Plan Review Details - Permit 21091315
Plan Review Stops For Permit 21091315
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-09-28 Cont ID  
Sent By cpuell Date 2021-09-28 Time 16:27 Rev Time 0.00
Received By cpuell Date 2021-09-28 Time 16:27 Sent To  
Notes
2021-09-28 16:28:19SUITE IS CORRECT

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status N Date 2021-10-20 Cont ID  
Sent By rmcdouga Date 2021-10-20 Time 17:23 Rev Time 0.00
Received By rmcdouga Date 2021-10-20 Time 17:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-12-23 Cont ID  
Sent By rmcdouga Date 2021-12-23 Time 08:55 Rev Time 0.00
Received By rmcdouga Date 2021-12-23 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-21 Cont ID  
Sent By rmcdouga Date 2021-10-21 Time 11:15 Rev Time 0.00
Received By rmcdouga Date 2021-10-20 Time 17:22 Sent To  
Notes
2021-10-21 11:02:12PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE BATHROOM DOORS AS SHOWN ON THE FLOOR PLAN DO NOT
 COMPLY WITH FBC ACCESSIBILITY 603.2.3 EXCEPTION 2. THE
 ARC OF THE DOOR SWING DOES NOT CLEAR OF THE 30" X 48"
 CLEAR FLOOR SPACE REQUIRED BY SECTION 305.3.
  
 2) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION DETAILS FOR THE TEKNION OPTOS FURNITURE
 SYSTEM. FBC 107.2.1
  
 3) SUBMIT DETAILS FOR THE TEKNION OPTOS SLIDING DOORS
 THAT SHOW THEY WILL COMPLY WITH FBC ACCESSIBILITY 404.
  
 4) ON SHEET A1.1, THERE IS AN ID TAG FOR NOTE #8. IT
 APPEARS THAT THIS TAG SHOULD BE FOR NOTE #15. PLEASE
 CLARIFY. FBC 107.2.1

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 07:53 Rev Time 0.00
Received By jleahy Date 2022-01-07 Time 07:30 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 12:12 Rev Time 0.00
Received By jleahy Date 2021-11-03 Time 11:54 Sent To  
Notes
2021-11-03 13:00:32ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E2.1
  
 NO OVERCURRENT PROTECTION SIZE SHOWN FOR THE PRIMARY OF
 THE TRANSFORMER. 30KVA 450.3(B)(1), 240.4 125%
  
 WIRE SIZE ON THE PRIMARY OF THE TRANSFORMER SHOULD BE
 #6 UNLESS YOU CAN SHOW CALCULATION 215.2(A)(1)(A),
 110.14(C)(1)(A)(2), 310.15(B)(16) 125%
  
 AIC RATING OF PANELS ? PLEASE SHOW CALCULATION. 110.9,
 110.10, 110.24

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By pleduc Date 2021-09-30 Time   Rev Time 0.00
Received By pleduc Date 2021-09-30 Time 16:37 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-01-18 Cont ID  
Sent By medwards Date 2022-01-18 Time 16:42 Rev Time 0.00
Received By medwards Date 2022-01-07 Time 10:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 07:54 Rev Time 0.00
Received By jleahy Date 2021-11-24 Time 15:35 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 13:00 Rev Time 0.00
Received By jleahy Date 2021-09-28 Time 14:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-01-18 Cont ID  
Sent By medwards Date 2022-01-18 Time 16:41 Rev Time 0.00
Received By medwards Date 2022-01-18 Time 16:41 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 13:40 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 13:40 Sent To  
Notes
2021-12-03 13:46:18IT APPEARS THAT THE VAV-14-1, VAV-14-2, AND VAV-14-3
 HAVE BEEN CHANGED TO NOW BE AHU'S PLEASE PROVIDE
 DETAILS FOR ALL AHU'S AND ALSO SHOW THE CONDENSATE
 PIPING, MATERIAL AND TERMINATION LOCATION. FBC 107.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By medwards Date 2021-10-20 Time 14:30 Rev Time 0.00
Received By medwards Date 2021-10-20 Time 14:30 Sent To  
Notes
2021-10-20 14:30:271ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091315
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.1: THE VAV TERMINAL BOX SCHEDULE LISTS THE
 DESIGN COOLING AIRFLOW CFM?S FOR VAV 14-2 IS 1600 CFM.
 SHEET M2.1: AFTER ADDING THE CFM?S AT EACH SUPPLY
 GRILLE THE TOTAL AIRFLOW IS 1825 CFM?S. PLEASE REVIEW.
 FBC 107.2.1
  
 2) SHEET M3.1: PLEASE SHOW THE VAV 14-4 IN THE VAV
 TERMINAL BOX SCHEDULE. FBC 107.2.1
  
 3) PLEASE PROVIDE A DETAIL SHOWING THE RETURN AIR PATH
 FROM THE TENANT SPACE BACK TO THE MECHANICAL ROOM. FBC
 M 601.6
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-12-12 Cont ID  
Sent By abelisle Date 2021-12-12 Time 15:12 Rev Time 0.00
Received By abelisle Date 2021-12-12 Time 14:13 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-28 Cont ID  
Sent By ccole Date 2021-10-28 Time 08:15 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:24 Sent To  
Notes
2021-10-28 08:15:53PLUMBING REVIEW BY JERALD SMITH
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21091315 360 S ROSEMARY AVE 1440
  
 1ST REVIEW
 PLUMBING COMMENTS: DENIED
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
 1.RE: A0.2 ADA; PER WPB FBC 107.2.1, TO SHOW COMPLIANCE
 WITH FBC ACC CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND
 ELEVATION DETAILS FOR NEW TOILET ROOM INDICATING THE
 FOLLOWING:
 ?A) RE: MOUNTING HEIGHT DETAIL FOR THE TOILET ROOM; THE
 WATER CLOSET SHALL BE POSITIONED WITH A WALL OR
 PARTITION TO THE REAR AND TO ONE SIDE. THE CENTERLINE
 OF THE WATER CLOSET SHALL BE 16 INCHES MINIMUM TO 18
 INCHES MAXIMUM FROM THE SIDE WALL OR PARTITION PER FBC
 ACC 604.2. NOT 18 INCHES MINIMUM AS INDICATED.
 ?B) RE: MOUNTING HEIGHT DETAIL FOR THE TOILET ROOM;
 REMOVE THE 6 INCH DIMENSION BETWEEN THE SIDE WALL AND
 THE AND THE REAR WALL GRAB BAR TO ALLOW FOR THE
 FLUCTUATION OF THE 16-18 INCHES CENTERLINE OF THE WATER
 CLOSET.
 ?C) FLUSH CONTROLS SHALL BE HAND OPERATED OR AUTOMATIC.
 HAND OPERATED FLUSH CONTROLS SHALL COMPLY WITH 309.
 FLUSH CONTROLS SHALL BE LOCATED ON THE OPEN SIDE OF THE
 WATER CLOSET PER FBC ACC 604.6.
 NOTE ON DETAIL THE CONTROL TO THE OPEN SIDE AWAY FROM
 WALL
 ?D) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN FRONT
 OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF THE
 DISPENSER. THE OUTLET OF THE DISPENSER SHALL BE 15
 INCHES MINIMUM AND 48 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR AND SHALL NOT BE LOCATED BEHIND GRAB BARS PER FBC
 ACC 604.8.
 PER WPB FBC 107.2.1, INDICATE MOUNTING HEIGHT OF
 DISPENSER.
 ?E) PER FBC 606.5 EXPOSED PIPES AND SURFACES. WATER
 SUPPLY & DRAINPIPES UNDER LAVATORIES AND SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT.
 ?F) RE: TYPICAL ELEVATIONS DETAIL FOR THE TOILET ROOM
 REAR WALL; MIRRORS LOCATED ABOVE LAVATORIES OR
 COUNTERTOPS SHALL BE INSTALLED WITH THE BOTTOM EDGE OF
 THE REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND PER FBC ACC 603.3.
  
 2.RE: P0.1 CONCERNING MATERIAL SPECIFICATIONS FOR WATER
 DISTRIBUTION AND FOR SANITARY WASTE AND VENTS. WATER
 CALLS FOR TYPE L COPPER OR SDR 11 CPVC. SANITARY WASTE
 AND VENTS CALL FOR WASTE ABOVE THE SLAB TO BE TO BE
 CAST IRON; BELOW SLAB, VENTS AND SINK P-TRAP MAY BE
 PVC. NO PVC ALLOWED THROUGH FIRE RATED ASSEMBLIES. P4.1
 SHOWS A FIRE RATED ASSEMBLY THROUGH A RATED FLOOR, THE
 FLOOR BEING CORRUGATED METAL WITH LIGHTWEIGHT CONCRETE.
 ADDITIONALLY, A4.1 PROVIDES UL ASSEMBLIES INCLUDING
 THROUGH THE FLOOR ASSEMBLIES FOR BOTH PLASTIC AND METAL
 PIPES.
 OBSERVATION: IT IS ADVISABLE TO CHOOSE A CONSISTENT
 MATERIAL SPECIFICATION FOR EACH SYSTEM TO AVOID
 CONFUSION.
 PER WPB FBC 107.2.1, PROVIDE THE FOLLOWING
 CLARIFICATIONS:
 ?A) WHICH UL PENETRATION DETAILS SHALL BE USED
 ?B) IS PVC PIPING TO BE ALLOWED IN THROUGH FLOOR RATED
 ASSEMBLIES? PLEASE CONFIRM THAT METAL PIPE THROUGH A
 RATED FLOOR ASSEMBLY WHEN THE UNDERSLAB PIPING AND
 ABOVE GROUND VENTS WILL PROTECT THE FLOOR
  
 3.PER WPB FBC 107.2.1, PROVIDE SPECIFICATION FOR
 VALVES; ALL COMPONENTS IN THE POTABLE WATER SYSTEM
 SHALL COMPLY WITH FBC PL 605.2.1 FOR LEAD CONTENT.
  
 4. PER WPB FBC 107.2.1, PROVIDE ON THE PIPE HANGER
 DETAIL ANCHOR METHOD AND A NOTE STATING, "HORIZONTAL
 PIPE SHALL BE SUPPORTED IN ACCORDANCE WITH FBC PL TABLE
 308.5."
  
 5.RE: P4.1/DETAIL 5; TYPICAL POINT OF USE HEATER
 (EWH-1) INSTALLATION. PER WPB FBC 107.2.1 PROVIDE THE
 FOLLOWING;
 ?A) PER FBC PL 602.1, PROVIDE A TEE BETWEEN THE POINT
 THE COLD WATER OUTLET PROTRUDES FROM THE WALL PLACED
 BETWEEN THE LAVATORY SHUTOFF VALVE AND THE WATER HEATER
 SERVICE VALVE
  
 6. FOR THE HEATER (EWH-2) SERVICING MORE THAN ONE
 FIXTURE (BREAKROOM SINK WITH DISHWASHER) PROVIDE A
 SECOND DETAIL SHOW A TEE BETWEEN THE POINT THE COLD
 WATER OUTLET PROTRUDES FROM THE WALL PLACED BETWEEN THE
 LAVATORY SHUTOFF VALVE AND THE WATER HEATER SERVICE
 VALVE AND A TEE IN HOT WATER PIPING WITH SHUTOFF VALVE
 TO EACH FIXTURE/APPLIANCE.
 ?A) ADD NOTE ON P2.1 ADDRESSING THE SAME. NOTE 3
 REFERRING TO P4.1/DETAIL 5 ONLY APPLIES TO BATHROOM
 HEATERS.
  
 7. PER WPB FBC 107.2.1, PROVIDE NOTE AT WATER HAMMER
 ARRESTER SCHEDULE STATING PER FLORIDA PLUMBING CODE
 604.9, PROVIDE WATER HAMMER ARRESTER AT DISHWASHER AND
 ICEMAKER
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-01-18 Cont ID  
Sent By medwards Date 2022-01-18 Time 16:42 Rev Time 0.00
Received By medwards Date 2022-01-18 Time 16:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-07 Cont ID  
Sent By jleahy Date 2022-01-07 Time 07:54 Rev Time 0.00
Received By jleahy Date 2022-01-07 Time 07:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-21 Cont ID  
Sent By rmcdouga Date 2021-10-21 Time 10:27 Rev Time 0.00
Received By rmcdouga Date 2021-10-21 Time 10:27 Sent To  
Notes
2021-10-21 10:28:39THE FIRE ALARM PLAN IS NOT SIGNED AND SEALED BY THE
 ENGINEER. ELECTRONICALLY SUBMITTED DRAWINGS ARE
 REQUIRED TO HAVE THE ARCHITECT OR ENGINEER'S DIGITAL
 SIGNATURE ON THEM. YOU ALSO HAVE THE OPTION TO SUBMIT
 THE SIGNED AND SEALED PAPER VERSION OF DRAWINGS. AFTER
 THE ELECTRONIC PLANS HAVE BEEN APPROVED, YOU CAN SUBMIT
 THE CORRESPONDING PAPER DRAWINGS AT THE BUILDING
 DEPARTMENT TO BE VERIFIED. THE ARCHITECT OR ENGINEER'S
 ORIGINAL HANDWRITTEN SIGNATURE AND SEAL IS REQUIRED TO
 BE ON THE DRAWINGS. NO PHOTOCOPY OR OTHER FACSIMILES OF
 THE SIGNATURE ARE ACCEPTABLE. FS 487 & 61G1 OR FS 471 &
 61G15