| 2021-11-10 17:41:10 | BUILDING PLAN REVIEW |
| | |
| | CHRISTOPHER S. THROOP, C.B.O., CFM |
| | PLANS EXAMINER II PX3169/SFP306 |
| | INSPECTOR BN4338 |
| | BUILDING OFFICIAL BU1635 |
| | ASFPM CERTIFIED FLOODPLAIN MANAGER US-21-11935 |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | (561) 805-6726 |
| | [email protected] |
| | |
| | CODES IN EFFECT: |
| | 2020 FLORIDA BUILDING CODE, 7TH EDITION W/2017 WEST |
| | PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| | CHAPTER 1 ADMINISTRATION |
| | NFPA 70 2017 EDITION NEC 2017 |
| | |
| | 1ST REVIEW |
| | |
| | RE: 345 SHUTTERS |
| | |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SUBMIT A SEPERATE PERMIT FOR EACH STRUCTURE (6 |
| | TOTAL). INCLUDE CORRECT ADDRESS AND PCN NUMBER. ASSIGN |
| | THE APPROPRIATE VALUE TO EACH PERMIT BASED ON THE |
| | NUMBER AND TYPE OF SHUTTERS TO BE INSTALLED. |
| | PERMITS - 105.1 REQUIRED. |
| | |
| | 2. PROVIDE ELEVATION VIEWS OF EACH STRUCTURE. IDENTIFY |
| | THE PLANS BY ADDRESS. SHOW LOCATION OF SHUTTERS ON EACH |
| | FLOOR LEVEL AND EACH ELEVATION (N/S/E/W). |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | NOTE: THE FLOOR PLANS AND PHOTOS ATTACHED TO YOUR |
| | E-MAIL WILL WORK FOR THE COLOMIAL MASTER SHUTTERS. |
| | (NEED ATTACCHMENT DETAIL OR FASTENER SCHEDULE FOR EACH |
| | OF THE 3 SIZES OF COLONIAL SHUTTERS) |
| | |
| | 3. PROVIDE A CURRENT FLORIDA PRODUCT APPROVAL OR A SHOP |
| | DRAWING OF EACH TYPE OF SHUTTER. SHOP DRAWING SHALL BE |
| | PEREPARED BY A QUALIFIED DESIGN PROFESSIONAL, SIGNED |
| | AND SEALED. |
| | FBC 107.3.4 PROVIDE PRODUCT APPROVALS FOR THOSE |
| | PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| | |
| | 4. FLOOR PLANS OF EACH STRUCTURE SHALL BE IDENTIFYED BY |
| | ADDRESS. FLOOR PLANS SUBMITTED FOR REVIEW APPEAR TO BE |
| | FOR 1 LEVEL OF A 4 STORY STRUCTURE. PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 5. DESIGN PRESSURE CALCULATIONS SHALL BE PREPARED BY A |
| | QUALIFIED DESIGN PROFESSIONAL. CALCULATIONS SHALL BE |
| | BASED ON THE FBC CHPT. 16 OR ASCE 7-16. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 6. IDENTIFY DESIGN PRESSURE CALCULATIONS BY BUILDING |
| | ADDRESS. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 7. DESIGN PRESSURE CALCULATIONS SUBMITTED FOR REVIEW |
| | REFERENCE DEVICE WIDTH. FLOOR PLANS SUBMITTED FOR |
| | REVIEW REFERENCES OPENING WIDTH. PLEASE CLARIFY. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 8. DESIGN PRESSURE CALCULATIONS, FLOOR PLANS AND |
| | ELEVATION VIEWS SHALL BE COORDINATED. |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | 9. DESIGN PRESSURE CALCULATINS SUBMITTED FOR REVIEW |
| | REFERENCE INTERIOR ZONES ONLY. PROVIDE PRESSURES FOR |
| | SHUTTERS LOCATED IN EXTERIOR ZONES (ZONE 5). |
| | 107.2 CONSTRUCTION DOCUMENTS. CONSTRUCTION DOCUMENTS |
| | SHALL BE IN ACCORDANCE WITH SECTIONS107.2.1 THROUGH |
| | 107.2.5. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |
| | |