Plan Review Details - Permit 21091316
Plan Review Stops For Permit 21091316
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2022-03-30 Cont ID  
Sent By cthroop Date 2022-03-30 Time 13:45 Rev Time 0.00
Received By cthroop Date 2022-03-30 Time 12:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2022-03-26 Cont ID  
Sent By shill Date 2022-03-26 Time 13:35 Rev Time 0.00
Received By shill Date 2022-03-26 Time 13:35 Sent To  
Notes
2022-03-26 13:36:51****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 A NEW FLOOR PLAN WAS NOT SUBMITTED. THEREFORE PREVIOUS
 COMMENT NOT ADDRESSED:
  
 1. FBC 107, FBC EB 702.4, REVISE PLAN TO PROVIDE THE
 FOLLOWING INFORMATION:
  
 TYPE OF WINDOW CURRENTLY IN THE OPENING (FOR EGRESS
 WINDOWS)
 TYPE OF WINDOW PROPOSED (FOR ALL WINDOWS)
  
 SINGLE HUNG AND HORIZONTAL ROLLER WINDOW PRODUCT
 APPROVALS WERE SUBMITTED. IT IS NOT CLEAR WHERE THEY
 ARE PROPOSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-03-05 Cont ID  
Sent By shill Date 2022-03-05 Time 12:27 Rev Time 0.00
Received By shill Date 2022-03-05 Time 12:27 Sent To  
Notes
2022-03-05 12:29:10****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, FBC EB 702.4, REVISE PLAN TO PROVIDE THE
 FOLLOWING INFORMATION:
  
 TYPE OF WINDOW CURRENTLY IN THE OPENING (FOR EGRESS
 WINDOWS)
 TYPE OF WINDOW PROPOSED (FOR ALL WINDOWS)
  
 SINGLE HUNG AND HORIZONTAL ROLLER WINDOW PRODUCT
 APPROVALS WERE SUBMITTED. IT IS NOT CLEAR WHERE THEY
 ARE PROPOSED.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-01-24 Cont ID  
Sent By jgomez Date 2022-01-24 Time 15:47 Rev Time 0.00
Received By jgomez Date 2022-01-24 Time 14:44 Sent To  
Notes
2022-01-24 15:49:08RESIDENTIAL(R3) ALTERATION, SECOND BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #21091316
  
 NOTE:
 LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING.
 SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL
 COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN
 THE FLORIDA BUILDING CODE.
  
 COPY OF ORIGINAL COMMENT FROM PREVIOUS PLAN EXAMINER:
 1. FBC 107, FBC EB 702.4, REVISE PLAN TO PROVIDE THE
 FOLLOWING INFORMATION:
 ROOM DESIGNATION (FOR INSTANCE, BEDROOM, KITCHEN, ETC.)
 TYPE OF WINDOW CURRENTLY IN THE OPENING
 TYPE OF WINDOW PROPOSED
  
 RESPONSE:
 REPEAT COMMENT. REVISED PLAN DOESN'T PROVIDE THE
 REQUIRED INFORMATION:
  
 WINDOW REPLACEMENT
 A)PROVIDE FLOOR PLAN OR SKETCH IDENTIFYING THE ROOMS
 WHERE WINDOWS ARE GOING TO BE REPLACED. FOR EXAMPLE:
 BEDROOM, LIVING AREA, ETC. THIS IS REQUIRED TO IDENTIFY
 THE BEDROOMS AND VERIFY COMPLIANCE WITH THE EGRESS
 REQUIREMENTS. SEE COMMENT #2 BELOW. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 B)SPECIFY SIZE AND TYPE OF EXISTING WINDOW AND SIZE AND
 TYPE OF PROPOSED WINDOWS TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 ADDITIONAL COMMENT TO BE CONSIDERED:
 2-SECOND FLOOR WINDOW OPENING CONTROL DEVICES: WINDOW
 OPENING CONTROL DEVICES IN WINDOW REPLACEMENT ARE
 REQUIRED WHEN THE TOP SILL OF THE WINDOW OPENING IS AT
 A HEIGHT LESS THAN 24 INCHES (610 MM) ABOVE THE
 FINISHED FLOOR.
 WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM
 F2090.
 CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE
 WINDOW SILL IS LESS THAN 24" ABOVE THE FINISH FLOOR.
 SEE SEC. 702.4 FBC-EXISTING BUILDING CODE.
 NOTE: THIS SECTION ALSO APPLIES TO OPERABLE WINDOWS
 WHERE WINDOW SILL IS GREATER THAN 72 INCHES ABOVE GRADE
 OR OTHER SURFACE BELOW.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 10:50 Rev Time 0.00
Received By shill Date 2021-10-10 Time 10:50 Sent To  
Notes
2021-10-10 10:55:56****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. FBC 107, FBC EB 702.4, REVISE PLAN TO PROVIDE THE
 FOLLOWING INFORMATION:
  
 ROOM DESIGNATION (FOR INSTANCE, BEDROOM, KITCHEN, ETC.)
 TYPE OF WINDOW CURRENTLY IN THE OPENING
 TYPE OF WINDOW PROPOSED
  
  

Review Stop HIST HISTORICAL
Rev No 4 Status P Date 2022-03-15 Cont ID  
Sent By amhamilt Date 2022-03-15 Time 11:32 Rev Time 0.00
Received By amhamilt Date 2022-03-15 Time 11:32 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 3 Status F Date 2022-03-07 Cont ID  
Sent By amhamilt Date 2022-03-07 Time 13:08 Rev Time 0.00
Received By amhamilt Date 2022-03-07 Time 13:08 Sent To  
Notes
2022-03-07 13:10:14THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PLEASE UPDATE CONTRACT TO SPECIFY THAT DIMENSIONAL
 GRIDS WILL BE ADDED TO THE WINDOWS TO MATCH EXISTING
 LITE PATTERN. PLEASE ALSO SEE BUILDING'S COMMENTS
 REGARDING HR WINDOW. ONLY WINDOWS TO MATCH EXISTING IN
 STYLE AND GRID PATTERN WAS APPROVED BY HPB
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 2 Status F Date 2022-01-06 Cont ID  
Sent By amhamilt Date 2022-01-06 Time 14:56 Rev Time 0.00
Received By amhamilt Date 2022-01-06 Time 14:56 Sent To  
Notes
2022-01-06 14:57:43THE PERMIT HAS FAILED FOR THE FOLLOWING REASON(S)
  
 PER HPB DECISION,"ALL LITES SHALL HAVE AN EXTERNAL
 DIMENSIONAL MUNTIN MATCHING THE EXISTING WINDOWS" 6
 OVER 1 STYLE GRIDS. REVISED CONTRACT INDICATES NO
 GRIDS, PLEASE REVISE.
  
 ANNE HAMILTON
 HISTORIC PRESERVATION PLANNER
 [email protected]
 561.822.1428

Review Stop HIST HISTORICAL
Rev No 1 Status F Date 2021-10-15 Cont ID  
Sent By fmittner Date 2021-10-15 Time 15:08 Rev Time 0.00
Received By fmittner Date 2021-10-15 Time 15:08 Sent To  
Notes
2021-10-15 15:10:06ORIGINAL WOOD WINDOWS, PROPERTY IS IN HISTORIC
 DISTRICT. STREET FACING TO BE PRESERVED. QUESTIONS,
 CONTACT:
  
 FRIEDERIKE MITTNER, CITY HISTORIC PRESERVATION PLANNER
 (561) 822-1457
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-03-30 Cont ID  
Sent By cthroop Date 2022-03-30 Time 13:45 Rev Time 0.00
Received By cthroop Date 2022-03-30 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-03-26 Cont ID  
Sent By shill Date 2022-03-26 Time 13:36 Rev Time 0.00
Received By shill Date 2022-03-09 Time 08:20 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-03-08 Cont ID  
Sent By aoliver Date 2022-03-08 Time 10:12 Rev Time 0.00
Received By aoliver Date 2022-02-22 Time 06:53 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-24 Cont ID  
Sent By jgomez Date 2022-01-24 Time 15:49 Rev Time 0.00
Received By jgomez Date 2021-12-27 Time 08:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-18 Cont ID  
Sent By lmarchan Date 2021-10-18 Time 11:07 Rev Time 0.00
Received By lmarchan Date 2021-09-30 Time 06:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 10:56 Rev Time 0.00
Received By shill Date 2021-10-10 Time 10:56 Sent To  
Notes
***NONE***