| 2021-12-01 11:00:37 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21091350 |
| | |
| | |
| | NOTE: |
| | SEC. 606 FBC-EXISTING BUILDING. SEC. 1101.1 |
| | FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS, |
| | COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THE FLORIDA BUILDING CODE. |
| | |
| | 1- DESIGN CRITERIA: |
| | A) ENGINEER TO UPDATE CODE REFERENCE. CODE IN EFFECT IS |
| | THE 2020 FBC 7TH EDITION NOT 2017 FBC 6TH EDITION. |
| | REVISE AS REQUIRED. SEC. 553 F.S. |
| | |
| | B) ENGINEER TO SPECIFY ALL THE WIND DESIGN CRITERIA AS |
| | REQUIRED BY SEC. R301.2.1 FBC-RESIDENTIAL. SPECIFY THE |
| | ULTIMATE AND NOMINAL WIND LOAD, BUILDING EXPOSURE, |
| | BUILDING MEAN ROOF HEIGHT, ETC. ALSO, SPECIFY THE ROOF |
| | COMPONENTS AND CLADDING DESIGN PRESSURES. |
| | |
| | 2- ENGINEER TO REVISE ROOF SHEATHING NAILING TYPE AND |
| | SPACING. ROOF SHEATHING NEEDS TO BE NAILED WITH RING |
| | SHANK NAILS AT 4 INCHES O.C. IN THE FIELD AND EDGES AS |
| | REQUIRED BY SEC. R803.2.3.1 AND TABLE R803.2.3.1 |
| | FBC-RESIDENTIAL. |
| | |
| | 3- SECTION DETAIL ON SHEET 1 OF 1: |
| | A)UPLIFT OF 14300# SPECIFIED FOR THE SIMPSON "ACA" POST |
| | CAP IS INCORRECT. SEE SIMPSON CATALOG AND REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.1 |
| | FBC-RESIDENTIAL. |
| | |
| | B) ENGINEER TO CLARIFY WHY SPECIFYING SIMPSON "H10-2" |
| | CONNECTORS FOR THE ROOF JOISTS IF THERE ARE NOT DOUBLE |
| | ROOF JOISTS. SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | 4- 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR FLAT ROOF. |
| | NOTE: CLEARLY MARK WHICH APPROVED ASSEMBLY IS GOING TO |
| | BE INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 6- ENGINEER OF RECORD NEEDS TO UPDATE THE STATUS OF HIS |
| | LICENSE. ENGINEER TO CONTACT DBPR (DEPARTMENT OF |
| | BUSINESS & PROFESSIONAL REGULATION). CHAPTER |
| | 61G15-22.0001 LICENSE RENEWAL. |
| | |
| | 7- VALUATION DECLARED IN THE PERMIT APPLICATION IS LOW. |
| | VALUATION TO INCLUDE ALL LABOR, MATERIALS, CONTRACTOR'S |
| | OVERHEAD AND PROFIT AND DESIGN PROFESSIONAL FEES AS |
| | REQUIRED BY SEC. 109.3 CITY AMENDMENTS. |
| | VALUATION WAS UPDATED TO $10,000. THE PERMIT FEE |
| | BALANCE IS $154.62 |
| | |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL |
| | HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |