEARANCES FOR A RESTROOM SINK AND DOES NOT SPECIFY
 WHICH SINKS SHOULD BE INSTALLED ACCORDING TO THE
 DETAIL- SITE SPECIFIC DETAILS ARE REQUIRED. THE
 PROPOSED INSTALLATIONS SHALL BE IN COMPLIANCE WITH THE
 FOLLOWING FBC ACC CODE SECTIONS. REVISE THE PLANS
 ACCORDINGLY.
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3. SHOW THE DIAGRAMS AT ALL
 SINKS SPECIFIED AS ACCESSIBLE.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2. SHOW THE DIAGRAMS AT ALL
 WATER CLOSETS SPECIFIED AS ACCESSIBLE.
 C) TURNING SPACE DIAMETERS- SECTION 304.3. SHOW THE
 DIAGRAMS IN ALL ACCESSIBLE RESTROOMS.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2. SHOW THE CENTERLINES OF ALL WATER
 CLOSETS SPECIFIED AS ACCESSIBLE.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4. SHOW THE HEIGHT MEASURMENTS AT
 ALL WATER CLOSETS SPECIFIED AS ACCESSIBLE.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3. PROVIDE A LIST
 OF ACCESSIBLE LAVATORIES ON THE DETAIL.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3. NOT PROVIDED ON
 A0-00D.
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2. THE STANDARD DETAILS ON
 A0-00D SHOW THE MEASUREMENTS TO THE CENTERLINES OF THE
 GRAB BARS. MEASUREMENTS SHALL BE TO THE TOPS OF THE
 GRIPPING SURFACES.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6. NOT PROVIDED
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. INCORRECTLY SHOWN ON A0-00D.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2. PROVIDE A LIST OF ACCESSIBLE LAVATORIES ON THE
 DETAIL
  
 9) FAILED. A3-70, 71, 72, & 73- REFER TO PROVIDE THE
 FOLLOWING FBC ACC COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER
 FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES-
 SECTIONS 606.2 & 305. NOT PROVIDED.
 C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE
 MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308.
 NOT PROVIDED.
 D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS,
 MICROWAVES ETC.- SECTION 309. NOT PROVIDED.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS
  
 1) P-400: S3 SINKS IN GN RR 18069, 18070, 18074, 18075
 ARE MISLABELED AS S1 SINKS IN THE CLOUDED SANITARY
 RISER
  
 2) SHEET P-600: PLEASE PROVIDE ACCESSIBILITY COMPLIANCE
 NOTES WHERE REQUIRED IN THE PLUMBING FIXTURE SCHEDULE-
 SEC. 404.1 FBC P. SEE COMMENT #8 ABOVE. THE PLANS DO
 NOT CLEARLY ADDRESS WHICH RESTROOMS AND FIXTURES ARE TO
 BE ACCESSIBLE.
  
 3) P600 DEFFERRED SUBMITTALS: PROVIDE A LIST OF
 DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE
 LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES
 AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS
 SPECIFIED ON THE PLANS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-18 Cont ID  
Sent By ccole Date 2021-11-18 Time 08:04 Rev Time 0.00
Received By ccole Date 2021-11-17 Time 14:35 Sent To  
Notes
2021-11-18 08:05:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21100004
 11/17/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED SERVICE
 SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND SHOW
 THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P.
  
 2) A0-18: PLEASE PROVIDE THE CORRECT NUMBER OF WATER
 CLOSET AND LAVATORY FIXTURES PROVIDED BASED ON THE NEW
 BATHROOMS BEING INSTALLED ON THE FLOOR- TABLE 403.1 FBC
 P.
  
 3) P-001: PROVIDE A SANITARY DRAINAGE VENT ISOMETRIC
 DRAWING- SECTION 107.3.5.1.3 WPB.
  
 4) P-400 & P-600: PLEASE ADD W5 & W6 TO THE FIXTURE
 SCHEDULE- SECTION 107.2.1 WPB.
  
 5) P-400 & P-600: INDICATE HOW TEMPERED WATER WILL BE
 PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P.
 CLARIFY THE NOTE UNDER THE WH SCHEDULE ABOUT THE HOLBY
 TEMPERING VALVES. ARE THESE VALVES TEMPERATURE LIMITING
 DEVICES THAT CONFORM TO ASSE 1070 AS REQUIRED BY
 SECTION 607.1.2 FBC P? PLEASE SHOW THEIR LOCATIONS ON
 THE RISER.
  
 6) P-600: PLEASE PROVIDE A DEVICE SCHEDULE FOR WATER
 HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS
 AND TRAP PRIMERS- SECTIONS 604.9, 807.2.1, 608.3, AND
 1002.4.1 FBC P.
  
 7) P-600: PROVIDE UL TESTED AND APPROVED FIRESTOPPING
 ASSEMBLY DETAILS FOR SEALING THE ANNULAR SPACES AROUND
 PLUMBING PIPING PENETRATING THE SLABS- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 8) A2-30 & A2-31: REFER TO SECTION 213 AND PROVIDE THE
 FOLLOWING FBC ACCESSIBILITY COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSETS- SECTION 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORIES- SECTION 606.2.
 C) TURNING SPACE DIAMETERS- SECTION 304.3.
 D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE
 WALLS- SECTION 604.2.
 E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED
 FLOORS- SECTION 604.4.
 F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SECTION 606.3.
 G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO
 THE REFLECTIVE SURFACES- SECTION 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
  
 9) A3-70, 71, 72, & 73- REFER TO PROVIDE THE FOLLOWING
 FBC ACC COMPLIANCES:
 A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER
 FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES-
 SECTIONS 606.2 & 305.
 B) KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES TO
 SINKS BASED ON COMMENT ABOVE AND SECTIONS 606.2, 305, &
 306.
 C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE
 MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308.
 D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS,
 MICROWAVES ETC.- SECTION 309.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-02-16 Cont ID  
Sent By rmcphers Date 2022-02-16 Time 15:31 Rev Time 0.00
Received By rmcphers Date 2022-02-16 Time 15:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-02-15 Cont ID  
Sent By rmcphers Date 2022-02-15 Time 10:33 Rev Time 0.00
Received By rmcphers Date 2022-02-15 Time 10:33 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-27 Cont ID  
Sent By rmcphers Date 2022-01-27 Time 14:40 Rev Time 0.00
Received By rmcphers Date 2022-01-27 Time 14:40 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-19 Cont ID  
Sent By mpeterso Date 2021-11-19 Time 16:50 Rev Time 0.00
Received By mpeterso Date 2021-11-19 Time 16:50 Sent To  
Notes
2021-11-19 16:54:37DRAWINGS" M-001,, P-001, E-221" CANNOT AUTHORIZE THE
 DIGITAL SIGNATURES IN EITHER ADOBE OR BLUEBEAM
  
 PLEASE CORRECT THESE ISSUES AS OUTLINED BELOW
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-11-19 Cont ID  
Sent By rmcphers Date 2021-11-19 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2021-11-19 Time 14:44 Sent To  
Notes
2021-11-19 14:46:39SIGNATURE REVIEW
  
 DRAWINGS M-001, M-600, P-001, E-221 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
2021-11-10 16:18:20MECHANICAL SHEETS APPROVED ME

Review Stop Z ZONING
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By eschneid Date 2022-02-10 Time 14:33 Rev Time 0.50
Received By eschneid Date 2022-02-10 Time 13:08 Sent To  
Notes
2022-02-10 14:36:47PASSED W/PROVISO
  
 1) THE NEW ROOFTOP MECHANICAL EQUIPMENT SCREENWALLS
 REQUIRE A SEPARATE PERMIT WITH PLANS.
  
 2) THE FINAL INSPECTION (104) FOR THE BUILD-OUT
 APPROVED BY THIS PERMIT IS NOT TO BE ISSUED UNTIL THE
 SCREENWALL PERMIT IS APPROVED, THE SCREENWALL INSTALLED
 AND PASSES INSPECTION.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By eshneide Date 2021-10-22 Time 09:09 Rev Time 0.50
Received By eschneid Date 2021-10-22 Time 09:09 Sent To  
Notes
2021-10-22 09:13:39FAILED
  
 1) THE PLANS SHOW NEW ROOFTOP EQUIPMENT ON A NEW
 SUPPORT RACK. PROVIDE INFORMATION ON THE OVERALL HEIGHT
 OF THE NEW EQUIPMENT AND THE SUPPORT RACK.
  
 2) IN ACCORDANCE WITH THE BUILDING DESIGN WITH
 EQUIPMENT SCREEN WALLS AND THE CITYPLACE DRI
 REQUIREMENTS, YOU WILL NEED TO INSTALL SCREENING FOR
 THE FULL HEIGHT OF THE EQUIPMENT AROUND THE NEW
 EQUIPMENT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]