| Plan Review Stops For Permit 21100004 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-12-05 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-05 |
Time |
11:45 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-05 |
Time |
11:45 |
Sent To |
|
|
| Notes |
| 2021-12-05 11:46:22 | FLOOR PLANS PROVIDED, UPDATED THE RELVANT DATABASES. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-11-19 |
Time |
13:06 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-11-19 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2021-11-19 13:08:22 | SUITE 1750 IS NOT A RECOGNIZED SUITE NUMBER, PLEASE | | | PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR, | | | SINCE WORK IS TO BE DONE ON THE 18TH FLOOR PLEASE | | | PROVIDE A FLOOR PLAN FOR THAT FLOOR TOO. PLEASE EMAIL | | | TO [email protected] FOR FURTHER QUESTIONS YOU CAN ALSO | | | CALL 561-805-6659 |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-01-27 |
Time |
14:30 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-01-27 |
Time |
14:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-19 |
Time |
14:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-19 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2021-11-19 14:16:12 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-16 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-16 |
Time |
15:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2022-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-15 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-15 |
Time |
10:21 |
Sent To |
|
|
| Notes |
| 2022-02-15 10:27:48 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE DOOR (18078) LOCATED IN THE FIRE | | | RATED WALLS TO BE FIRE RATED PER FBC 716 | | | | | | 2) DRAWING (A2-31) DETAIL H SHOWS (18") FOR THE CENTER | | | OF THE TOILET PAPER HOLDER TO THE FACE OF THE TOILET - | | | PLEASE CORRECT - ACCESSIBLE RESTROOMS - DRAWING A0-00D | | | - PLEASE SHOW THE DIMENSION OF THE TOILET PAPER HOLDER | | | FROM THE FACE OF THE TOILET TO THE CENTER OF THE TOILET | | | PAPER HOLDER - FBC A 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | | | | 3) PLEASE USE THE WORDS "REFLECTING OR REFLECTIVE" | | | SURFACE - ACCESSIBLE RESTROOM - DRAWING A0-00D - FOR | | | THE MIRROR PLEASE SHOW THE DIMENSION FROM THE FINISHED | | | FLOOR TO THE REFLECTIVE SURFACE FBC A 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 4) PLEASE PROVIDE THE ROOF TOP MECHANICAL SCREENING | | | DETAILS FROM A DESIGN PROFESSIONAL TO MEET THE WIND | | | LOADS FBC 1609 | | | ROOF TOP SCREENING DETAILS MAY BE DEFERRED SUBMITTALS | | | BY LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION | | | DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. FOR THE | | | PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE | | | DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT | | | SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE | | | TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-01-27 |
Time |
14:29 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-01-27 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2022-01-27 14:16:06 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED | | | WALLS TO BE FIRE RATED PER FBC 716 (SUCH AS DOORS | | | 17029, 18075, 18074, 18070, 18069, 18068) | | | | | | 2) ACCESSIBLE RESTROOMS - DRAWING A0-00D - PLEASE SHOW | | | THE DIMENSION OF THE TOILET PAPER HOLDER FROM THE FACE | | | OF THE TOILET TO THE CENTER OF THE TOILET PAPER HOLDER | | | - FBC A 604.7 DISPENSERS. | | | TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND | | | SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230 | | | MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO | | | THE CENTERLINE OF THE DISPENSER. | | | | | | 3) ACCESSIBLE RESTROOM - DRAWING A0-00D - FOR THE | | | MIRROR PLEASE SHOW THE DIMENSION FROM THE FINISHED | | | FLOOR TO THE REFLECTIVE SURFACE FBC A 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 4) ACCESSIBLE RESTROOM - DRAWING A0-00D - THE VERTICAL | | | GRAB BAR SHOWN IS NOT A REQUIREMENT OF THE FBC | | | ACCESSIBILITY - PLEASE SHOW THE 12 INCH CLEARANCE ABOVE | | | THE VERTICAL GRAB BAR PER FBC A 609.3 THE SPACE BETWEEN | | | THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL BE 12 | | | INCHES (305 MM) MINIMUM. | | | | | | 5) PLEASE PROVIDE THE ROOF TOP MECHANICAL SCREENING | | | DETAILS FROM A DESIGN PROFESSIONAL TO MEET THE WIND | | | LOADS FBC 1609 | | | | | | 6) ROOF TOP SCREENING DETAILS MAY BE DEFERRED | | | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE | | | CONSTRUCTION DOCUMENTS - 107.3.4.1 DEFERRED SUBMITTALS. | | | FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS | | | ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE | | | NOT SUBMITTED AT THE TIME OF THE APPLICATION AND THAT | | | ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A | | | SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL | | | HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE | | | REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE | | | SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION | | | DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. | | | DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE | | | SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN | | | RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD | | | THEM TO THE BUILDING OFFICIAL WITH A NOTATION | | | INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE | | | BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO | | | THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL | | | ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED | | | SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING | | | OFFICIAL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-19 |
Time |
14:16 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-19 |
Time |
11:49 |
Sent To |
|
|
| Notes |
| 2021-11-19 14:14:39 | OFFICE BUILD OUT | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE DETAILS FOR THE RAISED FLOOR (NON | | | CUMBUSTIBLE) PER FBC 603.1 | | | | | | 2) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW THE FIRE | | | RATED WALLS PER SCHEDULE MARKINGS. - PLEASE CLARIFY THE | | | FIRE RATED WALLS. | | | | | | 3) PLEASE SHOW THE HOURLY FIRE RATING AND THE FIRE | | | RATING PROTECTION TYPE FOR THE STEEL STAIR AND LANDING | | | CONSTRUCTION PER FBC 601 | | | | | | 4) FLOOR PLAN FOR THE 17TH FLOOR DOES NOT SHOW A RATED | | | ELEVATOR LOBBY - ARE THE ELEVATOR HOIST WAYS | | | PRESSURIZED? - PLEASE SHOW THE ELEVATOR HOIST WAY | | | PROTECTION PER FBC 3006.3 | | | | | | 5) PLEASE SHOW THE DOORS LOCATED IN THE FIRE RATED | | | WALLS TO BE FIRE RATED PER FBC 716 | | | | | | 6) PLEASE SHOW THE FIRE RATED DOORS TO BE SELF CLOSING | | | AND LATCHING PER FBC 716.5.9 | | | | | | 7) ACCESSIBLE RESTROOMS - PLEASE SHOW THE LOCATION | | | DIMENSIONS FOR THE TOILET GRAB BARS, FIXTURE CLEAR | | | FLOOR SPACE, TOILET PAPER DISPENSER, MIRRORS ETC PER | | | FBC ACCESSIBILITY CHAPTER 6. | | | | | | 8) PLEASE SHOW THE FLOOR RAMP SLOPES AND ANY REQUIRED | | | RAMP HAND RAILS PER FBC ACCESSIBILITY 405 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-02-04 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-04 |
Time |
15:24 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-02 |
Time |
15:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-20 |
Time |
17:10 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-19 |
Time |
16:45 |
Sent To |
|
|
| Notes |
| 2021-11-20 17:35:21 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) NO LOAD CALCULATION SHOWN PLEASE SHOW HOW | | | DISTRIBUTION WAS SIZED. 215.5 | | | | | | 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY | | | HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS | | | SHALL BE | | | PROVIDED PRIOR TO THE INSTALLATION OF THE FEEDERS. SUCH | | | A DIAGRAM SHALL SHOW THE AREA IN SQUARE FEET OF THE | | | BUILDING OR | | | OTHER STRUCTURE SUPPLIED BY EACH FEEDER, THE TOTAL | | | CALCULATED LOAD BEFORE APPLYING DEMAND FACTORS, THE | | | DEMAND FACTORS USED, | | | THE CALCULATED LOAD AFTER APPLYING DEMAND FACTORS, AND | | | THE SIZE AND TYPE OF CONDUCTORS TO BE USED. | | | | | | | | | 2) POWER PLAN DOES NOT SHOW OUTLETS IN INDIVIDUAL | | | OFFICES. THEY ARE SHOWN IN THE DETAILS PLEASE INDICATE | | | OR COME UP WITH A SCHEDULE OF OFFICES AND WHAT TYPE OF | | | POWER REQUIREMENTS ARE TO BE SUPPLIED. | | | | | | 3) SEVERAL CONFERENCE ROOMS ARE SHOWN WHICH WILL HAVE | | | TO MEET THE REQUIREMENTS OF 210.71(A)(B) | | | | | | 210.71 MEETING ROOMS. | | | (A) GENERAL. EACH MEETING ROOM OF NOT MORE THAN 93 M2 | | | (1000 FT2) IN OTHER THAN DWELLING UNITS SHALL HAVE | | | OUTLETS FOR | | | NONLOCKING-TYPE, 125-VOLT, 15- OR 20-AMPERE | | | RECEPTACLES. THE OUTLETS SHALL BE INSTALLED IN | | | ACCORDANCE WITH 210.71(B). WHERE | | | A ROOM OR SPACE IS PROVIDED WITH MOVABLE PARTITION(S), | | | EACH ROOM SIZE SHALL BE DETERMINED WITH THE PARTITION | | | IN THE POSITION | | | THAT RESULTS IN THE SMALLEST SIZE MEETING ROOM. | | | INFORMATIONAL NOTE NO. 1: FOR THE PURPOSES OF THIS | | | SECTION, | | | MEETING ROOMS ARE TYPICALLY DESIGNED OR INTENDED FOR | | | THE GATHERING OF SEATED OCCUPANTS FOR SUCH PURPOSES AS | | | CONFERENCES, | | | DELIBERATIONS, OR SIMILAR PURPOSES, WHERE PORTABLE | | | ELECTRONIC EQUIPMENT SUCH AS COMPUTERS, PROJECTORS, OR | | | SIMILAR EQUIPMENT | | | IS LIKELY TO BE USED. INFORMATIONAL NOTE NO. 2: | | | EXAMPLES OF ROOMS THAT ARE NOT MEETING ROOMS INCLUDE | | | AUDITORIUMS, SCHOOLROOMS, | | | AND COFFEE SHOPS. | | | (B) RECEPTACLE OUTLETS REQUIRED. THE TOTAL NUMBER OF | | | RECEPTACLE OUTLETS, INCLUDING FLOOR OUTLETS AND | | | RECEPTACLE OUTLETS IN | | | FIXED FURNITURE, SHALL NOT BE LESS THAN AS DETERMINED | | | IN (1) AND (2). THESE RECEPTACLE OUTLETS SHALL BE | | | PERMITTED TO BE LOCATED AS | | | DETERMINED BY THE DESIGNER OR BUILDING OWNER. (1) | | | RECEPTACLE OUTLETS IN FIXED WALLS. RECEPTACLE OUTLETS | | | SHALL | | | BE INSTALLED IN ACCORDANCE WITH 210.52(A)(1) THROUGH | | | (A)(4). (2) FLOOR RECEPTACLE OUTLETS. A MEETING ROOM | | | THAT IS AT LEAST | | | 3.7 M (12 FT) WIDE AND THAT HAS A FLOOR AREA OF AT | | | LEAST 20 M2 (215 FT2) SHALL HAVE AT LEAST ONE | | | RECEPTACLE OUTLET LOCATED IN THE | | | FLOOR AT A DISTANCE NOT LESS THAN 1.8 M (6 FT) FROM ANY | | | FIXED WALL FOR EACH 20 M2 (215 FT2) OR MAJOR PORTION OF | | | FLOOR SPACE. | | | | | | 4) SAME AS NOTE TWO FOR THE DATA AND PHONE WIRING. | | | SEPARATE PERMIT REQUIRED | | | | | | 5) FAULT CURRENT CALCULATIONS REQUIRED FOR THE | | | DISTRIBUTION SYSTEM ON 17 AND 18. 110.9, 110.10 | | | | | | 110.9 INTERRUPTING RATING. EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS SHALL HAVE AN | | | INTERRUPTING RATING AT NOMINAL | | | CIRCUIT VOLTAGE AT LEAST EQUAL TO THE CURRENT THAT IS | | | AVAILABLE AT THE LINE TERMINALS OF THE EQUIPMENT. | | | | | | | | | 6) RISER NOTE SHALL BE REQUIIRED ON PLAN TO SHOW WHERE | | | POWER IS RECEIVED FROM FOR ALL PANELS ON THE 17TH AND | | | 18TH FLOORS PER 408.4(B) | | | | | | 408.4(B) SOURCE OF SUPPLY. ALL SWITCHBOARDS, | | | SWITCHGEAR, AND PANELBOARDS SUPPLIED BY A FEEDER(S) IN | | | OTHER THAN ONE- OR TWO-FAMILY | | | DWELLINGS SHALL BE PERMANENTLY MARKED TO INDICATE EACH | | | DEVICE OR EQUIPMENT WHERE THE POWER ORIGINATES. THE | | | LABEL SHALL BE | | | PERMANENTLY AFFIXED, OF SUFFICIENT DURABILITY TO | | | WITHSTAND THE ENVIRONMENT INVOLVED, AND NOT HANDWRITTEN |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-01-12 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-01-12 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-01-11 |
Time |
13:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2021-10-25 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-10-25 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-10-25 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2021-10-25 14:52:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) SHEET A0 -17 - THERE IS AN INDICATION OF COMMENT Z1 | | | 1HR WATER CURTAIN EQUIVALENT. | | | | | | THERE IS A DOUBLE DOOR ALSO INDICATED WHICH CAN NOT BE | | | WITHIN THE PROPOSED RATED WALL WITH A WINDOW SPRINKLER. | | | | | | THIS IS A MIS-APPLICATION OF A WATER CURTAIN. | | | | | | 8.15.26* SPRINKLER-PROTECTED GLAZING. | | | | | | WHERE SPRINKLERS ARE USED IN COMBINATION WITH GLAZING | | | AS AN ALTERNATIVE TO A REQUIRED FIRERATED | | | WALL OR WINDOW ASSEMBLY, THE SPRINKLER-PROTECTED | | | ASSEMBLY SHALL COMPLY WITH THE | | | FOLLOWING: | | | (1) SPRINKLERS SHALL BE LISTED AS SPECIFIC APPLICATION | | | WINDOW SPRINKLERS UNLESS THE STANDARD | | | SPRAY SPRINKLERS ARE SPECIFICALLY PERMITTED BY THE | | | BUILDING CODE. | | | (2) SPRINKLERS SHALL BE SUPPLIED BY A WET-PIPE SYSTEM. | | | (3) GLAZING SHALL BE HEAT-STRENGTHENED, TEMPERED, OR | | | GLASS CERAMIC AND SHALL BE FIXED. | | | (4) WHERE THE ASSEMBLY IS REQUIRED TO BE PROTECTED FROM | | | BOTH SIDES, SPRINKLERS SHALL BE | | | INSTALLED ON BOTH SIDES OF THE GLAZING. | | | (5) THE USE OF SPRINKLER-PROTECTED GLAZING SHALL BE | | | LIMITED TO NON-LOAD-BEARING WALLS. | | | (6) THE GLAZED ASSEMBLY SHALL NOT HAVE ANY HORIZONTAL | | | MEMBERS THAT WOULD INTERFERE WITH UNIFORM | | | DISTRIBUTION OF WATER OVER THE SURFACE OF THE GLAZING, | | | AND THERE SHALL BE NO OBSTRUCTIONS | | | BETWEEN SPRINKLERS AND GLAZING THAT WOULD OBSTRUCT | | | WATER DISTRIBUTION. | | | (7) THE WATER SUPPLY DURATION FOR THE DESIGN AREA THAT | | | INCLUDES THE WINDOW SPRINKLERS SHALL | | | NOT BE LESS THAN THE REQUIRED RATING OF THE | | | ASSEMBLYAPPLICATION OF A WINDOW SPRINKLER WHICH CAN BE | | | USED PER NFPA 13 | | | | | | PLEASE REVIEW AND CORRECT | | | | | | | | | | | | 2) SHEET A0 -18 - THERE IS AN INDICATION OF COMMENT Z3 | | | AREA OF REFUGE | | | | | | I AM NOT UNDERSTANDING THIS COMMENT OF WHAT IT | | | REPRESENTED PURPOSE. | | | | | | FOR CLARIFICATION PURPOSES, WHAT IS THE CODE REFERNCE | | | FOR THE REQUIERMENT? | | | | | | WHAT IS THE INTENT OF THE COMMENT/OCCUPANCY AND THIS | | | PROPOSED AREA OF REFUGE? | | | | | | | | | 3) SHEET SP-001 - THE FIRE SPRINKLE SYSTEM SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ALL FIRE SPRINKLER WORK. INCLUDING DEMO, SHALL BE DONE | | | UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF | | | ACKNOWLEDGMENT TO THE SHEET. | | | | | | | | | | | | 4) SHEET SP-001 - THE FIRE ALARM SYSTEM SHALL BE | | | MAINTAINED THROUGHOUT DEMO & CONSTRUCTION PERIODS | | | | | | ALL FIRE ALARM WORK. INCLUDING DEMO, SHALL BE DONE | | | UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | PLEASE ENSURE COMPLIANCE AND PROVIDE A NOTE OF | | | ACKNOWLEDGMENT TO THE SHEET. | | | | | | | | | | | | 5) ELECTICAL SHEETS INFORMATION - IF THERE IS ANY | | | PROPOSED CARD READERS/ACCESS CONTROL ON ANY FLOOR IT | | | SHALL BE INSTALLED UNDER SEPARATE PERMITS & SHOP | | | DRAWINGS. | | | | | | IF APPLICABLE, PROVIDE A NOTE OF ACKNOWLEDEMENT. | | | | | | | | | | | | 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-02-16 |
Time |
|
Rev Time |
0.00 |
| Received By |
aoliver |
Date |
2022-02-14 |
Time |
09:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-02-10 |
Time |
15:15 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-10 |
Time |
14:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-20 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-20 |
Time |
17:35 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-10-20 |
Time |
08:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-19 |
Time |
14:17 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-19 |
Time |
14:17 |
Sent To |
|
|
| Notes |
| 2021-11-19 14:18:09 | NO CHANGE OF OCCUPANCY |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-14 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-14 |
Time |
16:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-01-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-20 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-20 |
Time |
16:19 |
Sent To |
|
|
| Notes |
| 2022-01-20 16:20:22 | PLEASE PROVIDE PROVIDE THE OUTDOOR AIR CALCULATIONS | | | ASKED FOR IN COMMENT 3 BELOW OF THE PREVIOUS MECHANICAL | | | REVIEW. | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE FOR THESE TENANT SPACES. FBC M 403.3.1.1 | | | AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-10 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-10 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-09 |
Time |
12:58 |
Sent To |
|
|
| Notes |
| 2021-11-10 16:15:41 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21100004 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) COVER SHEET: PLEASE REFERENCE THE ASHRAE 62.1- 2016 | | | AS THIS IS THE EDITION REFERENCED IN THE 2020 FBC | | | MECHANICAL CODE. | | | | | | 2) PLEASE PROVIDE A DETAIL OF THE ROOF CONDENSING UNIT | | | STAND AND THE APPLIANCE TIE DOWN METHOD. FBC 107.2.1 | | | | | | 3) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH | | | USE OF SPACE FOR THESE TENANT SPACES. FBC M 403.3.1.1 | | | AND TABLE 403.3.1.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-16 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-16 |
Time |
16:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-14 |
Time |
18:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-01-25 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-01-25 |
Time |
17:32 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-01-25 |
Time |
12:44 |
Sent To |
|
|
| Notes |
| 2022-01-25 17:32:48 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 21100004 | | | 1/25/22 | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE | | | 1ST REVIEW LISTED BELOW WITH ADDITIONAL NOTES IN CAPS. | | | | | | 1) FAILED. SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED | | | SERVICE SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND | | | SHOW THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P. | | | LOCATIONS OF SERVICE SINKS NOT SHOWN. | | | | | | 7) FAILED. P-600: PROVIDE UL TESTED AND APPROVED | | | FIRESTOPPING ASSEMBLY DETAILS FOR SEALING THE ANNULAR | | | SPACES AROUND PLUMBING PIPING PENETRATING THE SLABS- | | | SECTION 315.1 FBC P AND SECTION 714.4.1.2 FBC B. NOT | | | PROVIDED. | | | | | | 8) FAILED. A2-30 & A2-31: REFER TO SECTION 213 AND | | | PROVIDE THE FOLLOWING FBC ACCESSIBILITY COMPLIANCE | | | DETAILS: THE RESPONSE NARRATIVE REFERENCES SHEETS | | | A0-00D & A5-40. SHEET A00-00D SHOWS STANDARD ADA | | | DETAILS SOME OF WHICH ARE NOT CONSISTENT WITH THE FBC | | | ACC WHICH IS THE GOVERNING CODE IN THE STATE OF | | | FLORIDA. SHEET A5-40 PROVIDES ONLY KNEE AND TOE | | | CLEARANCES FOR A RESTROOM SINK AND DOES NOT SPECIFY | | | WHICH SINKS SHOULD BE INSTALLED ACCORDING TO THE | | | DETAIL- SITE SPECIFIC DETAILS ARE REQUIRED. THE | | | PROPOSED INSTALLATIONS SHALL BE IN COMPLIANCE WITH THE | | | FOLLOWING FBC ACC CODE SECTIONS. REVISE THE PLANS | | | ACCORDINGLY. | | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | WATER CLOSETS- SECTION 604.3. SHOW THE DIAGRAMS AT ALL | | | SINKS SPECIFIED AS ACCESSIBLE. | | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | LAVATORIES- SECTION 606.2. SHOW THE DIAGRAMS AT ALL | | | WATER CLOSETS SPECIFIED AS ACCESSIBLE. | | | C) TURNING SPACE DIAMETERS- SECTION 304.3. SHOW THE | | | DIAGRAMS IN ALL ACCESSIBLE RESTROOMS. | | | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE | | | WALLS- SECTION 604.2. SHOW THE CENTERLINES OF ALL WATER | | | CLOSETS SPECIFIED AS ACCESSIBLE. | | | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED | | | FLOORS- SECTION 604.4. SHOW THE HEIGHT MEASURMENTS AT | | | ALL WATER CLOSETS SPECIFIED AS ACCESSIBLE. | | | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE | | | FROM THE FINISHED FLOOR- SECTION 606.3. PROVIDE A LIST | | | OF ACCESSIBLE LAVATORIES ON THE DETAIL. | | | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | | THE REFLECTIVE SURFACES- SECTION 603.3. NOT PROVIDED ON | | | A0-00D. | | | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. THE STANDARD DETAILS ON | | | A0-00D SHOW THE MEASUREMENTS TO THE CENTERLINES OF THE | | | GRAB BARS. MEASUREMENTS SHALL BE TO THE TOPS OF THE | | | GRIPPING SURFACES. | | | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - | | | SECTION 604.6. NOT PROVIDED | | | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND | | | FIGURE 604.7. INCORRECTLY SHOWN ON A0-00D. | | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION | | | 606.2. PROVIDE A LIST OF ACCESSIBLE LAVATORIES ON THE | | | DETAIL | | | | | | 9) FAILED. A3-70, 71, 72, & 73- REFER TO PROVIDE THE | | | FOLLOWING FBC ACC COMPLIANCES: | | | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER | | | FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES- | | | SECTIONS 606.2 & 305. NOT PROVIDED. | | | C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE | | | MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308. | | | NOT PROVIDED. | | | D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS, | | | MICROWAVES ETC.- SECTION 309. NOT PROVIDED. | | | | | | NEW COMMENTS BASED ON RESUBMITTED PLANS | | | | | | 1) P-400: S3 SINKS IN GN RR 18069, 18070, 18074, 18075 | | | ARE MISLABELED AS S1 SINKS IN THE CLOUDED SANITARY | | | RISER | | | | | | 2) SHEET P-600: PLEASE PROVIDE ACCESSIBILITY COMPLIANCE | | | NOTES WHERE REQUIRED IN THE PLUMBING FIXTURE SCHEDULE- | | | SEC. 404.1 FBC P. SEE COMMENT #8 ABOVE. THE PLANS DO | | | NOT CLEARLY ADDRESS WHICH RESTROOMS AND FIXTURES ARE TO | | | BE ACCESSIBLE. | | | | | | 3) P600 DEFFERRED SUBMITTALS: PROVIDE A LIST OF | | | DEFERRED SUBMITTALS ON THE PLAN- SEC. 107.4.1 WPB. THE | | | LIST SHALL INCLUDE ALL FIXTURES, DEVICES, APPLIANCES | | | AND EQUIPMENT THAT DO NOT HAVE MAKES AND MODELS | | | SPECIFIED ON THE PLANS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-11-18 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-11-18 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-11-17 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2021-11-18 08:05:11 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21100004 | | | 11/17/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A0-17 & A0-18: PLEASE ADD THE REQUIRED SERVICE | | | SINKS TO THE PLUMBING FIXTURE CALCULATIONS AND SHOW | | | THEIR LOCATIONS ON THE PLANS- TABLE 403.1 FBC P. | | | | | | 2) A0-18: PLEASE PROVIDE THE CORRECT NUMBER OF WATER | | | CLOSET AND LAVATORY FIXTURES PROVIDED BASED ON THE NEW | | | BATHROOMS BEING INSTALLED ON THE FLOOR- TABLE 403.1 FBC | | | P. | | | | | | 3) P-001: PROVIDE A SANITARY DRAINAGE VENT ISOMETRIC | | | DRAWING- SECTION 107.3.5.1.3 WPB. | | | | | | 4) P-400 & P-600: PLEASE ADD W5 & W6 TO THE FIXTURE | | | SCHEDULE- SECTION 107.2.1 WPB. | | | | | | 5) P-400 & P-600: INDICATE HOW TEMPERED WATER WILL BE | | | PROVIDED TO THE LAVATORIES- SECTION 419.5 FBC P. | | | CLARIFY THE NOTE UNDER THE WH SCHEDULE ABOUT THE HOLBY | | | TEMPERING VALVES. ARE THESE VALVES TEMPERATURE LIMITING | | | DEVICES THAT CONFORM TO ASSE 1070 AS REQUIRED BY | | | SECTION 607.1.2 FBC P? PLEASE SHOW THEIR LOCATIONS ON | | | THE RISER. | | | | | | 6) P-600: PLEASE PROVIDE A DEVICE SCHEDULE FOR WATER | | | HAMMER ARRESTORS, MIXING VALVES, BACKFLOW PREVENTERS | | | AND TRAP PRIMERS- SECTIONS 604.9, 807.2.1, 608.3, AND | | | 1002.4.1 FBC P. | | | | | | 7) P-600: PROVIDE UL TESTED AND APPROVED FIRESTOPPING | | | ASSEMBLY DETAILS FOR SEALING THE ANNULAR SPACES AROUND | | | PLUMBING PIPING PENETRATING THE SLABS- SECTION 315.1 | | | FBC P AND SECTION 714.4.1.2 FBC B. | | | | | | 8) A2-30 & A2-31: REFER TO SECTION 213 AND PROVIDE THE | | | FOLLOWING FBC ACCESSIBILITY COMPLIANCE DETAILS: | | | A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | WATER CLOSETS- SECTION 604.3. | | | B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE | | | LAVATORIES- SECTION 606.2. | | | C) TURNING SPACE DIAMETERS- SECTION 304.3. | | | D) CENTERLINES OF THE WATER CLOSETS FROM THE SIDE | | | WALLS- SECTION 604.2. | | | E) HEIGHTS OF THE WATER CLOSET SEATS FROM THE FINISHED | | | FLOORS- SECTION 604.4. | | | F) HEIGHTS OF THE LAVATORY SINK RIM OR COUNTER SURFACE | | | FROM THE FINISHED FLOOR- SECTION 606.3. | | | G) HEIGHTS OF THE MIRRORS FROM THE FINISHED FLOORS TO | | | THE REFLECTIVE SURFACES- SECTION 603.3 | | | H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB | | | BARS FOR THE WATER CLOSETS- SECTION 604.5 & 609.4, | | | FIGURES 604.5.1 & 604.5.2. | | | I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS - | | | SECTION 604.6. | | | J) CENTERLINES OF THE TOILET PAPER DISPENSERS MEASURED | | | FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND | | | FIGURE 604.7. | | | K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION | | | 606.2. | | | | | | 9) A3-70, 71, 72, & 73- REFER TO PROVIDE THE FOLLOWING | | | FBC ACC COMPLIANCES: | | | A) CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR EITHER | | | FORWARD OR PARALLEL APPROACHES TO SINKS, APPLIANCES- | | | SECTIONS 606.2 & 305. | | | B) KNEE AND TOE CLEARANCES FOR FORWARD APPROACHES TO | | | SINKS BASED ON COMMENT ABOVE AND SECTIONS 606.2, 305, & | | | 306. | | | C) REACH HEIGHTS FOR COUNTERTOP APPLIANCES- COFFEE | | | MAKERS, WATER DISPENSERS, MICROWAVES ETC.- SECTION 308. | | | D) OPERABLE PARTS OF COFFEE MAKERS, WATER DISPENSERS, | | | MICROWAVES ETC.- SECTION 309. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-02-16 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-16 |
Time |
15:31 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-16 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-02-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-02-15 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-02-15 |
Time |
10:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-01-27 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-01-27 |
Time |
14:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
mpeterso |
Date |
2021-11-19 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
mpeterso |
Date |
2021-11-19 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2021-11-19 16:54:37 | DRAWINGS" M-001,, P-001, E-221" CANNOT AUTHORIZE THE | | | DIGITAL SIGNATURES IN EITHER ADOBE OR BLUEBEAM | | | | | | PLEASE CORRECT THESE ISSUES AS OUTLINED BELOW | | | | | | FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR | | | ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE | | | SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND | | | SIGNED. | | | | | | EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN | | | TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF | | | APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX, | | | OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER | | | ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION. | | | SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO | | | BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED | | | DOCUMENTS ARE PREFERRED. | | | | | | PLEASE EMAIL [email protected] AND CC TO | | | [email protected] | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
F |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-19 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-19 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2021-11-19 14:46:39 | SIGNATURE REVIEW | | | | | | DRAWINGS M-001, M-600, P-001, E-221 DO NOT SHOW AS | | | DIGITALLY SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR | | | ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A | | | CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED | | | A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF | | | E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES | | | NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN | | | DROP OFF THE ORIGINAL SIGNED AND SEALED | | | DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING | | | DIVISION AT THE CITY HALL. | | | | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | | | 2021-11-10 16:18:20 | MECHANICAL SHEETS APPROVED ME |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-02-10 |
Time |
14:33 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2022-02-10 |
Time |
13:08 |
Sent To |
|
|
| Notes |
| 2022-02-10 14:36:47 | PASSED W/PROVISO | | | | | | 1) THE NEW ROOFTOP MECHANICAL EQUIPMENT SCREENWALLS | | | REQUIRE A SEPARATE PERMIT WITH PLANS. | | | | | | 2) THE FINAL INSPECTION (104) FOR THE BUILD-OUT | | | APPROVED BY THIS PERMIT IS NOT TO BE ISSUED UNTIL THE | | | SCREENWALL PERMIT IS APPROVED, THE SCREENWALL INSTALLED | | | AND PASSES INSPECTION. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-10-22 |
|
|
Cont ID |
|
| Sent By |
eshneide |
Date |
2021-10-22 |
Time |
09:09 |
Rev Time |
0.50 |
| Received By |
eschneid |
Date |
2021-10-22 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2021-10-22 09:13:39 | FAILED | | | | | | 1) THE PLANS SHOW NEW ROOFTOP EQUIPMENT ON A NEW | | | SUPPORT RACK. PROVIDE INFORMATION ON THE OVERALL HEIGHT | | | OF THE NEW EQUIPMENT AND THE SUPPORT RACK. | | | | | | 2) IN ACCORDANCE WITH THE BUILDING DESIGN WITH | | | EQUIPMENT SCREEN WALLS AND THE CITYPLACE DRI | | | REQUIREMENTS, YOU WILL NEED TO INSTALL SCREENING FOR | | | THE FULL HEIGHT OF THE EQUIPMENT AROUND THE NEW | | | EQUIPMENT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446 | | | [email protected] |
|
|