Plan Review Details - Permit 21091343
Plan Review Stops For Permit 21091343
Review Stop AD ADDRESSING
Rev No 5 Status P Date 2022-09-15 Cont ID  
Sent By cpuell Date 2022-09-15 Time 12:46 Rev Time 0.00
Received By cpuell Date 2022-09-15 Time 12:45 Sent To  
Notes
2022-09-15 12:47:12APPLICATION AND COVER SHEET UPDATED TO REFLECT THE
 APPROVED ADDRESS.

Review Stop AD ADDRESSING
Rev No 4 Status F Date 2022-08-30 Cont ID  
Sent By cpuell Date 2022-08-30 Time 13:13 Rev Time 0.00
Received By cpuell Date 2022-08-30 Time 13:13 Sent To  
Notes
2022-08-30 13:14:35UNIT ADDRESSES HAVE BEEN ESTABLISHED, HOWEVER THE PLANS
 AND APPLICATION FORMS ARE STILL SHOWING THE INCORRECT
 ADDRESS, APPLICANT HAS BEEN NOTIFIED.

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2022-07-21 Cont ID  
Sent By cpuell Date 2022-07-21 Time 11:47 Rev Time 0.00
Received By cpuell Date 2022-07-21 Time 11:47 Sent To  
Notes
2022-07-21 11:51:46PLANS UPLOADED WITH THE INCORRECT ADDRESS OF 350
 AUSTRALIAN AVE, THIS IS NOT THE APPROVED AND AGREED
 UPON ADDRESS. UNITS HAVE YET TO BE ESTABLISHED. PLEASE
 CONTACT [email protected] OR CALL 561-805-6659

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2022-03-10 Cont ID  
Sent By cpuell Date 2022-03-10 Time 15:33 Rev Time 0.00
Received By cpuell Date 2022-03-10 Time 15:33 Sent To  
Notes
2022-03-10 15:33:21PREVIOUS COMMENTS NOT ADDRESSED, ADDRESSING WAS A
 CONDITION OF APPROVAL OF PPRC CASE Z21040018

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By cpuell Date 2021-10-22 Time 10:35 Rev Time 0.00
Received By ptharpe Date 2021-10-29 Time 07:17 Sent To  
Notes
2021-10-22 10:36:55A UNIQUE ADDRESS NEEDS TO BE ASSIGNED TO THIS PROJECT
 USING THE PCN 74434321210000022, AS WELL AS UNIT
 ADDRESSES PLEASE PROVIDE A SITE PLAN SHOWING THE MAIN
 ENTRANCE TO THE BUILDING AND EACH FLOOR PLAN SHOWING
 THE UNITS ON EACH FLOOR. PLEASE EMAIL TO [email protected]
 OR CALL 561-805-6659.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 3 Status P Date 2022-09-07 Cont ID  
Sent By scwelter Date 2022-08-29 Time 09:30 Rev Time 0.00
Received By scwelter Date 2022-09-07 Time 10:44 Sent To  
Notes
2022-08-29 09:33:19PUBLIC ART REQUIREMENT SATISFIED AND COMPLETED. CO HOLD
 RELEASED FOR PUBLIC ART 9.07.2022
  
 PUBLIC ART REQUIREMENT NOT SATISFIED.
 INVOICE SENT 8.15.2022 VIA EMAIL TO BRIAN BARTZACK,
 HYPERION DEVELOPMENT GROUP
  
  

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 2 Status F Date 2022-08-04 Cont ID  
Sent By scwelter Date 2022-08-04 Time 11:26 Rev Time 0.00
Received By scwelter Date   Time   Sent To  
Notes
2022-08-04 11:27:33APPLICANT HAS RECEIVED THE ART ASSESSMENT APPLICATION.
 CURRENTLY, WAITING FOR APPLICANT TO COMPLETE AND RETURN
 THE ASSESSMENT WHICH IS DUE NOW.

Review Stop AIPP ART IN PUBLIC PLACES
Rev No 1 Status F Date 2021-10-13 Cont ID  
Sent By scwelter Date 2021-10-13 Time 14:19 Rev Time 0.00
Received By scwelter Date 2021-10-13 Time 14:20 Sent To  
Notes
2021-10-13 14:20:20TOTAL CONSTRUCTION COSTS OF THIS DEVELOPMENT ARE OVER
 $500,000 IT IS SUBJECT TO THE PUBLIC ART REQUIREMENT AS
 PER CITY ORDINANCE.
  
 SECTION 78-129: ALL PRIVATE DEVELOPMENT PROJECTS,
 INCLUDING NEW CONSTRUCTION, OR THE RENOVATION OR
 IMPROVEMENT OF AN EXISTING BUILDING, WHERE TOTAL
 CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN
 $500,000 ARE SUBJECT TO THE PUBLIC ART REQUIREMENT.
 OPTION 1: INSTALL ARTWORK ON THE DEVELOPMENT SITE
 VALUED IN AN AMOUNT NOT LESS THAN ONE PERCENT OF THE
 TOTAL CONSTRUCTION COSTS; OR
 OPTION 2: CONTRIBUTE AN AMOUNT EQUAL TO 75 PERCENT OF
 ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS FOR DEPOSIT
 TO THE PUBLIC ART ACCOUNT.
 A COMPLETED PUBLIC ART ASSESSMENT APPLICATION IS
 REQUIRED AT TIME OF BUILDING PERMIT SUBMITTAL.
  
 PLEASE CONTACT SYBILLE WELTER AT [email protected] OR
 561.822.1521 TO OBTAIN AN APPLICATION AND REVIEW THE
 REQUIREMENTS.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By rmcphers Date 2022-09-15 Time 14:44 Rev Time 0.00
Received By rmcphers Date 2022-09-15 Time 14:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-08-10 Cont ID  
Sent By rmcphers Date 2022-08-10 Time 10:31 Rev Time 0.00
Received By rmcphers Date 2022-08-08 Time 16:49 Sent To  
Notes
2022-08-10 10:15:26NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) THE DOOR TO THE TRASH CHUTE ROOM HAS BEEN CHANGED -
 THE TRASH CHUTE ROOM NEEDS TO BE ACCESSIBLE - FBC FHA
 SECTION 5 REQUIREMENT 2 AND REQUIREMENT 3
  
 2) DRAWING A-1 320 DETAIL #2 - WOMENS ROOM TOILET IS
 MISSING.
  
 3) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-30 Cont ID  
Sent By rmcphers Date 2022-03-30 Time 13:01 Rev Time 0.00
Received By rmcphers Date 2022-03-28 Time 15:35 Sent To  
Notes
2022-03-30 12:58:37NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) GARAGE OPENING AREA CALCULATIONS SHOWS 18% FOR THE
 2ND FLOOR - SHOULD BE 20% - FBC 406.5.2 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF
 THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS
 ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 2) DRAWING A2-210 DETAIL 4 AND 5 AND DRAWING A2-211
 DETAIL 2 AND 4 - PLEASE SHOW RESTROOMS AND SERVICE SINK
 ROOM WALL AND FLOOR AND BASEBOARD FINISHES TO COMPLY
 WITH - FBC 1210.2.1 FLOORS AND WALL BASES. - 1210.2.2
 WALLS AND PARTITIONS. (DRYWALL IS NOT CONSIDERED A HARD
 SURFACE)
  
 3) GRAB BAR BACKING DETAILS PROVIDED NEED TO SHOW THE
 BACKING HEIGHT (SHOWER AREA SHOWS BACKING STARTING AT 2
 FEET FROM THE FLOOR BUT DOES NOT SHOW HOW HIGH) - ALL
 DIMENSIONS ARE NEEDED TO SHOW COMPLIANCE - FBC
 ACCESSIBILITY FHA REQUIREMENT 6 - REINFORCED BATHROOM
 WALLS TO ALLOW LATER INSTALLATION OF GRAB BARS AROUND
 THE TOILET, TUB, SHOWER STALL AND SHOWER SEAT, WHERE
 SUCH FACILITIES ARE PROVIDED, WOULD MEET SECTION
 100.205(C)(3)(III) IF REINFORCED AREAS ARE PROVIDED AT
 LEAST AT THOSE POINTS WHERE GRAB BARS WILL BE MOUNTED.
  
 4) PLEASE USE THE WORDS "REFLECTIVE SURFACE" - COMMON
 AREA RESTROOMS - PLEASE SHOW MIRROR DIMENSION FROM THE
 FINISHED FLOOR TO THE BOTTOM OF THE "REFLECTIVE
 SURFACE" - FBC ACCESSIBILITY FHA REQUIREMENT 2 WHERE
 PROVIDED IN PUBLIC-USE AND COMMON-USE FACILITIES, AT
 LEAST ONE OF EACH FIXTURE PROVIDED PER ROOM. (ANSI)
 A117.1-1986 - 4.19.6* MIRRORS. MIRRORS SHALL BE MOUNTED
 WITH THE BOTTOM EDGE OF THE REFLECTING SURFACE NO
 HIGHER THAN 40 IN (1015 MM) FROM THE FLOOR (SEE FIG.
 31).
  
 5) DRAWING A4-301 - TRASH CHUTE DOOR SHOULD BE (1 1/2 )
 HOUR FIRE RATED PER FBC 716.5
  
 6) DRAWING A1-104 AND A0-104 PLEASE SHOW THE FIRE RATED
 SEPARATION - STAIRWELL AND TRASH CHUTE - FBC 713.13.1
 WASTE AND LINEN.
 A SHAFT ENCLOSURE CONTAINING A RECYCLING, OR WASTE OR
 LINEN CHUTE SHALL NOT BE USED FOR ANY OTHER PURPOSE
  
 7) DRAWING A1-103 - PLEASE SHOW THE FIRE RATED TRASH
 CHUTE ROOM DOOR - FBC 713.13.3 CHUTE ACCESS ROOMS.
 ACCESS OPENINGS FOR WASTE OR LINEN CHUTES SHALL BE
 LOCATED IN ROOMS OR COMPARTMENTS ENCLOSED BY NOT LESS
 THAN 1-HOUR FIRE BARRIERS CONSTRUCTED IN ACCORDANCE
 WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED
 IN ACCORDANCE WITH SECTION 711, OR BOTH. OPENINGS INTO
 THE ACCESS ROOMS SHALL BE PROTECTED BY OPENING
 PROTECTIVES HAVING A FIRE PROTECTION RATING OF NOT LESS
 THAN 3/4 HOUR. DOORS SHALL BE SELF- OR
 AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN
 ACCORDANCE WITH SECTION 716.5.9.4.
  
 8) DRAWINGS A0-103, A0-104, A0-105, A0-107 - PLEASE
 SHOW THE HOURLY SHAFT FOR THE TRASH CHUTE FIRE RATING -
 FBC 713.4 FIRE-RESISTANCE RATING.
 SHAFT ENCLOSURES SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 2 HOURS
  
 9) DRAWING A1-303 DETAIL 10 - THE CLEAR FLOOR SPACE FOR
 THE SINK DOES NOT APPEAR TO BE CENTERED ON THE SINK
 BASED ON THE DIMENSIONS SHOWN FOR THE SINK. FBC FHA
 REQUIREMENT 7 (2)
  
 10) DOOR SWINGS INTO THE REQUIRED CLEAR FLOOR SPACE -
 DRAWINGS A1-304 DETAIL 1, DRAWING A1-303 DETAIL 2,
 DRAWING A1-302 DETAIL 3 - FBC FHA REQUIREMENT 7 (2)
  
 11) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD SHALL CONTAIN A STATEMENT THAT,
 TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
 THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
 STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
 ACCORDANCE WITH THIS SECTION AND CHAPTER 633 FLORIDA
 STATUTES.
  
 12) THE FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED:
 ( FOR FLOORS OTHER THAN CARPET )
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 13) FLOORING IIC AND STC REQUIRED TEST REPORTS AND
 ROOFTOP EQUIPMENT SCREENING DETAILS CAN BE ADDED TO THE
 DEFERRED SUBMITTALS LIST - PLEASE LIST ITEMS TO BE
 DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1
 DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-03 Cont ID  
Sent By rmcphers Date 2021-12-03 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2021-11-29 Time 09:17 Sent To  
Notes
2021-12-01 16:59:50NEW RESIDENTIAL HI RISE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE CALCULATIONS FOR THE OPENINGS ON
 THE WEST AND SOUTH EXTERIOR WALLS -
 FBC 705.8 OPENINGS. OPENINGS IN EXTERIOR WALLS SHALL
 COMPLY WITH SECTIONS 705.8.1 THROUGH 705.8.6.
 FBC 705.3 BUILDINGS ON THE SAME LOT.
 FOR THE PURPOSES OF DETERMINING THE REQUIRED WALL AND
 OPENING PROTECTION, PROJECTIONS AND ROOF-COVERING
 REQUIREMENTS, BUILDINGS ON THE SAME LOT SHALL BE
 ASSUMED TO HAVE AN IMAGINARY LINE BETWEEN THEM. WHERE A
 NEW BUILDING IS TO BE ERECTED ON THE SAME LOT AS AN
 EXISTING BUILDING, THE LOCATION OF THE ASSUMED
 IMAGINARY LINE WITH RELATION TO THE EXISTING BUILDING
 SHALL BE SUCH THAT THE EXTERIOR WALL AND OPENING
 PROTECTION OF THE EXISTING BUILDING MEET THE CRITERIA
 AS SET FORTH IN SECTIONS 705.5 AND 705.8.
 705.8 OPENINGS. OPENINGS IN EXTERIOR WALLS SHALL COMPLY
 WITH SECTIONS 705.8.1 THROUGH 705.8.6.
 GARAGE - 406.5.6 FIRE SEPARATION DISTANCE.
 EXTERIOR WALLS AND OPENINGS IN EXTERIOR WALLS SHALL
 COMPLY WITH TABLES 601 AND 602. THE DISTANCE TO AN
 ADJACENT LOT LINE SHALL BE DETERMINED IN ACCORDANCE
 WITH TABLE 602 AND SECTION 705.
  
 2) PLEASE PROVIDE THE OPEN PARKING GARAGE WALL OPENING
 VENTILATION CALCULATIONS -
 406.5.2 OPENINGS.
 FOR NATURAL VENTILATION PURPOSES, THE EXTERIOR SIDE OF
 THE STRUCTURE SHALL HAVE UNIFORMLY DISTRIBUTED OPENINGS
 ON TWO OR MORE SIDES. THE AREA OF SUCH OPENINGS IN
 EXTERIOR WALLS ON A TIER SHALL BE NOT LESS THAN 20
 PERCENT OF THE TOTAL PERIMETER WALL AREA OF EACH TIER.
 THE AGGREGATE LENGTH OF THE OPENINGS CONSIDERED TO BE
 PROVIDING NATURAL VENTILATION SHALL BE NOT LESS THAN 40
 PERCENT OF THE PERIMETER OF THE TIER. INTERIOR WALLS
 SHALL BE NOT LESS THAN 20 PERCENT OPEN WITH UNIFORMLY
 DISTRIBUTED OPENINGS.
  
 3) DRAWING A0-003 SHOWS THE BUILDING DESIGN PER 2017
 FBC - SHOULD BE PER THE CODE IN EFFECT 2020 FBC
  
 4) PLEASE SHOW THE COMPLETE POOL BARRIER PER FBC
 454.1.3.1.9 ( THERE IS NO GATE SHOWN AT STAIR NUMBER 3
 - SHOW THE SURROUNDING PLANTER WALL HEIGHTS ETC..)
  
 5) PLEASE SHOW A STAIR HANDRAIL DETAIL SHOWING THE
 REQUIRED HANDRAIL EXTENSIONS AT TOP AND BOTTOM OF ALL
 STAIRS - FBC 1014.6
  
 6) PLEASE SHOW THE HANDRAILS ON BOTH SIDES OF THE POOL
 ACCESS STAIR FBC 1011.11
  
 7) PLEASE SHOW THE POOL ACCESS TREAD DEPTH AND RISER
 HEIGHT FBC 1011.5.2
  
 8) DRAWING S000 SHOWS WIND DESIGN EXPOSURE "C" -
 BUILDING IN NEAR A LARGE LAKE - PLEASE RE EVALUATE THE
 EXPOSURE USED WHICH MAY BE "D" - FBC 1609.4
  
 9) PLEASE SHOW RESTROOMS AND SERVICE SINK ROOM WALL AND
 FLOOR AND BASEBOARD FINISHES TO COMPLY WITH - FBC
 1210.2.1 FLOORS AND WALL BASES. - 1210.2.2 WALLS AND
 PARTITIONS. (DRYWALL IS NOT CONSIDERED A HARD SURFACE)
  
 10) DRAWING A1- 106 SHOWS A POOL AREA DETAIL ON DRAWING
 A4-113.1 - DRAWING A4-113.1 IS NOT PROVIDED.
  
 11) PLEASE SHOW THE FIRE SERVICE ELEVATORS ( AT LEAST
 2) PER FBC 403.6.1
  
 12) PLEASE SHOW THE FIRE SERVICE ELEVATOR ACCESS LOBBY
 WITH DIMENSIONS OR THE DIMENSIONS AND CORRIDOR WALL
 RATINGS TO MEET THE EXCEPTIONS PER FBC 3007.6
  
 13) PLEASE SHOW AN ELEVATOR THAT MEETS THE REQUIREMENTS
 PER FBC 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE
 STRETCHER
  
 14) PLEASE SHOW THE POOL AREA ACCESSIBLE ACCESS PER FBC
 ACCESSIBILITY FHA - SECTION 5 REQUIREMENT NUMBER 2
  
 15) UNIT C2, C1, C3, C5, C4, C6, FOR BATHROOM SPEC "A"
 PLEASE SHOW THE CLEAR FLOOR SPACE TO BE ABLE TO CLOSE
 THE DOOR FROM INSIDE - FBC ACCESSIBILITY FHA
 REQUIREMENT 7 (2) (A) (I)SUFFICIENT MANEUVERING SPACE
 IS PROVIDED WITHIN THE BATHROOM FOR A PERSON USING A
 WHEELCHAIR OR OTHER MOBILITY AID TO ENTER AND CLOSE THE
 DOOR, USE THE FIXTURES, REOPEN THE DOOR AND EXIT. DOORS
 MAY SWING INTO THE CLEAR FLOOR SPACE PROVIDED AT ANY
 FIXTURE IF THE MANEUVERING SPACE IS PROVIDED.
 MANEUVERING SPACES MAY INCLUDE ANY KNEESPACE OR
 TOESPACE AVAILABLE BELOW BATHROOM FIXTURES.
  
 16) UNIT C3, C1, C5, D1, FOR BATHROOM SPEC "B" PLEASE
 SHOW THE FLOOR SPACE BESIDE THE BATH TUB TO START AT
 THE FOOT OF THE TUB AND CONTINUE ALONG SIDE THE TUB -
 FBC ACCESSIBILITY FHA REQUIREMENT 7 (2) (B) (VI)
 BATHTUBS AND TUB/SHOWERS LOCATED IN THE BATHROOM
 PROVIDE A CLEAR ACCESS AISLE ADJACENT TO THE LAVATORY
 THAT IS AT LEAST 2'6" WIDE AND EXTENDS FOR A LENGTH OF
 4'0" (MEASURED FROM THE FOOT OF THE BATHTUB).
  
 17) UNIT D3 KITCHEN SINK CLEAR FLOOR SPACE SHOWN FOR
 THE SINK RUNS INTO THE CABINET - PLEASE REVISE FOR SINK
 CLEAR FLOOR SPACE - FBC ACCESSIBILITY FHA REQUIREMENT 7
 (1) USABLE KITCHENS. USABLE KITCHENS WOULD MEET SECTION
 100.205(C)(3)(IV) IF: (A) A CLEAR FLOOR SPACE AT LEAST
 30 INCHES BY 48 INCHES THAT ALLOWS A PARALLEL APPROACH
 BY A PERSON IN A WHEELCHAIR IS PROVIDED AT THE RANGE OR
 COOKTOP AND SINK AND EITHER A PARALLEL OR FORWARD
 APPROACH IS PROVIDED AT OVEN, DISH WASHER,
 REFRIGERATOR/FREEZER OR TRASH COMPACTOR.
  
 18) PLEASE SHOW THE LOCATION AND BACKING TYPE DETAIL
 FOR THE REINFORCED WALLS - FBC ACCESSIBILITY FHA
 REQUIREMENT 6 - REINFORCED BATHROOM WALLS TO ALLOW
 LATER INSTALLATION OF GRAB BARS AROUND THE TOILET, TUB,
 SHOWER STALL AND SHOWER SEAT, WHERE SUCH FACILITIES ARE
 PROVIDED, WOULD MEET SECTION 100.205(C)(3)(III) IF
 REINFORCED AREAS ARE PROVIDED AT LEAST AT THOSE POINTS
 WHERE GRAB BARS WILL BE MOUNTED.
  
 19) COMMON AREA RESTROOMS - PLEASE SHOW MIRROR
 DIMENSION FROM THE FINISHED FLOOR TO THE BOTTOM OF THE
 "REFLECTIVE SURFACE" - FBC ACCESSIBILITY FHA
 REQUIREMENT 2 WHERE PROVIDED IN PUBLIC-USE AND
 COMMON-USE FACILITIES, AT LEAST ONE OF EACH FIXTURE
 PROVIDED PER ROOM. (ANSI) A117.1-1986 - 4.19.6*
 MIRRORS. MIRRORS SHALL BE MOUNTED WITH THE BOTTOM EDGE
 OF THE REFLECTING SURFACE NO HIGHER THAN 40 IN (1015
 MM) FROM THE FLOOR (SEE FIG. 31).
  
 20) LIBRARY DOOR (728A) PLEASE SHOW DOOR MANEUVERING
 CLEARANCE - FROM INSIDE THE LIBRARY - FBC ACCESSIBILITY
 FHA REQUIREMENT 2 - (ANSI) A117.1-1986 - 4.13.6
  
 21) COMMON AREA RESTROOMS - PLEASE SHOW THE CLEAR FLOOR
 SPACE TO CLOSE THE DOOR FOR - LEVEL 1 WOMENS RESTROOM,
 LEVEL 7 WOMENS RESTROOM - FBC ACCESSIBILITY FHA
 REQUIREMENT 2 - (ANSI) A117.1-1986 - 4.22.2 DOORS. ALL
 DOORS TO ACCESSIBLE TOILET ROOMS, BATHROOMS, BATHING
 FACILITIES, AND SHOWER ROOMS SHALL COMPLY WITH 4.13.
 DOORS MAY SWING INTO THE CLEAR FLOOR SPACE REQUIRED FOR
 ANY FIXTURE ONLY IN A TOILET OR BATHROOM FOR INDIVIDUAL
 USE THAT PROVIDES SUFFICIENT MANEUVERING SPACE (SEE
 FIG. 3) WITHIN THE ROOM FOR A PERSON USING A WHEELCHAIR
 TO ENTER AND CLOSE THE DOOR, USE THE FIXTURES, REOPEN
 THE DOOR, AND EXIT.
  
 22) DOOR SCHEDULE PROVIDED SHOWS - UNIT A5 ENTRY WITH
 NO FIRE RATING - SHOULD BE FIRE RATED - FBC 716 (PLEASE
 CHECK ALL DOORS ON THE SCHEDULE).
  
 23) CORRIDOR (127) PLEASE SHOW RAMP DETAILS (SLOPE,
 REQUIRED HANDRAILS ETC.) FBC ACCESSIBILITY FHA
 REQUIREMENT 2 - 4.3.7 SLOPE. AN ACCESSIBLE ROUTE WITH A
 RUNNING SLOPE GREATER THAN I:20 IS A RAMP AND SHALL
 COMPLY WITH 4.8. NOWHERE SHALL THE CROSS SLOPE OF AN
 ACCESSIBLE ROUTE EXCEED 1:50.
  
 24) PLEASE LABEL ELEVATOR NUMBER 6 ON THE FLOOR PLAN.
  
 25) WALLS THAT REQUIRE SOUND RATINGS - PLEASE SHOW THE
 INSULATION THICKNESS AND TYPE TO MEET THE STC 50 SOUND
 RATING - FBC 1207.2 AIRBORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH
 OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT
 LESS THAN 45 IF FIELD TESTED, FOR AIRBORNE NOISE WHEN
 TESTED IN ACCORDANCE WITH ASTM E90. ALTERNATIVELY, THE
 SOUND TRANSMISSION CLASS OF WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SHALL BE ESTABLISHED BY
 ENGINEERING ANALYSIS BASED ON A COMPARISON OF WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES HAVING SOUND
 TRANSMISSION CLASS RATINGS AS DETERMINED BY THE TEST
 PROCEDURES SET FORTH IN ASTM E90.
  
 26) FLOORS - PLEASE SHOW THE FLOORING FINISHES - THE
 FOLLOWING ACUSTICAL TEST REPORTS ARE REQUIRED: ( FOR
 FLOORS OTHER THAN CARPET )
  
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90..
 PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING
 SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY
 DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP
 CEILING DESCRIPTION)
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP
 CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING
 ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED
 DROP CEILING DESCRIPTION)
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS
 ATTACHED TO THE FLOORING)
  
 26) PLEASE PROVIDE THE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR
 DOORS, EXTERIOR LOUVERS, ROOFING SYSTEMS ETC. ALL
 PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED
 APPROVED BY THE BUILDING DESIGNER OF RECORD FBC WPB
 107.3.4
  
 27) ITEMS SUCH AS ROOFING SYSTEMS, WINDOW AND DOOR
 PRODUCT APPROVALS ETC. MAY BE DEFERRED SUBMITTALS BY
 LISTING ITEMS TO BE DEFERRED ON THE CONSTRUCTION
 DOCUMENTS - FBC WPB 107.3.4.1 DEFERRED SUBMITTALS. FOR
 THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS ARE
 DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE NOT
 SUBMITTED AT THE TIME OF THE APPLICATION AND THAT ARE
 TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A
 SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL
 HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE
 REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION
 DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL.
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2022-08-06 Cont ID  
Sent By jleahy Date 2022-08-06 Time 16:59 Rev Time 0.00
Received By jleahy Date 2022-08-05 Time 16:19 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-04-14 Cont ID  
Sent By jleahy Date 2022-04-14 Time 13:39 Rev Time 0.00
Received By jleahy Date 2022-04-13 Time 16:52 Sent To  
Notes
2022-04-14 13:40:20FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 BACK UP GENERATOR TO COMPLY WITH 700.3(F)

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2021-11-24 Cont ID  
Sent By jleahy Date 2021-11-24 Time 08:02 Rev Time 0.00
Received By jleahy Date 2021-11-24 Time 08:02 Sent To  
Notes
2021-11-24 08:15:14ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER SHOWS NO GROUNDING ELECTRODE SYSTEM TO MAINS 2 OF
 3 AND 3 OF 3. 250.66
  
 NO FAUL CURRENT CALCULATION FOR THE SERVICE 110.9,
 110.10
  
 NO LOAD CALCULATION SHOW FOR THE SERVICE 215.5
  
 UNITS AE, B7, D3 UNITS MISSING OUTLETS ON BALCONIES
 210.52 (E)(3)
  
 THE FOLLOWING REQUIRE SEPARATE PERMITS
  
 FIRE ALARAM
 GENERATOR
 POOL
 LOW VOLTAGE WIRING TELEPHONE DATA
 BDA SYSTEM
 LIGHTNING PROTECTION
 ACCESS CONTROL
 CCTV
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2021-11-16 Time   Rev Time 0.00
Received By jleahy Date 2021-11-16 Time 12:52 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 6 Status P Date 2022-09-20 Cont ID  
Sent By rrossano Date 2022-09-20 Time   Rev Time 0.00
Received By rrossano Date 2022-09-20 Time   Sent To I
Notes
2022-09-19 14:14:55OLD PAGES NEED TO BE DELETED
  

Review Stop ENG ENGINEERING CSD
Rev No 5 Status P Date 2022-09-19 Cont ID  
Sent By rrossano Date 2022-09-19 Time   Rev Time 0.00
Received By rrossano Date 2022-09-19 Time   Sent To  
Notes
2022-09-19 10:08:53PASSED WITH PROVISO: FINAL APPROVED ENGINEERING PLANS
 WILL BE REQUIRED TO BE UPLOADED FOR BUILDING PERMIT.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, ENGINEERING
 SERVICES AT 561-494-1098 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2022-08-12 Cont ID  
Sent By rrossano Date 2022-08-12 Time   Rev Time 0.00
Received By rrossano Date 2022-08-12 Time   Sent To  
Notes
2022-08-12 10:00:04PASSED WITH PROVISO: FINAL APPROVED ENGINEERING PLANS
 WILL BE REQUIRED TO BE UPLOADED FOR BUILDING PERMIT.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, ENGINEERING
 SERVICES AT 561-494-1098 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2022-07-25 Cont ID  
Sent By rrossnao Date 2022-07-25 Time   Rev Time 0.00
Received By rrossano Date 2022-07-25 Time   Sent To  
Notes
2022-07-25 16:33:35PASSED WITH PROVISO: FINAL APPROVED ENGINEERING PLANS
 WILL BE REQUIRED TO BE UPLOADED FOR BUILDING PERMIT.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR, ENGINEERING
 SERVICES AT 561-494-1098 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2022-03-14 Cont ID  
Sent By rrossano Date 2022-03-14 Time   Rev Time 0.00
Received By rrossano Date 2022-03-14 Time   Sent To  
Notes
2022-03-14 12:05:41UNDER FORMAL ENGINEERING SUBMITTTAL REVIEW E20100038

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-11-08 Cont ID  
Sent By rrossano Date 2021-11-08 Time   Rev Time  
Received By rrossano Date 2021-11-08 Time   Sent To  
Notes
2021-11-08 11:31:53PLEASE ADVISE STATUS OF FORMAL ENGINEERING SUBMITTAL.
  
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-03-14 Cont ID  
Sent By cwalker Date 2022-03-14 Time   Rev Time 0.00
Received By cwalker Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-11-23 Cont ID  
Sent By pleduc Date 2021-11-23 Time   Rev Time 0.00
Received By pleduc Date 2021-11-03 Time 09:43 Sent To  
Notes
2021-11-23 11:29:18THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) SHEET LS AO 101 - EXIT STAIR # 1 DISCHARGERS INTO A
 SMALL CORRIDOR OFF OF THE MAIN LOBBY AREA THAT MAY NOT
 COMPLY WITH THE CODE
  
 PER NFPA 101, MEANS OF EGRESS.
  
 7.2.3.5 DISCHARGE.
 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE
 INTO A PUBLIC WAY,
 INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC
 WAY, OR INTO AN EXIT
 PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT
 OPENINGS, OTHER
 THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE
 DOOR OPENING TO
 THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT
 PASSAGEWAY SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY A
 2-HOUR FIRE RESISTANCE
 RATING.
 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED
 TO DISCHARGE
 THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF
 THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
 (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL
 LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY
 SHALL BE
 READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF
 DISCHARGE FROM
 THE SMOKEPROOF ENCLOSURE.
 (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND
 CAPACITY OF
 EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL
 DISCHARGE THROUGH
 INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2.
  
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS COMPLYING
 WITH THE CODE OF CORRECT.
  
  
  
  
 2) SHEET LS AO 102 - EXIT STAIR # 2 EXITS INTO AN
 ELEVATOR LOBBY.
  
 7.2.3.5 DISCHARGE.
 7.2.3.5.1 EVERY SMOKEPROOF ENCLOSURE SHALL DISCHARGE
 INTO A PUBLIC WAY,
 INTO A YARD OR COURT HAVING DIRECT ACCESS TO A PUBLIC
 WAY, OR INTO AN EXIT
 PASSAGEWAY. SUCH EXIT PASSAGEWAYS SHALL BE WITHOUT
 OPENINGS, OTHER
 THAN THE ENTRANCE TO THE SMOKEPROOF ENCLOSURE AND THE
 DOOR OPENING TO
 THE OUTSIDE YARD, COURT, OR PUBLIC WAY. THE EXIT
 PASSAGEWAY SHALL BE
 SEPARATED FROM THE REMAINDER OF THE BUILDING BY A
 2-HOUR FIRE RESISTANCE
 RATING.
 7.2.3.5.2 THE SMOKEPROOF ENCLOSURE SHALL BE PERMITTED
 TO DISCHARGE
 THROUGH INTERIOR BUILDING AREAS, PROVIDED THAT ALL OF
 THE FOLLOWING CRITERIA
 ARE MET:
 (1) THE BUILDING SHALL BE PROTECTED THROUGHOUT BY AN
 APPROVED, SUPERVISED
 AUTOMATIC SPRINKLER SYSTEM IN ACCORDANCE WITH SECTION
 9.7.
 (2) THE DISCHARGE FROM THE SMOKEPROOF ENCLOSURE SHALL
 LEAD TO A FREE
 AND UNOBSTRUCTED WAY TO AN EXTERIOR EXIT, AND SUCH WAY
 SHALL BE
 READILY VISIBLE AND IDENTIFIABLE FROM THE POINT OF
 DISCHARGE FROM
 THE SMOKEPROOF ENCLOSURE.
 (3) NOT MORE THAN 50 PERCENT OF THE REQUIRED NUMBER AND
 CAPACITY OF
 EXITS COMPRISED OF SMOKEPROOF ENCLOSURES SHALL
 DISCHARGE THROUGH
 INTERIOR BUILDING AREAS IN ACCORDANCE WITH 7.7.2.
  
  
  
 2A) SHEET LS AO102 - THE EVEVATOR LOBBY DOORS OF # 2
 ABOVE SWING INTO THE LOBBY AND AGAINST THE PATH OF
 TRAVEL.
  
 7.2.1.4.2* DOOR LEAF SWING DIRECTION. DOOR LEAVES
 REQUIRED TO BE OF
 THE SIDE-HINGED OR PIVOTED-SWINGING TYPE SHALL SWING IN
 THE DIRECTION
 OF EGRESS TRAVEL UNDER ANY OF THE FOLLOWING CONDITIONS:
 (1) WHERE SERVING A ROOM OR AREA WITH AN OCCUPANT LOAD
 OF 50 OR MORE,
 EXCEPT UNDER ANY OF THE FOLLOWING CONDITIONS:
 (A) DOOR LEAVES IN HORIZONTAL EXITS SHALL NOT BE
 REQUIRED TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL WHERE PERMITTED BY
 7.2.4.3.8.1
 OR 7.2.4.3.8.2.
 (B) DOOR LEAVES IN SMOKE BARRIERS SHALL NOT BE REQUIRED
 TO SWING
 IN THE DIRECTION OF EGRESS TRAVEL IN EXISTING HEALTH
 CARE OCCUPANCIES,
 AS PROVIDED IN CHAPTER 19.
 (2) WHERE THE DOOR ASSEMBLY IS USED IN AN EXIT
 ENCLOSURE, UNLESS THE
 DOOR OPENING SERVES AN INDIVIDUAL LIVING UNIT THAT
 OPENS DIRECTLY
 INTO AN EXIT ENCLOSURE
 (3) WHERE THE DOOR OPENING SERVES A HIGH-HAZARD
 CONTENTS AREA
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 3) SHEET LS AO106 - THERE APPEARS TO BE A DOUBLE DOOR
 GATE FROM THE POOL AREA THAT OPEN UP OBSTRUCTING THE
 EXIT TRAVEL PATH.
  
 PER NFPA 101 CHAPTER 7, MEANS OF EGRESS
 7.2.1.4.3 DOOR LEAF ENCROACHMENT
 7.2.1.4.3.1 DURING ITS SWING, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED WIDTH OF
 AN AISLE, A CORRIDOR,
 A PASSAGEWAY, OR A LANDING UNOBSTRUCTED, UNLESS BOTH OF
 THE FOLLOWING
 CONDITIONS ARE MET:
 (1) THE DOOR OPENING PROVIDES ACCESS TO A STAIR IN AN
 EXISTING
 BUILDING.
 (2) THE DOOR OPENING MEETS THE REQUIREMENT OF
 7.2.1.4.3.2.
 7.2.1.4.3.2 WHEN FULLY OPEN, ANY DOOR LEAF IN A MEANS
 OF EGRESS SHALL
 NOT PROJECT MORE THAN 7 IN. (180 MM) INTO THE REQUIRED
 WIDTH OF AN AISLE,
 A CORRIDOR, A PASSAGEWAY, OR A LANDING, UNLESS THE DOOR
 LEAF IS EQUIPPED
 WITH AN APPROVED SELF-CLOSING DEVICE AND IS NOT
 REQUIRED BY THE PROVISIONS
 OF 7.2.1.4.2 TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH A DETAILED
 NARRATIVE AND CODE REFERENCES
  
  
  
  
 4) SHEET A1 101 - THE FIRE COMMAND ROOM INDICATES A MIN
 WALL DIMENSION OF 10' 31/2"; HOWEVER, THAT IS FROM
 CENTER WALL TO CENTER WALL.
  
 PER NFPA 1
  
 11.9.3 THE EMERGENCY COMMAND CENTER ROOM SHALL BE A
 MINIMUM OF 200 FT2 (19 M2) WITH A MINIMUM DIMENSION OF
 10 FT (3050 MM).
  
 PLEASE CONFIRM/VERIFY THAT IN CLEAR ROOM WIDTH
 DIMENSION MEETS THE MINUMUM CODE.
  
  
  
 5) SHEET FP 109 - THERE ARE TWO ROOMS ON THE ROOF
 INDICATED AS ELEC 2301 & MECH 2301 THAT DO NOT AAPPEAR
 TO HAVE FIRE SPRINKLER PROTECTION.
  
 PER NFPA 1 & 101 THE BUILDING IS TO BE EQUIPPED WITH
 FIRE SPRINKLER PROTECTION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH SPECIFIC CODE
 REFERENCES AND NARRATIVE OR PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT TO PROVIDE ON SHOP DRAWINGS.
  
  
  
 6) SHEET FP 402 - THERE ARE NO INDICATIONS OF PRV
 WITHIN THE STAIRWELLS AT THE FDV'S WERE APPLICABLE.
  
 PER NFPA 14
  
 7.2.3* MAXIMUM PRESSURE AT HOSE CONNECTIONS.
 7.2.3.1 WHERE THE RESIDUAL PRESSURE AT A 11?2 IN. (40
 MM) OUTLET
 ON A HOSE CONNECTION AVAILABLE FOR TRAINED PERSONNEL
 USE
 EXCEEDS 100 PSI (6.9 BAR), AN APPROVED
 PRESSURE-REGULATING
 DEVICE SHALL BE PROVIDED TO LIMIT THE RESIDUAL PRESSURE
 AT THE
 FLOW REQUIRED BY SECTION 7.10 TO 100 PSI (6.9 BAR).
 7.2.3.1.1 PARAGRAPH 7.2.3.1 SHALL NOT APPLY TO THE 11?2
 IN.
 (40 MM) OUTLET ON A 21?2 IN. ? 11?2 IN. (65MM? 40 MM)
 REDUCER
 AS ALLOWED BY 5.3.3.2 AND 7.3.4.1.
 7.2.3.2* WHERE THE STATIC PRESSURE AT A 21?2 IN. (65
 MM) HOSE
 CONNECTION EXCEEDS 175 PSI (12.1 BAR), AN APPROVED
 PRESSUREREGULATING
 DEVICE SHALL BE PROVIDED TO LIMIT STATIC AND RESIDUAL
 PRESSURES AT THE OUTLET OF THE HOSE CONNECTION TO 175
 PSI
 (12.1 BAR).
 7.2.3.3 THE PRESSURE ON THE INLET SIDE OF THE
 PRESSUREREGULATING
 DEVICE SHALL NOT EXCEED THE RATED WORKING PRESSURE
 OF THE DEVICE.
  
 PLEASE REVIEW AND CORRECT OR PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT TO PROVIDE ON SHOP DRAWINGS.
  
  
  
 7) SHEET FP 401 - THERE APPEARS TO BE AN INDICATION OF
 AN ELECTRIC FIRE PUMP.
  
 AN ELECTRICAL FIRE PUMP IS REQUIRED TO BE PROVIDED WITH
 A RELIABLE BACKUP POWER SOURCE.
  
 PER NFPA 70
  
 695.3 POWER SOURCE(S) FOR ELECTRIC MOTOR-DRIVEN FIRE
 PUMPS. ELECTRIC MOTOR-DRIVEN FIRE PUMPS SHALL HAVE A
 RELIABLE
 SOURCE OF POWER.
  
 (B) MULTIPLE SOURCES. IF RELIABLE POWER CANNOT BE
 OBTAINED
 FROM A SOURCE DESCRIBED IN 695.3(A), POWER SHALL BE
 SUPPLIED BY ONE OF THE FOLLOWING: [20:9.3.2]
 (1) INDIVIDUAL SOURCES. AN APPROVED COMBINATION OF TWO
 OR MORE OF THE SOURCES FROM 695.3(A).
 (2) INDIVIDUAL SOURCE AND ON-SITE STANDBY GENERATOR.
 AN APPROVED COMBINATION OF ONE OR MORE OF THE SOURCES
 IN
 695.3(A) AND AN ON-SITE STANDBY GENERATOR COMPLYING
 WITH
 695.3(D). [20:9.3.4]
  
 PLEASE REVIEW AND CORRECT OR PROVIDE AN APPLICABLE NOTE
 OF ACKNOWLEDGEMENT TO CONNECT TO THE ON-SITE GENERATOR
 PROPOSED.
  
  
 8) SHEET C 08 - ALL FIRE LINE LINE UNDERGROUND
 (INCLUDING, FDC, DDCV AND PRIVATE FIRE HYDRANTS) SHALL
 BE SUBMITTED UNDER SEPARATE PERMIT & SHOP DRAWINGS,
 INSTALLED BY A FLORIDA CERTIFIED UNDERGROUND CONTRACTOR
 AND INSPECTED PER NFPA 24
  
 PLEASE REVIEW AND ENSURE COMPLIANCE AND PROVIDE AN
 APPLICABLE NOTE OF ACKNOWLEDGEMENT.
  
  
  
 9) THERE IS NO INDICATION OF THE SMOKE CONTROL RATIONAL
 ANALYSIS.
  
 PLEASE PROVIDE SMOKE CONTROL DETAILS.
  
  
  
 10) SHEET ELECTICAL - THERE IS NO INDICATION TO PROVIDE
 FOR EMERGENCY RADIO COMMUNICATIONS.
  
 NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY
 RADIO ENHANCEMENT SERVICES.
 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM
 RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT
 COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL
 DETERMINED BY THE AHJ.
 NFPA 72, 24.9 TWO-WAY RADIO COMMUNICATIONS ENHANCEMENT
 SYSTEMS.
 24.9.1 GENERAL.
 24.9.1.1 NON-INTERFERENCE. NO AMPLIFICATION SYSTEM
 CAPABLE
 OF OPERATING ON FREQUENCIES OR CAUSING INTERFERENCE ON
 FREQUENCIES
 ASSIGNED TO THE JURISDICTION BY THE FCC SHALL BE
 INSTALLED
 WITHOUT PRIOR COORDINATION AND APPROVAL OF THE
 AUTHORITY
 HAVING JURISDICTION. THE BUILDING MANAGER/OWNER SHALL
 SUSPEND AND CORRECT OTHER EQUIPMENT INSTALLATIONS THAT
 DEGRADE
 THE PERFORMANCE OF THE PUBLIC SAFETY RADIO SYSTEM OR
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM.
 24.9.1.2 APPROVAL AND PERMIT. PLANS SHALL BE SUBMITTED
 FOR
 APPROVAL PRIOR TO INSTALLATION. AT THE CONCLUSION OF
 SUCCESSFUL
 ACCEPTANCE TESTING, A RENEWABLE PERMIT SHALL BE ISSUED
 FOR THE
 PUBLIC SAFETY RADIO ENHANCEMENT SYSTEM WHERE REQUIRED
 BY
 THE AUTHORITY HAVING JURISDICTION.
  
 THE SYSTEM SHALL MAINTAIN A MINIMUM RADIO SIGNAL
 STRENGTH OF -95 DBM FOR THE RADIO SYSTEM USED BY WEST
 PALM BEACH FIRE DEPARTMENT. TESTING SHALL BE BY AN
 ACCEPTABLE NATIONAL STANDARD DOCUMENTING PERCENTAGES
 NOTED ABOVE AND BY ACTUAL RADIO TESTING BY FIRE
 PERSONNEL. IF THE MINIMUM CANNOT BE MAINTAINED, A
 BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH
 A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP.
 PLEASE CONTACT MARK FILLA, PALM BEACH COUNTY PUBLIC
 SAFETY RADIO SYSTEMS MANAGER, [email protected],
 561-233-0837; AS OUR RADIOS OPERATE ON THEIR SYSTEM FOR
 DETAILED RADIO FREQUENCY AND INSTALLATION INSTRUCTIONS.
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 ACKNOWLEDGMENT.
  
  
  
 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By ccole Date 2022-09-15 Time 17:26 Rev Time 0.00
Received By ccole Date 2022-09-15 Time 15:55 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-07-28 Cont ID  
Sent By ccole Date 2022-07-28 Time 17:11 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 13:55 Sent To  
Notes
2022-07-28 17:16:193RD REVIEW FBC-2020 FUEL GAS
 PERMIT- 21091343
 7/28/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 1) P105 & P402: BASED ON THE COMMENT RESPONSES FROM THE
 ENGINEER THE MANUFACTURER?S SPECIFICATIONS FOR THE BBQ
 GRILLS AND THE ENGINEERING FOR INSTALLATION ARE TO BE
 DEFERRED SUBMITTALS, PLEASE PROVIDE A LIST OF DEFFERRED
 SUBMITTALS ON THE PLANS THAT INCLUDES THE BBQ GRILLS,
 THE GRILL ENGINEERING, AND THE REGULATORS- SEC.
 107.3.4.1 WPB.
  
 2) P104 & P402: PLEASE PROVIDE NOTES ON THE PLAN TO
 INDICATE THE POOL HEATER AND COMBUSTION AND VENTING
 PLANS WILL BE UNDER A SEPARATE PERMIT- SECS. 107.2.1 7
 107.3.4.2 WPB.
  
 3) NEW COMMENT BASED ON RESUBMITTED P402: PLEASE SHOW
 THE REQUIRED PIPE UNIONS LOCATED WITH 1 FT. OF EITHER
 SIDE OF THE REGULATOR- SEC. 410.2(7) FBC FG.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-04-05 Cont ID  
Sent By ccole Date 2022-04-05 Time 11:17 Rev Time 0.00
Received By ccole Date 2022-03-31 Time 17:50 Sent To  
Notes
2022-04-05 11:18:052ND REVIEW FBC-2020 FUEL GAS
 PERMIT- 21091343
 4/5/22
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 2) FAILED. P102- P104: SHOW GAS PIPING HORIZONTAL RUNS
 AND RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS.
 401.1 & 402.1 FBC FG. PIPE SIZES SHOWN AT THE NEW RISER
 ON P402 DO NOT MATCH SIZES SHOWN ON THE PLANS- PLEASE
 CORRECT.
  
 3) FAILED. P104, P105, & P402: THE PLANS SHOW BRANCH
 PIPING CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE
 AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO
 INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE
 APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG.
 PIPE SIZES SHOWN AT THE NEW RISER ON P402 DO NOT MATCH
 SIZES SHOWN ON THE PLANS- PLEASE CORRECT.
  
 7) FAILED. P402: PROVIDE EQUIPMENT SCHEDULES FOR THE
 POOL HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS- SECTION 305.1 FBC FG. ACKNOWLEDGED THAT THE
 POOL HEATERS SPECS WILL BE SUBMITTED UNDER A SEPARATE
 GAS PERMIT HOWEVER THE REQUESTED BBQ SPECS AND INSTALL
 MANUALS WERE NOT PROVIDED. PLEASE PROVIDE THE SPECS AND
 WIND LOAD ANCHORING DETAILS FOR THE APPLIANCES- SECS.
 301.10 & 623.1 FBC FG.
  
 8) FAILED. P402: PROVIDE COMBUSTION AIR CALCULATIONS
 FOR THE POOL HEATERS AND INDICATE HOW THE AIR WILL BE
 PROVIDED- SEC. 304.1 FBC FG. THE NARRATIVE RESPONSE
 INDICATES PLAN SHEET M104, HOWEVER COMBUSTION CALCS ARE
 NOT PROVIDED ON THE PLAN.
  
 9) FAILED. P402: PROVIDE POOL HEATER GAS VENTING PLANS
 INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT
 PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS.
 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION
 CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS-
 503.8. THE NARRATIVE RESPONSE INDICATES PLAN SHEET
 M104, HOWEVER VENTING DETAILS ARE NOT PROVIDED ON THE
 PLAN.
  
 NEW COMMENT:
  
 1) SHEET P402: PROVIDE ELECTRICAL BONDING DETAILS- SEC.
 310.1 FBC FG. PIPING LIKELY TO BECOME ENERGIZED SHALL
 BE ELECTRICALLY CONTINUOUS AND BONDED TO AN EFFECTIVE
 GROUND-FAULT CURRENT PATH.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By ccole Date 2021-12-15 Time 11:52 Rev Time 0.00
Received By ccole Date 2021-12-10 Time 15:07 Sent To  
Notes
2021-12-15 11:53:381ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 21091343
 12/15/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS C-08 & P101: SHOW THE GAS PIPING RUNS FROM
 THE MAIN LINE ONSITE TO THE METER AT THE BUILDING, AND
 FROM THE METER THROUGH THE BUILDING TO THE RISER
 LOCATION- SEC. 107.2.1 WPB, AND SECS. 401.1 & 402.1 FBC
 FG.
  
 2) P102- P104: SHOW GAS PIPING HORIZONTAL RUNS AND
 RISER LOCATIONS- - SEC. 107.2.1 WPB, AND SECS. 401.1 &
 402.1 FBC FG.
  
 3) P104, P105, & P402: THE PLANS SHOW BRANCH PIPING
 CONTINUATIONS TO APPLIANCES (BBQ GRILLS?) ON THE
 AMENITIES DECK. PLEASE REVISE THE RISER DRAWING TO
 INCLUDE THE PIPING AND APPLIANCE LOADS AND IDENTIFY THE
 APPLIANCES ON THE PLAN VIEW- SEC. 402.1 & 402.2 FBC FG.
  
 4) P104 & P402: THE PLAN SHOWS ONE POOL HEATER, THE ISO
 SHOWS TWO- PLEASE CORRECT.
  
 5) P402: PROVIDE THE MAKE AND MODEL OF THE REGULATORS
 AND INDICATE THE OUTPUT PRESSURES- SEC. 410.2 FBC FG.
 A) PLEASE SHOW THE REQUIRED TEST TEE FITTINGS UPSTREAM
 AND DOWNSTREAM OF THE REGULATORS, AND THE REQUIRED PIPE
 UNIONS WITHIN 1 FT. OF EITHER SIDE OF THE REGULATOR-
 SEC.410.2 (ITEMS 6 & 7).
  
 6) P402: PROVIDE VENTING DETAILS FOR THE REGULATORS IF
 THE REGULATORS ARE NOT EQUIPPED WITH APPROVED
 VENT-LIMITING DEVICES- SEC. 410.2 FBC FG.
  
 7) P402: PROVIDE EQUIPMENT SCHEDULES FOR THE POOL
 HEATERS AND THE AMENITY APPLIANCES ON THE PLAN AND
 SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 MANUALS- SECTION 305.1 FBC FG.
  
 8) P402: PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 POOL HEATERS AND INDICATE HOW THE AIR WILL BE PROVIDED-
 SEC. 304.1 FBC FG.
  
 9) P402: PROVIDE POOL HEATER GAS VENTING PLANS
 INCLUDING A DIAGRAM SHOWING THE TYPE AND SIZE OF VENT
 PIPING, THE VENT RUN AND TERMINATION LOCATION- SECS.
 305.1, 503.1 FBC FG. PLEASE INCLUDE VENT TERMINATION
 CLEARANCES AND SUBMIT SPECS FOR THE VENT MATERIALS-
 503.8.
  
 10) P104: A VESTIBULE IS REQUIRED FOR THE POOL
 EQUIPMENT ROOM 602 BASED ON SECTION 305.3.2 FBC FG.
 CONNECTION OF A PARKING GARAGE WITH ANY ROOM IN WHICH
 THERE IS A FUEL-FIRED APPLIANCE SHALL BE BY MEANS OF A
 VESTIBULE PROVIDING A TWO-DOORWAY SEPARATION, EXCEPT
 THAT A SINGLE DOOR IS PERMITTED WHERE THE SOURCES OF
 IGNITION IN THE APPLIANCE ARE ELEVATED IN ACCORDANCE
 WITH SECTION 305.3.2.
 11) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 BOTH THE POOL AND THE POOL HEATER- SECTION 105.1 &
 107.2.1 WPB.
  
 12) PLEASE NOTE THE REQUESTED SPECIFICATIONS FOR THE
 POOL HEATERS, AMENITY APPLIANCES, VENT PIPING,
 REGULATORS MAY BE DEFERRED IN ACCORDANCE WITH SEC.
 107.3.4.1 WPB. PLEASE PROVIDE A LITS OF DEFERRED
 SUBMITTALS IF APPLICABLE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-09-20 Cont ID  
Sent By lmarchan Date 2022-09-20 Time 11:18 Rev Time 0.00
Received By lmarchan Date 2022-09-20 Time 08:34 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-19 Cont ID  
Sent By shill Date 2022-09-19 Time 14:14 Rev Time 0.00
Received By shill Date 2022-08-29 Time 06:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-23 Cont ID  
Sent By aoliver Date 2022-08-23 Time 11:49 Rev Time 0.00
Received By aoliver Date 2022-07-19 Time 16:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-21 Cont ID  
Sent By aoliver Date 2022-04-21 Time 07:38 Rev Time 0.00
Received By aoliver Date 2022-03-10 Time 08:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-22 Cont ID  
Sent By lmarchan Date 2021-12-22 Time 11:24 Rev Time 0.00
Received By lmarchan Date 2021-10-22 Time 09:29 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-09-14 Cont ID  
Sent By lmarchan Date 2022-09-14 Time 13:45 Rev Time 0.00
Received By lmarchan Date 2022-07-29 Time 14:47 Sent To  
Notes
2022-09-14 10:01:33RECEIPT - 2022-041653 - $2,957,298.09 PAID
2022-07-29 14:48:067/29/22 EMAILED IMPACT OFFICE TO REVIEW - OK TO SEND
 PER SHILL. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-03 Cont ID  
Sent By rmcphers Date 2021-12-03 Time 09:52 Rev Time 0.00
Received By rmcphers Date 2021-12-03 Time 09:52 Sent To  
Notes
2021-12-03 09:53:36PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF
  
 UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE
 RECEIPT TO YOUR PROJECT OR EMAIL IT TO
 [email protected] .
  

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 08:58 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 08:58 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2022-09-08 Cont ID  
Sent By medwards Date 2022-09-08 Time 09:01 Rev Time 0.00
Received By medwards Date 2022-09-08 Time 09:01 Sent To  
Notes
2022-09-08 09:04:364TH REVIEW FMC
 PERMIT: 21091343
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) NARRATIVES SUBMITTED STATES M-203- PROVIDE FIRE
 DAMPER FOR AHU-1L-2 OUTSIDE AIR DUCT PENETRATION, THIS
 IS NOT ON THIS SHEET, THIS IS LOCATED ON M205. ALSO,
 THE NARRATIVE STATES THAT THE SPF-1A HAS BEEN RELOCATED
 TO THE 6TH LEVEL, PLEASE SUBMIT THIS DRAWING SHOWING
 THE CHANGE. FBC 107.3.5
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-07-29 Cont ID  
Sent By medwards Date 2022-07-29 Time 08:54 Rev Time 0.00
Received By medwards Date 2022-07-29 Time 08:54 Sent To  
Notes
2022-07-29 08:54:333RD REVIEW FMC
 PERMIT: 21091343
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 THERE SEEMS TO BE SEVERAL CHANGES THROUGHOUT THE
 REVISED DRAWINGS WITH NO MENTION OF THESE CHANGES IN A
 NARRATIVE. PLEASE SUBMIT A NARRATIVE FOR THESE CHANGES.
 BELOW IS A PARTIAL LIST OF COMMENTS TO THESE CHANGES. I
 CANNOT DO A COMPLETE REVIEW WITHOUT THE NARRATIVE FOR
 THE CHANGES. FBC 107.2.1
  
 1) SHEET M-2.03: THE 48 INCH X 26 INCH FLAME-BAR DUCT
 AND SPF-1A HAS BEEN REMOVED IN THIS CYCLE OF REVIEWS,
 PLEASE EXPLAIN. FBC 107.2.1
  
 2) SHEET M-3.04: THE 100 PERCENT O/A ROOF TOP UNIT
 SCHEDULE IS MISSING FROM THIS LATEST SUBMITTAL. PLEASE
 EXPLAIN. FBC 107.2.1
  
 3) SHEET M-4.00: THE SMOKE CONTROL RISER DIAGRAM HAS
 BEEN OMITTED FROM THIS LATEST SUBMITTAL. PLEASE
 EXPLAIN. FBC 107.2.1
  
 4) SHEET M-402: EXPLAIN WHY THE SMOKE CONTROL DESIGN
 HAS CHANGED. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By medwards Date 2022-03-31 Time 15:44 Rev Time 0.00
Received By medwards Date 2022-03-31 Time 15:44 Sent To  
Notes
2022-03-31 15:44:522ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091343
  
 CODES IN EFFECT:
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.01: THE EQUIPMENT LABELS HAVE BEEN REMOVED
 ON THIS CYCLE, PLEASE PUT THEM BACK ON THE DRAWING AND
 CHECK THE OTHER SHEETS. FBC 107.2.1
  
 2) THE NO2 AND CO SENSORS HAVE BEEN REMOVED FROM THIS
 CYCLE, PLEASE PUT THEM BACK ON THE DRAWING. PROVIDE THE
 CALCULATIONS FOR THE FIRST LEVEL PARKING GARAGE
 VENTILATION SYSTEM. FMC 404.1
  
 3) SHEET M1.01: IT APPEARS THAT THE OUTDOOR AIR DUCT
 THAT IS NOW SHOWN FOR AHU-1L-6 IS CONNECTING TO THE
 SUPPLY SIDE OF THE UNIT. AND THERE IS NOW A DAMPER
 SHOWN ON THE RETURN SIDE OF THE UNIT. PLEASE PROVIDE A
 DETAIL DRAWING EXPLAINING WHY THE DUCT IS CONNECTING TO
 THE SUPPLY AND THE NEED FOR THE DAMPER IN THE RETURN AT
 THE AHU-1L-6. FBC 107.2.1
  
 4) SHEET M1.01: PLEASE IDENTIFY THE INTAKE LOUVER FOR
 THE GENERATOR ROOM. FBC 107.2.1
  
 5) PLEASE SHOW THE REQUIRED PROTECTION FOR THE 3-HOUR
 RATED WALLS WHERE THE ELEC. ROOM AND GENERATOR ROOM
 EXHAUST PENETRATES THE WALLS. FMC 607
  
 6) PLEASE CLEARLY IDENTIFY THE FIRE DAMPERS AT THE
 REQUIRED LOCATIONS. FBC 107.2.1
  
 7) PROVIDE DRYER DUCT LENGTHS FOR EACH UNIT AND SHOWING
 EACH WILL MEET FMC 504.8.4.1 35 FOOT MAX. LENGTH OR
 PROVIDE THE MANUFACTURER?S INSTRUCTIONS FOR THE
 SPECIFIC DRYER USED IN EACH UNIT. FMC 504.8.4.2
  
 8) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR THIS
 BUILDING ACCORDING TO FMC TABLE 403.3.1.1 AND NOT THE
 ARCHITECTURAL EGRESS OCCUPANT LOAD. PLEASE IDENTIFY
 EACH SPACE ACCORDING TO THE OCCUPANT CLASSIFICATION
 FROM TABLE 403.3.1.1 SO THIS REVIEWER CAN CALCULATE THE
 SPACES AS YOU HAVE. FMC 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-15 Cont ID  
Sent By medwards Date 2021-11-15 Time 14:50 Rev Time 0.00
Received By medwards Date 2021-11-15 Time 09:07 Sent To  
Notes
2021-11-15 14:50:281ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091343
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) SHEET M1/01: IN UNIT B-7 PLEASE SHOW THE EXHAUST
 TERMINATION LOCATION IS ON THE EXTERIOR OF THE BUILDING
 AND NOT INSIDE THE PARKING GARAGE. FBC M 501.3
  
 2) SHEET M1/01: PLEASE SHOW THE OUTDOOR AIR DUCT FOR
 AHU-1L-6. FBC M 107.2.1
  
 3) SHEET M1/01: PLEASE SHOW THE FIRE DAMPER AT THE
 RATED WALLS WHERE THE OUTDOOR AIR PENETRATES FOR THE
 PET WASH AND THE STORAGE ROOMS AND THE RATED CORRIDOR
 WALL. FBC M 607
  
 4) SHEET M1/01: PLEASE SHOW HOW THE GENERATOR ROOM WILL
 BE SUPPLIED WITH OUTDOOR AIR FROM THE EXTERIOR OF THE
 BUILDING AND NOT THE PARKING GARAGE. FBC 107.2.1
  
 5) PLEASE PROVIDE VENTILATION CALCULATIONS FOR THE
 PARKING GARAGES. FBC M 404
  
 6) PLEASE SHOW THE PARKING GARAGE FANS AND EXHAUST
 TERMINATION LOCATIONS FOR EACH FLOOR. FBC 107.2.1
  
 7) SHEET M1/05B: PLEASE SHOW THE OUTDOOR AIR DUCT FOR
 AHU-7-2 IN THE FITNESS CENTER. FBC 107.2.1
  
 8) SHEET M1/05B: PLEASE SHOW THE REQUIRED FIRE DAMPERS
 FOR THE OUTDOOR AIR FOR THE TENANTS AS THE DESIGN DOES
 NOT MEET FBC M 607.5.3-3.3: THE DUCT SHALL NOT HAVE
 OPENINGS THAT COMMUNICATE THE CORRIDOR WITH ADJACENT
 SPACES OR ROOMS.
  
 9) PLEASE PROVIDE INFORMATION ON THE DRYER DUCT FOR
 EACH UNIT. FBC M 504.6, 504.8.4
  
 10) SHEET M201: UNIT B-7, PLEASE SHOW THE RETURN AIR
 PATH FROM THE BEDROOM BACK TO THE FCU-C. FBC M 601.5
  
 11) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR
 THIS BUILDING, PLEASE USE TABLE 403.3.1.1 OCCUPANCY
 CLASSIFICATION TO DETERMINE THE USE OF EACH SPACE. FBC
 M 403.3.1.1 AND TABLE 403.3.1.1
  
 12) A1-110: PLEASE SHOW THAT THE CLEARANCES FROM THE
 MECHANICAL UNITS TO THE ROOF EDGE WILL MEET THE 10 FT.
 CLEARANCE OR GUARD PROTECTION. FBC M 304.11
  
 13) PLEASE ADD A NOTE ON THE DRAWINGS THAT STATES THE
 GENERATOR WILL REQUIRE SEPARATE PERMIT APPLICATION,
 REVIEW AND DOCUMENTS FOR REVIEW AS THE GENERATOR WILL
 REQUIRE A SEPARATE PERMIT.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By ccole Date 2022-09-15 Time 17:26 Rev Time 0.00
Received By ccole Date 2022-09-15 Time 15:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-07-28 Cont ID  
Sent By ccole Date 2022-07-28 Time 15:50 Rev Time 0.00
Received By ccole Date 2022-07-27 Time 13:55 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-03-31 Cont ID  
Sent By ccole Date 2022-03-31 Time 17:49 Rev Time 0.00
Received By ccole Date 2022-03-22 Time 09:24 Sent To  
Notes
2022-03-31 17:50:082ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21091343
 3/28/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS FROM THE
 1ST REVIEW ARE LISTED BELOW WITH ADDITIONAL NOTES.
  
 1) FAILED. SHEET A0-000 & P101: PLEASE PROVIDE ON THE
 PLANS A LIST OF REQUIRED SEPARATE PERMITS INCLUDING:
 POOL, POOL HEATERS, GREASE INTERCEPTOR, IRRIGATION,
 GENERATOR, POTABLE WATER BACKFLOW PREVENTER, IRRIGATION
 SYSTEM BACKFLOW PREVENTER, POOL SERVICE BACKFLOW
 PREVENTER, FIRE LINE BACKFLOW PREVENTER, FIRE LINE,
 FIRE SPRINKLER, AND THE FIRE PUMP- SECTIONS 105.1 &
 107.2.1 WPB. THE LIST WAS NOT PROVIDED. PLEASE NOTE
 THAT DUE TO A CHANGE IN PROCESS THE WPB BUILDING DEPT.
 REQUIRES PERMIT APPLICATIONS BE SUBMITTED FOR THE
 GREASE INTERCEPTOR AND THE BACKFLOW PREVENTERS-
 POTABLE, FIRE, IRRIGATION, AND POOL SERVICE BE
 SUBMITTED PRIOR TO ISSUANCE OF THE MAIN (PRIMARY)
 BUILDING PERMIT- SECS. 105 & 107 WPB. FAILURE TO SUBMIT
 APPLICATIONS WILL RESULT ON A HOLD BEING PLACED ON THE
 MAIN BUILDING PERMIT.
 YOU CAN SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 NOTIFY ME VIA EMAIL AND I WILL CHANGE THE REVIEW STATUS
 TO PASS.
  
 2) FAILURE. P101- DEFERRED SUBMITTALS: MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR PLUMBING
 AND GAS EQUIPMENT, APPLIANCES, FIXTURES, CONTROLS,
 PIPING AND MATERIALS THAT ARE NOT SUBMITTED FOR REVIEW
 CAN BE DEFERRED SUBMITTALS IN ACCORDANCE WITH SECTION
 PROVIDE A LIST OF DEFERRED SUBMITTALS ON THE PLAN
 INCLUDING BUT NOT LIMITED TO THE DOMESTIC WATER PUMP,
 WATER HEATERS, KITCHEN AND BATH FIXTURES APPLIANCES,
 EXPANSION TANKS, FULL OPEN VALVES, MIXING VALVES,
 BACKFLOW PREVENTERS, RECIRCULATION PUMPS, WATER HAMMER
 ARRESTORS, TRAP PRIMERS, ROOF DRAINS, TERMINATION CAPS
 ETC.- SECTION 107.3.4.1 WPB. DEFERRED SUBMITTALS LIST
 NOT PROVIDED. FOR THE PURPOSES OF THIS SECTION,
 DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF
 THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE
 APPLICATION AND THAT ARE TO BE SUBMITTED TO THE
 BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL
 OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF
 THE BUILDING OFFICIAL. THE REGISTERED DESIGN
 PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE
 DEFERRED SUBMITTALS ON THE CONSTRUCTION. DOCUMENTS FOR
 REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED
 SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL
 REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL
 WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL
 DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL
 CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED
 SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE
 DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE
 BUILDING OFFICIAL.
  
 3) FAILED. P101- SWIMMING POOL WASTE WATER: THE POOL
 SHALL BE UNDER SEPARATE PERMIT HOWEVER DISPOSAL OF POOL
 WASTE WATER MAY IMPACT THE MAIN STORM DRAIN PLANS.
 PLEASE REVIEW THE FOLLOWING GUIDELINES FOR DISPOSAL OF
 THE WASTE WATER-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER?S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected]. THE ARCHITECT?S RESPONSE
 NARRATIVE INDICATES A STORM PIPE HAS BEEN PROVIDED BUT
 NO ACKNOWLEDGEMENT THAT DECHLORINATION WILL BE
 PROVIDED. PLEASE CLARIFY THE LOCATION OF THE STORM PIPE
 ON THE PLAN- WHICH PLAN SHEET & DETAIL NO.
  
 10) FAILED ITEMS B, C, D, & E. P101 GREASE INTERCEPTOR-
 SECS. 1003.1- 1003.3.8 FBC P.
 B) FAILED. PROVIDE AN INTERCEPTOR EQUIPMENT SCHEDULE-
 MAKE AND MODEL, GALLON SIZE. THERE IS A NOTE BY THE
 LOADING AREA SPECIFYING SCHIER GB-1000. PLEASE RELOCATE
 THE NOTE TO THE INTERCEPTOR LOCATION IF THIS THE MODEL
 TO BE INSTALLED. THE DETAIL ON P401 INDICATES MIAMI
 DERM FOG EFFICIENCY RATING HOWEVER THE PROJECT IS
 LOCATED IN WEST PALM BEACH. FOR WEST PALM BEACH
 REQUIREMENTS PLEASE CONTACT BRYAN SEALEY, CESCO, CESLO
 IPP/FOG COORDINATOR CITY OF WEST PALM BEACH PUBLIC
 UTILITIES DEPARTMENT IPP PROGRAM PHONE: (561) 822-2065
 CELL: (561) 662-2381 EMAIL: [email protected].
 C) FAILED. PROVIDE GREASE WASTE CALCULATIONS. NOT
 PROVIDED.
 D) FAILED. SHOW THE SAMPLING PORT AND VENTING
 LOCATIONS. NOT PROVIODED.
 E) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS. NOT PROVIDED, MAY REQUEST TO
 BE DEFERRED.
 D) FAILED. PLEASE NOTE INSTALLATION OF THE GREASE
 INTERCEPTOR SHALL BE UNDER SEPARATE PERMIT. THE
 REQUESTED SUBMITTAL MAY BE DEFERRED BY REQUEST- SECS.
 105.1 & 107.3.4.1 WPB. LIST OF SEPARATE PERMITS NOT
 PROVIDED- SEE COMMENT #1 ABOVE.
  
 11) FAILED ITEMS A, B ,C. P101- THERE ARE MANY MISSING
 DRAIN POINTS OF CONNECTION TO STORM OR SANITARY MAINS,
 OR CONTINUATIONS TO APPROVED DISPOSAL LOCATIONS. PLEASE
 PLACE NOTES ON THE PLAN TO INDICATE DISCHARGE OR
 CONNECTION LOCATIONS OF THE DP, CD, PD, AD, & O.F.
 PIPES- SEC. 107.2.1 WPB.
 A) FAILED. THE DP LINES SHALL TERMINATE OVER INDIRECT
 WASTE RECEPTORS OR TO THE EXTERIOR OF THE BUILDING-
 SEC. 504.7.2 FBC P. THE PLAN SHOWS THE LINES
 DISCHARGING ONTO THE TRASHROOM FLOOR. THE NEW SHEET
 P101B SH0WS THE ROOF DRAINAGE OVERFLOW LINES (OF)
 DISCHARGING ONTO THE GARAGE FLOORS WHICH IS NOT
 APPROVED PER SEC. 1101.2 FBC P. THE LINES SHALL
 DISCHARGE ABOVE GRADE A MINIMUM OF 12-INCHES FROM THE
 BUILDING IN A LOCATION THAT WOULD NORMALLY BE OBSERVED
 BY OCCUPANTS OR MAINTENANCE PERSONNEL- SEC. 1108.2 FBC
 P.
 B) FAILED. O.F. DRAINS SHOWN TERMINATING IN RETAIL 104,
 CORRIDOR 127, & BICYCLE STORAGE 100. PLEASE NOTE THAT
 IF THE DRAINS ARE TO CONNECT DIRECTLY TO THE GD PIPE,
 PLEASE CLARIFY HOW EMERGENCY OVERFLOW WILL BE OBSERVED
 MY BUILDING OCCUPANTS OR MAINTENANCE PERSONNEL- SEC.
 1108.2 FBC P. THE NEW SHEET P101B SH0WS THE ROOF
 DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE ROOM
 AND GARAGE FLOORS WHICH IS NOT APPROVED PER SEC. 1101.2
 FBC P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM
 OF 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD
 NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE
 PERSONNEL- SEC. 1108.2 FBC P.
 C) FAILED. REFER TO SECTION 1503.7 FBC B AND PROVIDE A
 DETAIL SHOWING THE O.F. DISCHARGE TERMINATION CAP AND
 MINIMUM 12-INCH DISCHARGE DISTANCE FROM THE STRUCTURE
 SIDEWALLS. DETAIL NOT PROVIDED & SEE NOTES ABOVE.
  
 12) FAILED. P101 & P301: SANITARY DRAINS FROM UNITS
 107, 110, & 11 TO MAIN SS NOT SHOWN- SEC. 107.2.1 WPB.
 NOT SHOWN ON P101A, P101B, P201. A) PLEASE CLEARLY
 IDENTIFY THE LOCATION AND SUIZE OF THE FD IN THE
 BOOSTER PUMP ROOM SHOWN ON P101A- SEC. 606.5 FBC P.
  
 13) FAILED. P101 & P301: SHOW THE WATER SERVICE PIPING
 ENTRANCES TO UNITS 107, 110, & 111 ON P101- SEC. 602.1
 FBC P. MAIN SHUTOFFS AND WATER METER LOCATIONS NOT
 SHOWN- SEC.
  
 15) FAILED. P101, P102, P103, P104, P105, P106: PLEASE
 PROVIDE THE MAIN PLUMBING RISER DRAWINGS THAT CORRELATE
 WITH THE CIRCLE SYMBOLS AT THE BASE OF EACH VERTICAL
 STACK LOCATION INCLUDING THE (SS- SANITARY). (CD-
 CONDENSATE PIPES), (DP- DISCHARGE PIPES FROM WATER
 HEATERS), (RWL- RAIN WATER LEADERS), (PD-PLANTER
 DRAINS) - SEC. 107.3.5.1.3 WPB. PLEASE PROVIDE SUPPORT
 AND BRACING DETAILS FOR THE RISERS- SECS. 308.1- 308.9
 FBC P. NEW SHEETS P305, P306, P308, P309: MINIMUM
 4-INCH STACK VENTS ARE REQUIRED FOR THE 4-INCH WASHING
 MACHINE WASTE STACKS- SEC. 913.3 FBC P. A)
  
 16) P101: PROVIDE TOTAL DFU CALCULATIONS AND THE MAIN
 SANITARY PIPE SIZES ALONG THE HORIZONTAL RUN FROM THE
 SOUTH END OF THE CORRIDOR TO THE EXIT ON THE NORTH END-
 SECS. 709 AND 710 FBC P. SHEETS P101A, P310, & P311:
 THE TOTAL DFU CALCULATIONS ON THE RISERS ARE DIFFERENT
 FROM THE FLOOR PLAN- WHICH IS CORRECT?
  
 18) FAILED. P101: PROVIDE WSFU CALCULATIONS AND MAIN
 WATER RISER DRAWING- SECS. 603.1, E103 FBC P, AND SEC.
 107.3.5.1.3 WPB. BASIS OF CALCULATIONS NOT PROVIDED.
 PLEASE VERIFY COMPLIANCE WITH SEC. 604.3 FBC P.
  
 20) FAILED. P101, P102, P103, P104: PROVIDE A GARAGE
 DRAIN RISER DRAWING- SEC. 107.3.5.1.3 WPB. SHEET P316:
 PROVIDE DRAIN-PIPE SIZING CALCULATIONS- SEC. 107.2.1
 WPB. A) PROVIDE A TYPICAL PIPE SLOPE FOR THE SYSTEM-
 TABLE 1106.2 FBC P. C) PROVIDE CLEANOUT LOCATIONS- SEC.
 1101.8 FBC P.
  
 22) FAILED. P104 & P107- ROOF DRAINAGE: SHEETS P101B,
 P312: A) PROVIDE A TYPICAL PIPE SLOPE FPR THE SYSTEM IN
 ACCORDANCE WITH TABLE 1106.2 FBC P. B) PROVIDE CLEANOUT
 LOCATIONS- SEC. 1101.8 FBC P.
 A) FAILED. PROVIDE PRIMARY AND OVERFLOW ROOF DRAIN
 RISER DRAWINGS- SECTION 107.3.5.1.3 WPB, AND SECS.
 1106.1, 1106.1, & 1108.1 FBC P. SHEETS P101B & P312:
 ROOF DRAINAGE OVERFLOW LINES (OF) DISCHARGING ONTO THE
 ROOM AND GARAGE FLOORS NOT APPROVED PER SEC. 1101.2 FBC
 P. THE LINES SHALL DISCHARGE ABOVE GRADE A MINIMUM OF
 12-INCHES FROM THE BUILDING IN A LOCATION THAT WOULD
 NORMALLY BE OBSERVED BY OCCUPANTS OR MAINTENANCE
 PERSONNEL- SEC. 1108.2 FBC P.
  
 24) FAILED. P201A: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P. COLD WATER IS ALLOWED TO BE DEIVERED FROM THE
 LAVATORIES HOWEVER THE REVISED DRAWING SHOWS ONLY COLD
 WATER DELIVERED FROM THE MOP SINK- HOT WATER IS
 REQUIRED PER SEC. 607.1 FBC P. A) WATER RISER FOR THE
 BATHROOMS NOT PROVIDED- SEC. 107.3.5.1.3 WPB. PLEASE
 NOTE THAT A MEANS OF LIMITING THE HOT WATER TEMPERATURE
 TO THE MOP SINK AND OTHER FIXTURES WILL BE REQUIRED PER
 SEC. 607.1.1 FBC P.
  
 26) FAILED. P205: PLEASE INDICATE HOW TEMPERED WATER
 WILL BE DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC
 P. COLD WATER PASSED. A) NEW #3 & #4 SANITARY
 ISOMETRIC: THE DF FIXTURE DRAINS SHALL DISCHARGE INTO
 THE 4-INCH DRAIN DOWNSREAM OF THE WC FIXTURE DRAIN-
 SEC. 912.1 FBC P. B) TWO OF THE FOUR WATER CLOSETS THAT
 ARE FURTHEST DOWNSTREAM ARE WET VENTED. THE TWO
 FURTHEST UPSTREAM MUST BE INDIVUALLY OR COMMONLY
 VENTED- SECS. 910.1, 911.1, & 912.1 FBC P. C) THE FLOOR
 DRAIN FIXTURE DRAIN SHALL CONNECT INDEPENDENTLY TO THE
 4-INCH DRAIN DOWNSTREAM OF THE LAVATORY DRAIN
 CONNECTION- SEC. 912.1.
  
 35) A0-003: PLEASE CORRECT ZONING REFERENCE INDICATING
 THE CITY OF HOLLYWOOD- SECTION 107.2.1 WPB.
  
 36) FAILED. A0-003 DESIGN CRITERIA: INDICATE WHICH
 CODES AND/OR STANDARDS WERE USED IN THE DESIGN OF THE
 PUBLIC BATHROOMS AND PRIVATE KITCHEN AND BATHROOMS-
 SECTION 107.2.1 WPB. PLEASE NOTE THAT THE FBC-2020 7TH
 EDITION ACCESSIBILITY CODE IS THE CURRENT CODE USED IN
 THE CITY OF WPB FOR PLUMBING FIXTURE INSTALLATIONS IN
 PLACES OF PUBLIC ACCOMMODATION AND COMMERCIAL
 FACILITIES- SEC. 210.1 FBC ACC. THE FBC ACC SHALL BE
 USED FOR DESIGN OF THE 1ST AND 7TH FLOOR BATHROOMS.
 CONCERNING THE PRIVATE APARTMENT KITCHENS AND BATHS,
 THE DESIGN AND INSTALLATION OF PLUMBING FIXTURES IN THE
 PRIVATE KITCHENS AND BATHROOMS SHALL BE IN COMPLIANCE
 WITH THE FAIR HOUSING ACT DESIGN MANUAL OR THE FAIR
 HOUSING ACCESSIBILITY GUIDELINES. THE GUIDELINES WHICH
 ARE FOUND IN THE FBC ACC PROVIDE SAFE HARBOR FOR
 COMPLIANCE WITH THE ACCESSIBILITY REQUIREMENTS OF THE
 FAIR HOUSING ACT. THE DESIGNER OF RECORD SHALL CHOOSE
 WHICH DESIGN METHOD WILL BE USED AND PROVIDE DRAWINGS
 AND DETAILS INDICATING COMPLIANCE. THE FAIR HOUSING
 DESIGN COMPLIANCE NOT CALLED OUT IN THE CODES AND
 STANDARDS BLOCK ON THE PLAN.
  
 37) FAILED B. A0-101 & A1-101- PLUMBING FIXTURE
 CALCULATIONS- SECTION AND TABLE 403.1 FBC P.
 B) FAILED. PROVIDE SEPARATE FIXTURE CALCULATION TABLES
 FOR RETAIL- 102, RETAIL- 104, OFFICE/RETAIL- 105.
 PLEASE REVISE THE PLANS TO SHOW THE LOCATIONS OF THE
 FIXTURES AND PLUMBING PIPING REQUIREMENTS. THE REQUIRED
 FIXTURES FOR THESE OCCUPANCIES CAN BE LISTED AS
 "FUTURE" IF NECESSARY. ACKNOWLEDGED THAT THE REQUIRED
 1ST FLOOR PLUMBING FIXTURES ARE FUTURE AND TO BE
 DETERMINED, HOWEVER PLEASE PROVIDE CALCULATIONS FOR THE
 WOMENS AND MENS RESTROOMS 124 AND 126 IN ACCORDANCE
 WITH TABLE 403.1 FBC P.
  
 38) FAILED. A0-106 & A1-106: THE OCCUPANT LOAD OF 456
 SHOWN IN THE PLUMBING FIXTURE CALCULATION TABLE IS
 INCORRECT BASED ON THE LIFE SAFETY LOAD TABLE WHICH
 INDICATES 562- TABLE 403.1 FBC P. THE OCCUPANT LOADS
 SHOWN IN THE TABLE ON A0-106 HAVE BEEN OVERLAYED BY
 GENERAL NOTES ON THE PLAN AND NOT ENTIRELY LEGIBLE.
  
 39) FAILED. A1-106: PLEASE PROVIDE THE CODE SECTION
 ASSOCIATED WITH THE SWIMMING POOL EXCEPTION AND SHOW
 THE 200-FOOT HORIZONTAL RADIUS TO VERIFY COMPLIANCE-
 SECTION 403.6 FBC P. IT APPEARS DESPITE THE EXCEPTION,
 THE PLANS INDICATE COMBINED POOLSIDE AND AMENITIES
 BATHROOMS. PLEASE CLARIFY IF FLOOR DRAINS WILL BE
 INSTALLED- NONE SHOWN ON P205- SEC. 403.6.3 FBC P.
 PLEASE LABEL THE 200 FT. RADIUS. PLEASE NOTE THE PLAN
 APPEARS TO SHOW THERE IS NOT AN ACCESSIBLE ROUTE TO THE
 POOL DECK- REQUIRMENT 2 FAIR HOUSING ACCESSIBILITY
 GUIDELINES FBC ACC, AND PG. 2.7 FAIR HOUSING DESIGN
 MANUAL.
  
 40) FAILED C, D, G, H . A1-320- FBC- ACC MISSING AND
 INCORRECT COMPLIANCE DETAILS. PLEASE NOTE THAT NEW
 CONSTRUCTION ACCESSIBLE COMPARTMENTS SHALL BE DESIGNED
 IN ACCORDANCE WITH 604.8.1.6 & 604.8.1.7.:
 C) FAILED. SHOW TURNING SPACE DIAMETERS- 304.3. NOT
 PROVIDED.
 D) FAILED. THE DOORS SHALL NOT SWING INTO THE CLEAR
 FLOOR SPACES FOR THE FIXTURES- 603.2.3. DETAIL 3 NOT IN
 COMPLIANCE.
 G) FAILED. SHOW THE HEIGHTS OF THE MIRRORS FROM THE
 FINISHED FLOORS NOT SHOWN TO THE REFLECTIVE SURFACES-
 SECTION 603.3 SHEET A2-210: NOTE INDICATING MEASUREMENT
 TO THE REFLECTIVE SURFACE NOT PROVIDED.
 H) FAILED. SHOW THE LOCATIONS, LENGTHS, AND MOUNTING
 HEIGHTS OF GRAB BARS FOR THE WATER CLOSETS IN
 COMPLIANCE WITH - SECTION 604.5 & 609.4, FIGURES
 604.5.1 & 604.5.2. SHEET A6-301: REFER TO THE FIGURES
 LISTED- 604.5.1 & 604.5.2. INDICATE SIDE WALL GRAB BAR
 TO EXTEND MINIMUM 54-INCHES FROM THE WALL. INDICATE
 REAR WALL GRAB BAR SHALL BE 36 INCHES LONG MINIMUM AND
 EXTEND FROM THE CENTERLINE OF THE WATER CLOSET 12
 INCHES MINIMUM ON ONE SIDE AND 24 INCHES MINIMUM ON THE
 OTHER SIDE.
 J) FAILED. CENTERLINES OF THE TOILET PAPER DISPENSERS
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7. DETAIL ON A6-301 REFERENCED IN NARRATIVE
 IS INCORRECT. TP SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM MEASURED FROM THE FRONTS OF THE WATER CLOSETS.
 K) FAILED. KNEE AND TOE CLEARANCES FOR THE LAVATORIES-
 SECTION 606.2. REFER TO FIGURES 306.2 7 306.3 FBC ACC
 AND MAKE CORRECTIONS.
 M) FAILED. CLEAR WIDTHS OF THE ACCESSIBLE COMPARTMENT
 DOORS- 404.2.3. NOT PROVIDED.
  
 44 & 45) FAILED. SHEET A1-301, A1-303, A1-305- UNITS
 A1, A2, B2, & B7: THE REVISED BATH FLOOR PLANS SHOWING
 SHOWERS INSTEAD OF BATHTUBS ARE NOT IN COMPLIANCE WITH
 THE FAIR HOUSING DESIGN ACT MANUAL- PGS. 7.56- 7.59 A)
 REQUIRED PARALLEL APPROACH 30X48-INCH UNOBSTRUCTED
 CLEAR FLOOR SPACE NOT PROVIDED. B) MINIMUM 36-INCH WIDE
 SHOWER NOT PROVIDED.
  
 49) FAILED. A1-305 UNITS C1: THE REVISED FLOOR PLAN
 SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 51) FAILED. A1-306 UNITS C2 & C3: THE REVISED FLOOR
 PLAN SHOWS THE CONTROLS FOR THE SHOWER ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL. SHOW THE
 MINIMUM REQUIRED 30X48-INCH CLEAR FLOOR SPACE DIAGRAMS
 FOR PARALLEL APPROACHES TO THE BATHTUBS- FHA MANUAL
 7.53- 7.55, AND FHA GUIDELINES FIGURE 8. PLEASE NOTE
 THAT COMPLIANCE IN C3 WILL NOT BE POSSIBLE UNLESS A
 WALL HUNG LAVATORY SINK WITH KNEE AND TOE CLEARANCES IS
 PROVIDED. A) UNIT C3: THE WATER CLOSET AND LAVATORY
 SPACING MEASURMENTS ARE NOT SHOWN- PG. 7.43 FHDA
 MANUAL.
  
 53) FAILED. A1-307 UNIT C5, A1-308 UNIT C6: THE REVISED
 FLOOR PLANS SHOW THE CONTROLS FOR THE SHOWERS ON THE
 REAR WALL INSTEAD OF THE SIDE WALL ADJACENT TO THE
 CLEAR FLOOR SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 55) FAILED. A1-309 UNIT D-1: THE REVISED FLOOR PLANS
 SHOW THE CONTROLS FOR THE SHOWERS ON THE REAR WALL
 INSTEAD OF THE SIDE WALL ADJACENT TO THE CLEAR FLOOR
 SPACE- SEE PGS. 7.56- 7.59 FHDA MANUAL.
  
 NEW COMMENTS BASED ON NEW OR CORRECT PLAN SHEETS:
  
 1) P313: PROVIDE PLANTER DRAIN-PIPE SIZING
 CALCULATIONS- SECS. 1105.2 & 1106.1 FBC P. A) PROVIDE A
 TYPICAL PIPE SLOPE FOR THE SYSTEM- TABLE 1106.2 FBC P.
 C) PROVIDE CLEANOUT LOCATIONS- SEC. 1101.8 FBC P.
  
 2) P106, P315: SHOW THE LOCATION OF THE 80-GALLON
 HYDROPNEUMATIC TANK ON THE ROOF- SEC. 107.2.1 WPB. A)
 PROVIDE DETAILS SHOWING TANK ANCHORING, WATER PIPING
 DETAILS, OVERFLOW, RELIEF AND DRAIN PIPING DETAILS, AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS- SECS. 606.5-
 606.5.7 FBC P.
  
 3) A1-310: FAIR HOUSING DIAGRAMS AND DIMENSIONS NOT
 SHOWN ON THE FLOOR PLAN- SEC. 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected].
  
  
  
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By cthroop Date 2021-12-15 Time 09:31 Rev Time 0.00
Received By ccole Date 2021-12-10 Time 12:41 Sent To  
Notes
2021-12-15 09:35:001ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091343
 12/14/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A0-000 & P101: PLEASE PROVIDE ON THE PLANS A
 LIST OF REQUIRED SEPARATE PERMITS INCLUDING: POOL, POOL
 HEATERS, GREASE INTERCEPTOR, IRRIGATION, GENERATOR,
 POTABLE WATER BACKFLOW PREVENTER, IRRIGATION SYSTEM
 BACKFLOW PREVENTER, POOL SERVICE BACKFLOW PREVENTER,
 FIRE LINE BACKFLOW PREVENTER, FIRE LINE, FIRE
 SPRINKLER, AND THE FIRE PUMP- SECTIONS 105.1 & 107.2.1
 WPB.
  
 2) P101- DEFERRED SUBMITTALS: MANUFACTURER'S
 SPECIFICATIONS AND INSTALLATION GUIDELINES FOR PLUMBING
 AND GAS EQUIPMENT, APPLIANCES, FIXTURES, CONTROLS,
 PIPING AND MATERIALS THAT ARE NOT SUBMITTED FOR REVIEW
 CAN BE DEFERRED SUBMITTALS IN ACCORDANCE WITH SECTION
 PROVIDE A LIST OF DEFERRED SUBMITTALS ON THE PLAN
 INCLUDING BUT NOT LIMITED TO THE DOMESTIC WATER PUMP,
 WATER HEATERS, KITCHEN AND BATH FIXTURES APPLIANCES,
 EXPANSION TANKS, FULL OPEN VALVES, MIXING VALVES,
 BACKFLOW PREVENTERS, RECIRCULATION PUMPS, WATER HAMMER
 ARRESTORS, TRAP PRIMERS, ROOF DRAINS, TERMINATION CAPS
 ETC.- SECTION 107.3.4.1 WPB.
  
 3) P101- SWIMMING POOL WASTE WATER: THE POOL SHALL BE
 UNDER SEPARATE PERMIT HOWEVER DISPOSAL OF POOL WASTE
 WATER MAY IMPACT THE MAIN STORM DRAIN PLANS. PLEASE
 REVIEW THE FOLLOWING GUIDELINES FOR DISPOSAL OF THE
 WASTE WATER-
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER?S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 A) THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH
 TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 B) NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 C) WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE
 ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL
 OWNER?S PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 D) DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 E) FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT
 O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 F) FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS,
 PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
 4) P101 & P400: TO HELP EXPEDITE THE REVIEW, PLEASE ADD
 THE ABBREVIATIONS DP, OF, AND SPK TO THE ABBREVIATION
 LEGEND- SEC. 107.2.1 WPB.
  
 5) P101: PROVIDE THE TEXT FOR CIRCLED KEYNOTES 1, 2, &
 3- SEC. 107.2.1 WPB.
  
 6) P101: PLEASE CORRECT THE SHEET TITLE INDICATING THE
 6TH FLOOR- SEC. 107.2.1 WPB.
  
 7) P101: PLEASE SHOW THE SS- 28, 28A, AND 29 PIPE
 CONNECTIONS INTO THE 6-INCH SANITARY LINE- SEC. 107.2.1
 WPB.
  
 8) P101: PLEASE IDENTIFY THE STORM DRAIN MANHOLE AND
 SHOW THE DRAINAGE CONTINUATION OUT OF THE BUILDING-
 SEC. 1101.2 FBC P.
  
 9) P101 & P400: INDICATE HOW THE ELEVATOR SUMP PITS
 WILL BE VENTED AND SUBMIT MANUFACTURER'S SPECIFICATIONS
 FOR THE PUMP AND THE PIT- SEC. 712.3 FBC P.
  
 10) P101 GREASE INTERCEPTOR- SECS. 1003.1- 1003.3.8 FBC
 P.
 A) SHOW THE GREASE WASTE PIPE POINT OF CONNECTION TO
 THE SANITARY.
 B) PROVIDE AN INTERCEPTOR EQUIPMENT SCHEDULE- MAKE AND
 MODEL, GALLON SIZE. THERE IS A NOTE BY THE LOADING AREA
 SPECIFYING SCHIER GB-1000. PLEASE RELOCATE THE NOTE TO
 THE INTERCEPTOR LOCATION IF THIS THE MODEL TO BE
 INSTALLED.
 C) PROVIDE GREASE WASTE CALCULATIONS.
 D) SHOW THE SAMPLING PORT AND VENTING LOCATIONS.
 E) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS.
  
 PLEASE NOTE INSTALLATION OF THE GREASE INTERCEPTOR
 SHALL BE UNDER SEPARATE PERMIT. THE REQUESTED SUBMITTAL
 MAY BE DEFERRED BY REQUEST- SECS. 105.1 & 107.3.4.1
 WPB.
  
 11) P101- THERE ARE MANY MISSING DRAIN POINTS OF
 CONNECTION TO STORM OR SANITARY MAINS, OR CONTINUATIONS
 TO APPROVED DISPOSAL LOCATIONS. PLEASE PLACE NOTES ON
 THE PLAN TO INDICATE DISCHARGE OR CONNECTION LOCATIONS
 OF THE DP, CD, PD, AD, & O.F. PIPES- SEC. 107.2.1 WPB.
 A) THE MAIN 4-INCH GARAGE DRAIN PIPE (GD) IS SHOWN
 EXITING THE BUILDING TO AN UNIDENTIFIED LOCATION- SEC.
 107.2.1 WPB.
 B) O.F. DRAINS SHOWN TERMINATING IN RETAIL 104,
 CORRIDOR 127, & BICYCLE STORAGE 100. PLEASE NOTE THAT
 IF THE DRAINS ARE TO CONNECT DIRECTLY TO THE GD PIPE,
 PLEASE CLARIFY HOW EMERGENCY OVERFLOW WILL BE OBSERVED
 MY BUILDING OCCUPANTS OR MAINTENANCE PERSONNEL- SEC.
 1108.2 FBC P.
 C) REFER TO SECTION 1503.7 FBC B AND PROVIDE A DETAIL
 SHOWING THE O.F. DISCHARGE TERMINATION CAP AND MINIMUM
 12-INCH DISCHARGE DISTANCE FROM THE STRUCTURE
 SIDEWALLS.
  
 12) P101 & P301: SANITARY DRAINS FROM UNITS 107, 110, &
 11 TO MAIN SS NOT SHOWN- SEC. 107.2.1 WPB.
  
 13) P101 & P301: SHOW THE WATER SERVICE PIPING
 ENTRANCES TO UNITS 107, 110, & 111 ON P101- SEC. 602.1
 FBC P.
  
 14) P101 & P400: PROVIDE FIXTURE SCHEDULES FOR THE
 GARAGE DRAINS, TRENCH DRAINS, FLOOR DRAINS, AND FLOOR
 SINKS- SECS. 413, 414 FBC P. PROVIDE HEAVY DUTY TRAFFIC
 RATED COVERS FOR THE GARAGE AND TRENCH DRAINS.
  
 15) P101, P102, P103, P104, P105, P106: PLEASE PROVIDE
 THE MAIN PLUMBING RISER DRAWINGS THAT CORRELATE WITH
 THE CIRCLE SYMBOLS AT THE BASE OF EACH VERTICAL STACK
 LOCATION INCLUDING THE (SS- SANITARY). (CD- CONDENSATE
 PIPES), (DP- DISCHARGE PIPES FROM WATER HEATERS), (RWL-
 RAIN WATER LEADERS), (PD-PLANTER DRAINS) - SEC.
 107.3.5.1.3 WPB. PLEASE PROVIDE SUPPORT AND BRACING
 DETAILS FOR THE RISERS- SECS. 308.1- 308.9 FBC P.
  
 16) P101: PROVIDE TOTAL DFU CALCULATIONS AND THE MAIN
 SANITARY PIPE SIZES ALONG THE HORIZONTAL RUN FROM THE
 SOUTH END OF THE CORRIDOR TO THE EXIT ON THE NORTH END-
 SECS. 709 AND 710 FBC P.
  
 17) P101: SHOW LOCATIONS OF CLEANOUTS IN ACCORDANCE
 WITH SECS. 708.1.1, 708.1.3, & 708.1.4 FBC P.
  
 18) P101: PROVIDE WSFU CALCULATIONS AND MAIN WATER
 RISER DRAWING- SECS. 603.1, E103 FBC P, AND SEC.
 107.3.5.1.3 WPB.
  
 19) P101, P102, P103, P104: PROVIDE A HOSE BIB WATER
 RISER DRAWING- SEC. 107.3.5.1.3 WPB.
  
 20) P101, P102, P103, P104: PROVIDE A GARAGE DRAIN
 RISER DRAWING- SEC. 107.3.5.1.3 WPB.
  
 21) P102, P103, P104: SOME OF THE CIRCLED SYMBOLS ARE
 MISSING PIPE IDENTIFICATIONS. PLEASE REVIEW AND
 CORRECT- SEC. 107.2.1 WPB.
  
 22) P104 & P107- ROOF DRAINAGE:
 A) PROVIDE PRIMARY AND OVERFLOW ROOF DRAIN RISER
 DRAWINGS- SECTION 107.3.5.1.3 WPB, AND SECS. 1106.1,
 1106.1, & 1108.1 FBC P.
 B) INDICATE THE RAINFALL RATE PER SEC. 1106.1 AND
 PROVIDE ROOF DRAINAGE CALCULATIONS BASED ON THE RATE-
 SECS. 1106.1- 1106.3 FBC P. P
 C) VERIFY THE ROOF AND DRAINAGE SYSTEM HAS BEEN
 DESIGNED IN COMPLIANCE WITH SECTION 1101.7 FOR MAXIMUM
 DEPTH OF PONDING WATER AND DEFLECTED STRUCTURAL
 ELEMENTS.
 D) PROVIDE THE MAKES AND MODELS OF THE ROOF AND
 OVERFLOW DRAINS AND SUBMIT MANUFACTURER?S
 SPECIFICATIONS PER SEC. 1105.1 FBC P.
  
 23) P201, P201A: PLEASE LABEL WHAT FLOOR THIS PLAN
 SHEET IS FOR AND PROVIDE ROOM NUMBERS FOR THE ENLARGED
 #2 SANITARY AND WATER LAYOUT DRAWINGS- SEC. 107.2.1
 WPB.
  
 24) P201A: PLEASE INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P.
  
 25) P201A: THE PLAN APPEARS TO SHOW THE 1/2-INCH HW
 PIPES TO THE LAVATORIES HAVE EXCEEDED THE MAXIMUM
 ALLOWABLE LENGTHS OF 2 FT. FROM THE SOURCE OF THE HW-
 SEE TABLE C404.5.1 FBC EC. PROVIDE EITHER RECIRCULATION
 PUMPS OR POINT OF USE WATER HEATERS.
  
 26) P205: PLEASE INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORIES- SEC. 419.5 FBC P.
  
 27) P205: SHOW THE VENT LOCATIONS AND VENT SIZES IN THE
 ENLARGED SANITARY DRAWINGS- SECS. 909-912 FBC P.
  
 28) P301, P303, P305, P401: SHOW THE LOCATIONS OF THE
 REQUIRED EXPANSION TANKS FOR THE WATER HEATERS- SEC.
 607.3 FBC P.
  
 29) P301, P303, P305, P401: BASED ON THE WATER HEATER
 DETAILS ON P401, PLEASE SHOW THE HW RECIRCULATION LINES
 IN THE ISOMETRIC DRAWINGS- SEC. 107.2.1 WPB, AND 607.2
 FBC P.
  
 30) P301, P303, P305, P401: PROVIDE BACKFLOW PREVENTION
 FOR THE WATER SUPPLY LINES TO THE DISHWASHER AND
 REFRIGERATOR ICE MAKERS- SECTIONS 409.2 & 608.3 FBC P.
  
 31) P302: PLEASE PROVIDE THE DRAIN AND VENT PIPE SIZES
 FOR THE WM AND SK/DW RISERS- SECS. 406.2 & 409.2 FBC P.
  
 32) P400: DOMESTIC DISHWASHERS SHALL CONFORM TO NSF
 184, NOT ASSE 1006 AS THE SCHEDULE INDICATES- SEC.
 409.1 FBC P.
  
 33) P401- CORRELATE THE WATER HEATER DISCHARGE PIPING
 DETAIL TO MATCH THE PLUMBING PLANS WHICH SHOW COMMON
 RISER PIPES CONVEYING THE DISCHARGES TO THE STORM DRAIN
 SYSTEM- SEC. 107.2.1 WPB, & SECS. 504.6- 504.7.2 FBC P.
  
 34) P401: WATER HEATER UNIT LOCATIONS NOT INDICATED
 BELOW THE DETAILS- SEC. 107.2.1 WPB.
  
 35) A0-003: PLEASE CORRECT ZONING REFERENCE INDICATING
 THE CITY OF HOLLYWOOD- SECTION 107.2.1 WPB.
  
 36) A0-003 DESIGN CRITERIA: INDICATE WHICH CODES AND/OR
 STANDARDS WERE USED IN THE DESIGN OF THE PUBLIC
 BATHROOMS AND PRIVATE KITCHEN AND BATHROOMS- SECTION
 107.2.1 WPB. PLEASE NOTE THAT THE FBC-2020 7TH EDITION
 ACCESSIBILITY CODE IS THE CURRENT CODE USED IN THE CITY
 OF WPB FOR PLUMBING FIXTURE INSTALLATIONS IN PLACES OF
 PUBLIC ACCOMMODATION AND COMMERCIAL FACILITIES- SEC.
 210.1 FBC ACC. THE FBC ACC SHALL BE USED FOR DESIGN OF
 THE 1ST AND 7TH FLOOR BATHROOMS. CONCERNING THE PRIVATE
 APARTMENT KITCHENS AND BATHS, THE DESIGN AND
 INSTALLATION OF PLUMBING FIXTURES IN THE PRIVATE
 KITCHENS AND BATHROOMS SHALL BE IN COMPLIANCE WITH THE
 FAIR HOUSING ACT DESIGN MANUAL OR THE FAIR HOUSING
 ACCESSIBILITY GUIDELINES. THE GUIDELINES WHICH ARE
 FOUND IN THE FBC ACC PROVIDE SAFE HARBOR FOR COMPLIANCE
 WITH THE ACCESSIBILITY REQUIREMENTS OF THE FAIR HOUSING
 ACT. THE DESIGNER OF RECORD SHALL CHOOSE WHICH DESIGN
 METHOD WILL BE USED AND PROVIDE DRAWINGS AND DETAILS
 INDICATING COMPLIANCE.
  
 37) A0-101 & A1-101- PLUMBING FIXTURE CALCULATIONS-
 SECTION AND TABLE 403.1 FBC P..
  
 A) CORRECT THE NOTE IN THE TABLE REFERENCING A0.105 FOR
 BREAKDOWN. NO BREAKDOWN IS SHOWN ON THAT PLAN SHEET.
 B) PROVIDE SEPARATE FIXTURE CALCULATION TABLES FOR
 RETAIL- 102, RETAIL- 104, OFFICE/RETAIL- 105. PLEASE
 REVISE THE PLANS TO SHOW THE LOCATIONS OF THE FIXTURES
 AND PLUMBING PIPING REQUIREMENTS. THE REQUIRED FIXTURES
 FOR THESE OCCUPANCIES CAN BE LISTED AS "FUTURE" IF
 NECESSARY.
  
 38) A0-106 & A1-106: THE OCCUPANT LOAD OF 456 SHOWN IN
 THE PLUMBING FIXTURE CALCULATION TABLE IS INCORRECT
 BASED ON THE LIFE SAFETY LOAD TABLE WHICH INDICATES
 562- TABLE 403.1 FBC P.
  
 39) A1-106: PLEASE PROVIDE THE CODE SECTION ASSOCIATED
 WITH THE SWIMMING POOL EXCEPTION AND SHOW THE 200-FOOT
 HORIZONTAL RADIUS TO VERIFY COMPLIANCE- SECTION 403.6
 FBC P. IT APPEARS DESPITE THE EXCEPTION, THE PLANS
 INDICATE COMBINED POOLSIDE AND AMENITIES BATHROOMS.
 PLEASE CLARIFY IF FLOOR DRAINS WILL BE INSTALLED- NONE
 SHOWN ON P205- SEC. 403.6.3 FBC ZP.
  
 40) A1-320- FBC- ACC MISSING AND INCORRECT COMPLIANCE
 DETAILS. PLEASE NOTE THAT NEW CONSTRUCTION ACCESSIBLE
 COMPARTMENTS SHALL BE DESIGNED IN ACCORDANCE WITH
 604.8.1.6 & 604.8.1.7.:
 A) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE WATER CLOSETS- SEC. 604.3.
 B) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE LAVATORIES- 606.2.
 C) SHOW TURNING SPACE DIAMETERS- 304.3.
 D) THE DOORS SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACES FOR THE FIXTURES- 603.2.3.
 E) SHOW CLEAR FLOOR SPACE DIAGRAMS AND DIMENSIONS FOR
 THE ACCESSIBLE URINALS- 605.3.
 F) THE CENTERLINE OF THE WATER CLOSET FROM THE SIDE
 WALL IN THE MEN?S 724 COMPARTMENT EXCEEDS THE MAXIMUM
 18 INCHES - SECTION 604.2.
 G) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED
 FLOORS NOT SHOWN TO THE REFLECTIVE SURFACES- SECTION
 603.3
 H) SHOW THE LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF
 GRAB BARS FOR THE WATER CLOSETS IN COMPLIANCE WITH -
 SECTION 604.5 & 609.4, FIGURES 604.5.1 & 604.5.2.
 I) LOCATIONS OF THE WATER CLOSET FLUSH CONTROLS -
 SECTION 604.6.
 J) CENTERLINES OF THE TOILET PAPER DISPENSERS SHALL BE
 7 INCHES MINIMUM AND 9 INCHES MAXIMUM MEASURED FROM THE
 FRONTS OF THE WATER CLOSETS- SECTION AND FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORIES- SECTION
 606.2.
 L) DEPTH OF THE ACCESSIBLE URINAL- 605.2.
 M) CLEAR WIDTHS OF THE ACCESSIBLE COMPARTMENT DOORS-
 404.2.3.
  
 41) A1-320: SHOW THE DEPTH AND WIDTH DIMENSIONS OF THE
 STANDARD WATER CLOSET COMPARTMENTS- SEC 405.3 FBC P.
  
 42) A1-301: BASED ON THE NOTE INDICATING SPECIFICATION
 A, IT IS ASSUMED THE PRIVATE ROOMS HAVE BEEN DESIGNED
 IN ACCORDANCE WITH THE FAIR HOUSING DESIGN ACT MANUAL
 WHICH IS BASED ON THE (ANSI) A117.1.1986.
  
 43) A1-301 UNIT A2: THE CLEAR FLOOR SPACE FORWARD
 APPROACH DIAGRAMS FOR THE KITCHEN SINK AND RANGE DO NOT
 SHOW THE REQUIRED EXTENSIONS NEEDED FOR KNEE AND TOE
 CLEARANCES. PLEASE SEE FHA MANUAL- PAGE 7.4. UNLESS
 KNEE SPACE IS PROVIDED, SPACE TO EXECUTE A PARALLEL
 APPROACH MUST BE PROVIDED AT RANGES, COOKTOPS AND
 SINKS. PLEASE CORRECT THE DRAWING OR PROVIDE A DETAIL
 TO INDICATE HOW KNEE SPACE WILL BE PROVIDED.
  
 44) A1-303 UNIT B1 & A1- 304 UNITS B2, B3: PROVIDE A
 60-INCH DIAMETER TURNING CIRCLE IN THE KITCHEN- FHA
 MANUAL- PAGE 7.9.
  
 45) A1-301 THRU A1-311: PROVIDE THE CLEAR FLOOR SPACE
 DIAGRAMS AND DIMENSIONS FOR THE WATER CLOSETS, AND THE
 CENTERLINES OF THE WATER CLOSETS- FHA MANUAL 7.43-
 7.46. PLEASE INDICATE THE DIRECTIONAL APPROACH TO THE
 WATER CLOSET USING AN ARROW SYMBOL, AND THE DEPTH OF
 THE LAVATORY AND/OR VANITY CABINET.
  
 46) A1-301 UNITS A1, A2, A3: THE CLEAR FLOOR SPACES FOR
 THE LAVATORIES ARE BEING OBSTRUCTED BY THE WATER
 CLOSETS- FHA MANUAL PGS. 7.39 & 7.47.
  
 47) A1-302 UNIT A5: THE CLEAR FLOOR SPACE FOR THE
 LAVATORY IS BEING OBSTRUCTED BY THE WATER CLOSETS- FHA
 MANUAL PGS. 7.39 & 7.47.
  
 48) A1-304 UNITS B2 & B3: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 49) A1-305 UNITS B7 & C2: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 50) A1-305 UNIT C1: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM FOR A PARALLEL
 APPROACH TO THE BATHTUB- FHA MANUAL 7.53- 7.55, AND FHA
 GUIDELINES FIGURE 8.
  
 51) A1-306 UNITS C2 & C3: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAMS FOR PARALLEL
 APPROACHES TO THE BATHTUBS- FHA MANUAL 7.53- 7.55, AND
 FHA GUIDELINES FIGURE 8. PLEASE NOTE THAT COMPLIANCE IN
 C3 WILL NOT BE POSSIBLE UNLESS A WALL HUNG LAVATORY
 SINK WITH KNEE AND TOE CLEARANCES IS PROVIDED.
  
 52) A1-306 UNIT C3: SHOW A 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAM OUTSIDE THE ARC
 OF THE IN-SWINGING DOOR- FHA MANUAL 7.40.
  
 53) A1-307 UNITS C4 & C5: SHOW 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAMS OUTSIDE THE
 ARCS OF THE IN-SWINGING DOORS- FHA MANUAL 7.40.
  
 54) A1-307 UNIT C5: SHOW THE MINIMUM REQUIRED
 30X48-INCH CLEAR FLOOR SPACE DIAGRAM FOR A PARALLEL
 APPROACH TO THE BATHTUB- FHA MANUAL 7.53- 7.55, AND FHA
 GUIDELINES FIGURE 8. PLEASE NOTE THAT COMPLIANCE WILL
 NOT BE POSSIBLE UNLESS A WALL HUNG LAVATORY SINK WITH
 KNEE AND TOE CLEARANCES IS PROVIDED.
  
 55) A1-309 & A1-310 UNIT D1 MASTER BATH: SHOW THE
 MINIMUM REQUIRED 30X48-INCH CLEAR FLOOR SPACE DIAGRAM
 FOR A PARALLEL APPROACH TO THE BATHTUB- FHA MANUAL
 7.53- 7.55, AND FHA GUIDELINES FIGURE 8. PLEASE NOTE
 THAT COMPLIANCE WILL NOT BE POSSIBLE BASED ON THE
 LOCATION OF THE WATER CLOSET.
  
 56) A1-311 UNIT D-3: SHOW 30X48-INCH MINIMUM
 UNOBSTRUCTED CLEAR FLOOR SPACE DIAGRAMS OUTSIDE THE
 ARCS OF THE IN-SWINGING DOORS- FHA MANUAL 7.40.
  
 57) PROVIDE PLUMBING FIXTURE GRAB BAR REINFORCMENT
 DETAILS. PROVIDE DRAWINGS THAT INDICATE THE LOCATIONS,
 LENGTHS, MOUNTING HEIGHTS, AND WIDTH OF REINFORCEMENTS
 FOR WATER CLOSETS AND BATHTUBS- SEE FHA MANAUAL PGS 6.1
 - 6.16. PLEASE INDICATE THE TYPE AND THICKNESS OF
 BACKING MATERIAL AND FASTENING DETAILS.
  
 58) P103- P105: THE AD PIPE SHALL NOT PENETRATE INTO
 THE INTERIOR EXIST STAIRWAY- SECTION 1023.5 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected].
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2022-09-15 Cont ID  
Sent By rmcphers Date 2022-09-16 Time 15:40 Rev Time 0.00
Received By rgathrig Date 2022-09-16 Time 15:40 Sent To  
Notes
2022-09-16 15:48:20COMPLETE PRIVATE PROVIDER DOCUMENTS UNDER FOUNDATION
 PERMIT 21091344
  
 RICHARD GATHRIGHT

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2022-08-23 Cont ID  
Sent By jbaker Date 2022-08-23 Time 11:22 Rev Time 0.00
Received By jbaker Date 2022-08-23 Time 11:21 Sent To  
Notes
2022-08-23 11:21:42PRIVATE PROVIDER REVIEW FOR INSPECTIONS ONLY FAILED
  
 THE ONLY DOCUMENT IS THE FILE IS THE NOTICE TO BUILDING
 OFFICIAL. (PLEASE NOTE THAT THESE ARE THE SAME COMMENTS
 AS IN THE FIRST REVIEW?)
  
 1. PROVIDE A CERTIFICATE OF INSURANCE DEMONSTRATING
 THAT PROFESSIONAL LIABILITY INSURANCE COVERAGE IS IN
 PLACE FOR THE PRIVATE PROVIDER?S FIRM, THE PRIVATE
 PROVIDER, AND ANY DULY AUTHORIZED REPRESENTATIVE IN THE
 AMOUNTS REQUIRED BY 553.791
  
 2. PROVIDE THE NAME, AND E-MAIL ADDRESS OF EACH PRIVATE
 PROVIDER WHO IS PERFORMING OR WILL PERFORM SUCH
 SERVICES, HIS OR HER PROFESSIONAL LICENSE OR
 CERTIFICATION NUMBER, QUALIFICATION STATEMENTS OR
 RESUMES
  
  
 JIM BAKER
 ASSISTANT BUILDING OFFICIAL
 561 805 6710
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2022-04-20 Cont ID  
Sent By rgathrig Date 2022-04-20 Time 15:55 Rev Time 0.00
Received By rgathrig Date 2022-04-20 Time 15:55 Sent To  
Notes
2022-04-20 16:01:42PRIVATE PROVIDER REVIEW FOR INSPECTIONS ONLY FAILED
  
 THE ONLY DOCUMENT IN THE FILE IS THE NOTICE TO BUILDING
 OFFICIAL.
  
 1. PLEASE PROVIDE A CERTIFICATE OF INSURANCE
 DEMONSTRATING THAT PROFESSIONAL LIABILITY INSURANCE
 COVERAGE IS IN PLACE FOR THE PRIVATE PROVIDER?S FIRM,
 THE PRIVATE PROVIDER, AND ANY DULY
 AUTHORIZEDREPRESENTATIVE IN THE AMOUNTS REQUIRED BY
 553.791
  
 2. PLEASE PROVIDE THE NAME, AND E-MAIL ADDRESS OF EACH
 PRIVATE PROVIDER WHO IS PERFORMING OR WILL PERFORM SUCH
 SERVICES, HIS OR HER PROFESSIONAL LICENSE OR
 CERTIFICATION NUMBER, QUALIFICATION STATEMENTS OR
 RESUMES,
  
  
 THANK YOU
  
 RICHARD GATHRIGHT
 ASSISTANT BUILDING OFFICIAL
 561 805 6679
  
  
2022-03-30 11:59:00INSPECTIONS ONLY

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status N Date 2022-03-30 Cont ID  
Sent By rmcphers Date 2022-03-30 Time 13:00 Rev Time 0.00
Received By rmcphers Date 2022-03-30 Time 13:00 Sent To  
Notes
2022-03-30 13:00:52ROOFING SYSTEM TO BE DEFERRED

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-12-03 Cont ID  
Sent By rmcphers Date 2021-12-03 Time 09:53 Rev Time 0.00
Received By rmcphers Date 2021-12-03 Time 09:53 Sent To  
Notes
2021-12-03 09:54:17SEE BUILDING PLAN REVIEW

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-09-20 Cont ID  
Sent By medwards Date 2022-09-20 Time 08:59 Rev Time 0.00
Received By medwards Date 2022-09-20 Time 08:59 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By rmcphers Date 2022-09-15 Time 15:52 Rev Time 0.00
Received By rmcphers Date 2022-09-15 Time 15:52 Sent To  
Notes
2022-09-08 09:02:30MECHANICAL DIGITAL SIGNATURES APPROVED ME
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-08-10 Cont ID  
Sent By rmcphers Date 2022-08-10 Time 10:51 Rev Time 0.00
Received By rmcphers Date 2022-08-10 Time 10:51 Sent To  
Notes
2022-07-29 08:56:34MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-30 Cont ID  
Sent By rmcphers Date 2022-03-30 Time 14:02 Rev Time 0.00
Received By rmcphers Date 2022-03-30 Time 14:02 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By ptharpe Date 2021-10-29 Time 07:42 Rev Time 0.00
Received By ptharpe Date 2021-10-29 Time 07:32 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 4 Status P Date 2022-09-15 Cont ID  
Sent By rmcphers Date 2022-09-15 Time 15:06 Rev Time 0.00
Received By rmcphers Date 2022-09-15 Time 15:06 Sent To  
Notes
***NONE***

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 3 Status F Date 2022-08-10 Cont ID  
Sent By rmcphers Date 2022-08-10 Time 10:30 Rev Time 0.00
Received By rmcphers Date 2022-08-10 Time 10:30 Sent To  
Notes
2022-08-10 10:31:09THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 2 Status F Date 2022-03-30 Cont ID  
Sent By rmcphers Date 2022-03-30 Time 13:05 Rev Time 0.00
Received By rmcphers Date 2022-03-30 Time 13:02 Sent To  
Notes
2022-03-30 13:05:16THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop THRESHOLD THRESHOLD INSPECTOR DOCUMENTS
Rev No 1 Status F Date 2021-12-03 Cont ID  
Sent By rmcphers Date 2021-12-03 Time 09:55 Rev Time 0.00
Received By rmcphers Date 2021-12-03 Time 09:55 Sent To  
Notes
2021-12-03 09:58:26THRESHOLD BUILDING
  
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 NOTE: THIS STRUCTURE IS CONSIDERED A THRESHOLD BUILDING
 PER FS 553.71 12) "THRESHOLD BUILDING" MEANS ANY
 BUILDING WHICH IS GREATER THAN THREE STORIES OR 50 FEET
 IN HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPANCY
 CLASSIFICATION AS DEFINED IN THE FLORIDA BUILDING CODE
 WHICH EXCEEDS 5,000 SQUARE FEET IN AREA AND AN OCCUPANT
 CONTENT OF GREATER THAN 500 PERSONS.
  
 PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE
 "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING
 THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS".
 YOU CAN E MAIL ME AND ASK FOR A COPY.
  
 A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION
 PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5)
 FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY
 THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED
 TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED
 AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED
 BEFORE PERMIT ISSUANCE WILL TAKE PLACE.
  
 C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT
 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED
 TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF
 RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF
 THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND
 SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM
 BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS
 AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH
 THIS SECTION AND CHAPTER 633 FLORIDA STATUTES.
  
 D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF
 INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME
 MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED
 HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL
 REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN
 INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR HISTORY
 FOR THIS TYPE OF CONSTRUCTION.
  
 F) 110.8.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  

Review Stop Z ZONING
Rev No 4 Status P Date 2022-09-16 Cont ID  
Sent By eschneid Date 2022-09-16 Time 11:46 Rev Time 0.00
Received By eschneid Date 2022-09-16 Time 11:46 Sent To  
Notes
2022-09-16 11:47:59PER ANA MARIA APONTE
  
 PROVISO:
 1. SOUTH ELEVATION REVEALS AND PROJECTIONS TO COMPLY
 WITH FA??ADE ARTICULATION SHALL HAVE A MINIMUM
 PROJECTION OF 4 INCHES.
 2. STREET LIGHT POLES AND FIXTURES ALONG CLEARWATER
 DRIVE SHALL MATCH DOWNTOWN STANDARD. POLES SHALL BE A
 MAXIMUM 13 FEET IN HEIGHT. PLEASE FOLLOW PROVIDED SPECS
 FOR MANUFACTURER AND SPECS. SPEC PROVIDED IN SHEET
 LD-207 DOES NOT MATCH DOWNTOWN STANDARD.
  
  

Review Stop Z ZONING
Rev No 3 Status F Date 2022-08-05 Cont ID  
Sent By aaponte Date 2022-08-05 Time 13:56 Rev Time 0.00
Received By aaponte Date 2022-08-05 Time 12:40 Sent To  
Notes
2022-08-05 13:56:101. SATISFIED- PLEASE INCLUDE A TABLE WITH ALL THE
 PROJECT DATA (UPDATED SHEET A.001 IN SITE PLAN SET) -
 PLEASE PROVIDE A COMPLETE SITE PLAN INDICATING THE
 MINIMUM SETBACKS, SIDEWALK WIDTH, PLANNING AREAS, TREE
 LOCATIONS, BIKE RACKS AND BENCHES.
 2. SATISFIED. PLEASE EXPLAIN THE DIFFERENCE IN GBA
 BETWEEN THE APPROVED 424,004 SF IN THE SITE PLAN
 DOCUMENTS AND THE 368,240 SF LISTED IN THE BUILDING
 PERMIT SET.
 3. SATISFIED -PLEASE ADJUST THE SETBACK TABLE IN SHEET
 A0-002 AS IT LISTS A SIDE SETBACK OF 157?.
 4. SATISFIER - FULLY ENCLOSED STORAGE ON THE GROUND
 FLOOR COUNTS AS PART OF THE GBA.
 5. SATISFIED- PLEASE EXPLAIN THE PUBLIC OPEN SPACE
 DIAGRAM IN SHEET A0-005. IT DOES NOT MATCH APPROVED
 SITE PLAN.
 6. SATISFIED - PLEASE PROVIDE A FA?ADE DIAGRAM TO
 CONFIRM COMPLIANCE WITH TRANSPARENCY REQUIREMENT AS
 MEASURED ACCORDING TO SEC 94-109 OF THE ZLDRS.
 7. SATISFIED - A TURN AROUND SPACE SHALL BE PROVIDED
 FOR THE GROUND FLOOR DEAD END PARKING.
 8. SATISFIED - SOME OF THE PARKING SPACES HAVE COLUMNS
 THAT OBSTRUCT THE OPENING OF THE CAR DOOR. PLEASE
 ADJUST STALL DIMENSION ACCORDING TO SEC 94-110 (C). -
 PARKING STALLS WITH A COLUMN OR WALL LOCATED NEXT TO
 DOOR OPENING AREA SHALL BE WIDENED BY 1 FOOT.
 9. SATISFIED- ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE
 CONSOLIDATED/GROUP AS MUCH AS POSSIBLE AND SCREENED
 WITH A SCREEN AS TALL AS THE EQUIPMENT MAKING IT AN
 INTEGRAL PART OF THE OVERALL BUILDING DESIGN.
 10. NOT SATISFIED ? IF TREATMENT FROM SITE PLAN CANNOT
 BE ACHIEVED, FURTHER DISCUSSIONS ARE NEEDED TO ENHANCE
 THE FA?ADE. AN OPTION IS TO MAINTAIN THE PATTERN BUT
 WILL NO OPENINGS. - SOUTH ELEVATION DOES NOT SEEM TO
 MATCH APPROVED SITE PLAN ELEVATION WITHIN THE PARKING
 GARAGE AREA. PLEASE ADJUST.
 11. SATISFIED - PLEASE EXPLAIN THE REASON WHY THE TOP
 LEVEL OF THE PARKING GARAGE IS NOW A 12? FINISHED FLOOR
 TO FINISHED FLOOR. AMENITY DECK HEIGHT WAS REDUCED FROM
 14? TO 12? AND THAT SEEMS TO AFFECT THE PROPORTIONS AND
 SEPARATION OF BASE AND TOWER.
 12. SATISFIED. PLEASE STUDY MAINTAINING A WINDOW
 SIMILAR TO APPROVED SITE PLAN. - GROUND FLOOR WINDOW OF
 SOUTH END RESIDENTIAL UNIT HAS BEEN CHANGED FROM
 APPROVED. PLEASE ADJUST.
 13. SATISFIED - SITE PLAN APPROVAL INCLUDED AN EYE
 BROS-CANOPY TURNING THE CORNER FROM NORTH FA?ADE TO
 EAST AT THE RETAIL LEVEL. PLEASE JUSTIFY WHY IT WAS
 REMOVED.
 14. SATISFIED- LOADING ENTRANCE ALONG CLEARWATER DRIVE
 SHALL INCLUDE AN OPAQUE DECORATIVE GATE.
 15. LANDSCAPE DRAWINGS SHALL BE REMOVED FROM THIS
 PERMIT AND SUBMITTED UNDER A SEPARATE LANDSCAPE PERMIT.
 16. SATISFIED - PLEASE INDICATE THE LOCATION OF THE
 MICROMOBILITY STATION.
 17. SATISFIED ? PLEASE ADD A NOTE IN CIVIL DRAWINGS
 STATING THAT THE SIDEWALK ELEVATION SHALL BE MAINTAINED
 ACROSS THE DRIVEWAY .- SIDEWALK ELEVATION SHALL BE
 MAINTAINED ACROSS DRIVEWAY. PLEASE PROVIDE SECTIONS OR
 DETAILS TO CONFIRM COMPLIANCE.
 18. SATISFIED - PLEASE PROVIDE CROSS SECTION OF THE
 SIDEWALK LEVEL TO CONFIRM GRADES ARE MET.
 19. PARTIALLY SATISFIED - CLEARLY INDICATE THE
 BOUNDARIES OF THE REQUIRED PUBLIC OPEN SPACE AREA.-
 PLEASE PROVIDE OPEN SPACE DIAGRAM TO MATCH APPROVED
 SITE PLAN.
 20. PARTIALLY SATISFIED. PLEASE INCLUDE LOCATIONS AND
 SPECS OF FIXTURES AND POLES ALONG CLEARWATER DRIVE TO
 CONFIRM COMPLIANCE WITH THE MINIMUM 0.6 FOOTCANDLE
 REQUIRED. SPEC FOR FIXTURE AND POLE SHALL COMPLY WITH
 CITY STANDARD. -PLEASE PROVIDE PHOTOMETRICS FOR THE
 GROUND FLOOR PUBLIC REALM AND CONFIRM COMPLIANCE WITH
 THE REQUIRED CITY STANDARD LIGHT FIXTURE.
 ADDITIONAL COMMENTS:
 21. NOT SATISFIED-SOUTH ELEVATION DOES NOT MATCH
 APPROVED DESIGN FOR THE GARAGE SCREENING. PLEASE ADJUST
 OR JUSTIFY CHANGES.
 22. SATISFIED- SOUTH WINDOW FOR THE CORNER UNIT WAS
 REMOVED CHANGING APPROVED SITE PLAN. PLEASE ADJUST OR
 JUSTIFY CHANGE.
 23. SATISFIED - BIKE RACKS ON NORTH SIDE OF LOBBY NEED
 TO BE REPOSITION. AS PROPOSED, SOME OF THE SPACES ARE
 NOT ACCESSIBLE.
 24. SATISFIED- PLEASE CLEARLY INDICATE WHICH PORTIONS
 OF THE GARAGE FA?ADE ARE OPEN.
 25. PARTIALLY SATISFIED - PLEASE CORRECT ADA STALL
 PAINTING DETAIL IN SHEET A6-401. NEEDS TO MATCH CITY
 STANDARD IN SECT 94-485 FOR LINE PAINTING WITH THE ADA
 DIMENSIONS.- PARKING STALL PAINTING DETAIL SHALL FOLLOW
 CITY STANDARD (SEC 94-485) PLEASE REVISE DETAIL IN
 SHEET A6-401.
 ADDITIONAL COMMENTS:
 26. SHEET A1-101 IDENTIFIES THE MICROMOBILITY STATION
 IS THE WRONG LOCATION (NW CORNER OF BUILDING) PLEASE
 REMOVE NOT TO AVOID CONFUSION.
  
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439

Review Stop Z ZONING
Rev No 2 Status F Date 2022-04-15 Cont ID  
Sent By aaponte Date 2022-04-15 Time 15:23 Rev Time 0.00
Received By aaponte Date 2022-04-15 Time 15:23 Sent To  
Notes
2022-04-15 15:23:591. PARTIALLY SATISFIED- PLEASE INCLUDE A TABLE WITH ALL
 THE PROJECT DATA (UPDATED SHEET A.001 IN SITE PLAN SET)
 - PLEASE PROVIDE A COMPLETE SITE PLAN INDICATING THE
 MINIMUM SETBACKS, SIDEWALK WIDTH, PLANNING AREAS, TREE
 LOCATIONS, BIKE RACKS AND BENCHES.
 2. PLEASE EXPLAIN THE DIFFERENCE IN GBA BETWEEN THE
 APPROVED 424,004 SF IN THE SITE PLAN DOCUMENTS AND THE
 368,240 SF LISTED IN THE BUILDING PERMIT SET.
 3. SATISFIED -PLEASE ADJUST THE SETBACK TABLE IN SHEET
 A0-002 AS IT LISTS A SIDE SETBACK OF 157?.
 4. SATISFIER - FULLY ENCLOSED STORAGE ON THE GROUND
 FLOOR COUNTS AS PART OF THE GBA.
 5. SATISFIED- PLEASE EXPLAIN THE PUBLIC OPEN SPACE
 DIAGRAM IN SHEET A0-005. IT DOES NOT MATCH APPROVED
 SITE PLAN.
 6. SATISFIER - PLEASE PROVIDE A FA?ADE DIAGRAM TO
 CONFIRM COMPLIANCE WITH TRANSPARENCY REQUIREMENT AS
 MEASURED ACCORDING TO SEC 94-109 OF THE ZLDRS.
 7. NOT SATISFIED - A TURN AROUND SPACE SHALL BE
 PROVIDED FOR THE GROUND FLOOR DEAD END PARKING.
 8. NOT SATISFIED - SOME OF THE PARKING SPACES HAVE
 COLUMNS THAT OBSTRUCT THE OPENING OF THE CAR DOOR.
 PLEASE ADJUST STALL DIMENSION ACCORDING TO SEC 94-110
 (C). - PARKING STALLS WITH A COLUMN OR WALL LOCATED
 NEXT TO DOOR OPENING AREA SHALL BE WIDENED BY 1 FOOT.
 9. SATISFIED- ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE
 CONSOLIDATED/GROUP AS MUCH AS POSSIBLE AND SCREENED
 WITH A SCREEN AS TALL AS THE EQUIPMENT MAKING IT AN
 INTEGRAL PART OF THE OVERALL BUILDING DESIGN.
 10. NOT SATISFIED ? IF TREATMENT FROM SITE PLAN CANNOT
 BE ACHIEVED, FURTHER DISCUSSIONS ARE NEEDED TO ENHANCE
 THE FA?ADE. AN OPTION IS TO MAINTAIN THE PATTERN BUT
 WILL NO OPENINGS. - SOUTH ELEVATION DOES NOT SEEM TO
 MATCH APPROVED SITE PLAN ELEVATION WITHIN THE PARKING
 GARAGE AREA. PLEASE ADJUST.
 11. SATISFIED - PLEASE EXPLAIN THE REASON WHY THE TOP
 LEVEL OF THE PARKING GARAGE IS NOW A 12? FINISHED FLOOR
 TO FINISHED FLOOR. AMENITY DECK HEIGHT WAS REDUCED FROM
 14? TO 12? AND THAT SEEMS TO AFFECT THE PROPORTIONS AND
 SEPARATION OF BASE AND TOWER.
 12. NOT SATISFIED. PLEASE STUDY MAINTAINING A WINDOW
 SIMILAR TO APPROVED SITE PLAN. - GROUND FLOOR WINDOW OF
 SOUTH END RESIDENTIAL UNIT HAS BEEN CHANGED FROM
 APPROVED. PLEASE ADJUST.
 13. SATISFIED - SITE PLAN APPROVAL INCLUDED AN EYE
 BROS-CANOPY TURNING THE CORNER FROM NORTH FA?ADE TO
 EAST AT THE RETAIL LEVEL. PLEASE JUSTIFY WHY IT WAS
 REMOVED.
 14. NOT SATISFIED- LOADING ENTRANCE ALONG CLEARWATER
 DRIVE SHALL INCLUDE AN OPAQUE DECORATIVE GATE.
 15. LANDSCAPE DRAWINGS SHALL BE REMOVED FROM THIS
 PERMIT AND SUBMITTED UNDER A SEPARATE LANDSCAPE PERMIT.
 16. SATISFIED - PLEASE INDICATE THE LOCATION OF THE
 MICROMOBILITY STATION.
 17. PARTIALLY SATISFIED ? PLEASE ADD A NOTE IN CIVIL
 DRAWINGS STATING THAT THE SIDEWALK ELEVATION SHALL BE
 MAINTAINED ACROSS THE DRIVEWAY .- SIDEWALK ELEVATION
 SHALL BE MAINTAINED ACROSS DRIVEWAY. PLEASE PROVIDE
 SECTIONS OR DETAILS TO CONFIRM COMPLIANCE.
 18. PARTIALLY SATISFIED - PLEASE PROVIDE CROSS SECTION
 OF THE SIDEWALK LEVEL TO CONFIRM GRADES ARE MET.
 19. PLEASE PROVIDE OPEN SPACE DIAGRAM TO MATCH APPROVED
 SITE PLAN.
 20. NOT SATISFIED. PLEASE INCLUDE LOCATIONS AND SPECS
 OF FIXTURES AND POLES ALONG CLEARWATER DRIVE TO CONFIRM
 COMPLIANCE WITH THE MINIMUM 0.6 FOOTCANDLE REQUIRED.
 SPEC FOR FIXTURE AND POLE SHALL COMPLY WITH CITY
 STANDARD. -PLEASE PROVIDE PHOTOMETRICS FOR THE GROUND
 FLOOR PUBLIC REALM AND CONFIRM COMPLIANCE WITH THE
 REQUIRED CITY STANDARD LIGHT FIXTURE.
 ADDITIONAL COMMENTS:
 21. SOUTH ELEVATION DOES NOT MATCH APPROVED DESIGN FOR
 THE GARAGE SCREENING. PLEASE ADJUST OR JUSTIFY CHANGES.
 22. SOUTH WINDOW FOR THE CORNER UNIT WAS REMOVED
 CHANGING APPROVED SITE PLAN. PLEASE ADJUST OR JUSTIFY
 CHANGE.
 23. BIKE RACKS ON NORTH SIDE OF LOBBY NEED TO BE
 REPOSITION. AS PROPOSED, SOME OF THE SPACES ARE NOT
 ACCESSIBLE.
 24. PLEASE CLEARLY INDICATE WHICH PORTIONS OF THE
 GARAGE FA?ADE ARE OPEN.
 25. PARKING STALL PAINTING DETAIL SHALL FOLLOW CITY
 STANDARD (SEC 94-485) PLEASE REVISE DETAIL IN SHEET
 A6-401.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-21 Cont ID  
Sent By aaponte Date 2021-12-21 Time 17:07 Rev Time 0.00
Received By aaponte Date 2021-12-21 Time 15:29 Sent To  
Notes
2021-12-21 17:07:361. PLEASE PROVIDE A COMPLETE SITE PLAN INDICATING THE
 MINIMUM SETBACKS, SIDEWALK WIDTH, PLANNING AREAS, TREE
 LOCATIONS, BIKE RACKS AND BENCHES.
 2. PLEASE EXPLAIN THE DIFFERENCE IN GBA BETWEEN THE
 APPROVED 424,004 SF IN THE SITE PLAN DOCUMENTS AND THE
 368,240 SF LISTED IN THE BUILDING PERMIT SET.
 3. PLEASE ADJUST THE SETBACK TABLE IN SHEET A0-002 AS
 IT LISTS A SIDE SETBACK OF 157?.
 4. FULLY ENCLOSED STORAGE ON THE GROUND FLOOR COUNTS AS
 PART OF THE GBA.
 5. PLEASE EXPLAIN THE PUBLIC OPEN SPACE DIAGRAM IN
 SHEET A0-005. IT DOES NOT MATCH APPROVED SITE PLAN.
 6. PLEASE PROVIDE A FA?ADE DIAGRAM TO CONFIRM
 COMPLIANCE WITH TRANSPARENCY REQUIREMENT AS MEASURED
 ACCORDING TO SEC 94-109 OF THE ZLDRS.
 7. A TURN AROUND SPACE SHALL BE PROVIDED FOR THE GROUND
 FLOOR DEAD END PARKING.
 8. PARKING STALLS WITH A COLUMN OR WALL LOCATED NEXT TO
 DOOR OPENING AREA SHALL BE WIDENED BY 1 FOOT.
 9. ALL MECHANICAL EQUIPMENT ON ROOF SHALL BE
 CONSOLIDATED/GROUP AS MUCH AS POSSIBLE AND SCREENED
 WITH A SCREEN AS TALL AS THE EQUIPMENT MAKING IT AN
 INTEGRAL PART OF THE OVERALL BUILDING DESIGN.
 10. SOUTH ELEVATION DOES NOT SEEM TO MATCH APPROVED
 SITE PLAN ELEVATION WITHIN THE PARKING GARAGE AREA.
 PLEASE ADJUST.
 11. PLEASE EXPLAIN THE REASON WHY THE TOP LEVEL OF THE
 PARKING GARAGE IS NOW A 12? FINISHED FLOOR TO FINISHED
 FLOOR. AMENITY DECK HEIGHT WAS REDUCED FROM 14? TO 12?
 AND THAT SEEMS TO AFFECT THE PROPORTIONS AND SEPARATION
 OF BASE AND TOWER.
 12. GROUND FLOOR WINDOW OF SOUTH END RESIDENTIAL UNIT
 HAS BEEN CHANGED FROM APPROVED. PLEASE ADJUST.
 13. SITE PLAN APPROVAL INCLUDED AN EYE BROS-CANOPY
 TURNING THE CORNER FROM NORTH FA?ADE TO EAST AT THE
 RETAIL LEVEL. PLEASE JUSTIFY WHY IT WAS REMOVED.
 14. LOADING ENTRANCE ALONG CLEARWATER DRIVE SHALL
 INCLUDE AN OPAQUE DECORATIVE GATE.
 15. LANDSCAPE DRAWINGS SHALL BE REMOVED FROM THIS
 PERMIT AND SUBMITTED UNDER A SEPARATE LANDSCAPE PERMIT.
 16. PLEASE INDICATE THE LOCATION OF THE MICROMOBILITY
 STATION.
 17. SIDEWALK ELEVATION SHALL BE MAINTAINED ACROSS
 DRIVEWAY. PLEASE PROVIDE SECTIONS OR DETAILS TO CONFIRM
 COMPLIANCE.
 18. PLEASE PROVIDE CROSS SECTION OF THE SIDEWALK LEVEL
 TO CONFIRM GRADES ARE MET.
 19. PLEASE PROVIDE OPEN SPACE DIAGRAM TO MATCH APPROVED
 SITE PLAN.
 20. PLEASE PROVIDE PHOTOMETRICS FOR THE GROUND FLOOR
 PUBLIC REALM AND CONFIRM COMPLIANCE WITH THE REQUIRED
 CITY STANDARD LIGHT FIXTURE.
 FOR ADDITIONAL INFORMATION PLEASE CONTACT ANA MARIA
 APONTE AT 561-822-1439
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved