Plan Review Details - Permit 21091319
Plan Review Stops For Permit 21091319
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By fgiaquin Date 2022-05-04 Time 19:41 Rev Time 0.00
Received By fgiaquin Date 2022-05-04 Time 18:37 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:22 Rev Time 0.00
Received By fgiaquin Date 2021-12-08 Time 11:19 Sent To  
Notes
2021-12-08 11:22:29ELECTRICAL REVIEW STATUS DENIED. SEE COMMENTS BELOW.
  
  
  
 I FAILED FOR SIGNATURE THE PLAN E-1 DRAWN BY AN
 ENGINEER WITH NO S+S 12/1/21
  
 PLAN E-1 DOES NOT HAVE SYMBOL LEGEND. FBC 107.2.1
  
 PLAN DOES NOT INDICATE WHAT IS EXISTING OR NEW? FBC
 107.2.1
  
 IS THERE A NEW SUB PANEL? FBC 107.2.1
  
 WHERE IS THE MAIN PANEL LOCATED? FBC 107.2.1
  
 IS THE BOAT LIFT EXISTING? WAS THIS A PERMITTED
 INSTALLATION? FBC 107.2.1 FBC 105.1
  
 WHICH CIRCUITS ARE GFI PROTECTED? FBC 107.2.1
  
 WHAT IS THE LOAD ON THE 200-AMP PANEL? WHERE IS THIS
 PANEL LOCATED? THE HOUSE IS LOCATED ON THE WEST SIDE OF
 FLAGLER AND DOCK ON THE OTHER SIDE OF THE ROAD. FBC
 107.2.1 NEC 215 220
  
 WHAT WIRING METHODS ARE USED? FBC 107.2.1 NEC 300
  
 ARE THERE LED STRIP LIGHTS BEING INSTALLED? FBC 107.2.1
  
 WHAT ARE THE SPECIFICATIONS OF THE STRIP LIGHTS? FBC
 107.2.1 NEC 110.3B
  
 HAND DRAWN PLAN IS NOT CLEARLY UNDERSTANDABLE. PROVIDE
 CLEAR AND CONCISE PLAN.
  
 VALUE LOW FOR AMOUNT OF WORK SHOWN FBC 109.3 PROVIDE
 ACCURATE VALUE AND CONTRACT SIGNED BY BOTH OWNER AND
 ELECTRICAL CONTRACTOR QUALIFIER.
  
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPT.
 561-805-6746
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-04 Cont ID  
Sent By fgiaquin Date 2022-05-04 Time 19:41 Rev Time 0.00
Received By fgiaquin Date 2022-04-15 Time 07:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-12-27 Cont ID  
Sent By fgiaquin Date 2021-12-27 Time 14:41 Rev Time 0.00
Received By aoliver Date 2021-12-09 Time 09:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-04 Cont ID  
Sent By fgiaquin Date 2022-05-04 Time 19:41 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By mpeterso Date 2021-12-01 Time 09:55 Rev Time 0.00
Received By mpeterso Date 2021-12-01 Time 09:55 Sent To  
Notes
2021-12-01 10:00:13SIGNATURE REVIEW FAILED
 DRAWING CREATED BY P.E. DAVID WOJCIESZAK DOES NOT
 CONTAIN A SEAL AND SIGNATURE AS REQUIRED.
  
 FS471/FS481 DOCUMENTS PREPARED BY AN ARCHITECT OR
 ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED, SEALED, DATED ORIGINALS OR DIGITALLY SEALED AND
 SIGNED.
 PLEASE CORRECT THESE ISSUES BY PROPERLY SIGNING AND
 SEALING THEM AS DESCRIBED BELOW.
  
 EITHER UPLOAD A DIGITALLY OR ELECTRONICALLY SIGNED PLAN
 TO THE SIGNATURE FOLDER WITH YOUR RESUBMITTAL (IF
 APPLICABLE) AND COMPLETE THE UPLOAD TASK IN PROJECTDOX,
 OR YOU CAN SUBMIT ONE ORIGINAL SIGNED AND SEALED PAPER
 ORIGINAL WITH A WET SIGNATURE TO THE BUILDING DIVISION.
 SIGNATURE DOCUMENTS ARE TYPICALLY REVIEWED WITHIN TWO
 BUSINESS DAYS AFTER SUBMITTAL; DIGITALLY SIGNED
 DOCUMENTS ARE PREFERRED.
  
 PLEASE EMAIL [email protected] AND CC TO
 [email protected]
  
 MICHAEL PETERSON
  
 [email protected]
 561-805-6746
  
  
  

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-22 Cont ID  
Sent By llouie Date 2022-04-22 Time   Rev Time 0.00
Received By llouie Date 2022-04-22 Time   Sent To  
Notes
2022-04-22 10:35:52ARTIFICIAL LIGHTING MAY BE INSTALLED ON A DOCK FOR
 SECURITY OR SAFETY REASONS BUT SHALL NOT LIGHT
 SURROUNDING PROPERTIES. BLINKING OR INTERMITTENT LIGHTS
 ARE PROHIBITED. [ZLDR S.94-313(P)]
  
 * NOTED IN PLANS.
  
 * SCOPE OF PERMIT IS FOR THE INSTALLATION OF LIGHTING
 ON EXISTING DOCK ONLY.

Review Stop Z ZONING
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By llouie Date 2021-12-27 Time   Rev Time 0.00
Received By llouie Date 2021-12-27 Time   Sent To  
Notes
2021-12-27 12:13:16** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) IT IS NOT CLEAR IN THE PLANS TO WHERE THE LIGHT
 FIXTURES FOR THE DOCK WILL BE SPECIFICALLY PLACED.
 PLEASE NOTE THAT PER SEC. 94-313.P. OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), PLEASEE SHOW
 SPECIFIC LIGHT FIXTURE PLACEMENT. ALSO "ARTIFICIAL
 LIGHTING MAY BE INSTALLED ON A DOCK FOR SECURITY OR
 SAFETY REASONS BUT SHALL NOT LIGHT SURROUNDING
 PROPERTIES. BLINKING OR INTERMITTENT LIGHTS ARE
 PROHIBITED." A NOTE IN THE SITE PLAN SHALL BE PROVIDED
 IN THE PLANS TO DEMONSTRATE COMPLIANCE WITH THE ZLDRS.
  
  
  
 NOTES:
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  