Plan Review Details - Permit 21091249
Plan Review Stops For Permit 21091249
Review Stop AD ADDRESSING
Rev No 3 Status P Date 2022-05-10 Cont ID  
Sent By cpuell Date 2022-05-10 Time 13:06 Rev Time 0.00
Received By cpuell Date 2022-05-10 Time 13:06 Sent To  
Notes
2022-05-10 13:06:53ADDRESS APPROPRIATE FOR PROJECT.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2021-12-15 Cont ID  
Sent By cpuell Date 2021-12-15 Time 15:57 Rev Time 0.00
Received By cpuell Date 2021-12-15 Time 15:57 Sent To  
Notes
2021-12-15 15:59:50ADDRESS WAS PROPOSED ON 11/16/20 OF 85 SOUTHERN BLVD,
 SENT TO NADIA VANESSA ZEITINGER
  NO CONFIMATION FOR
 THIS ADDRESS WAS EVER GIVEN. PLEASE CONTACT
 [email protected] OR CALL 561-805-6659 TO DISCUSS OPTIONS.

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-01 Cont ID  
Sent By cpuell Date 2021-12-01 Time 12:01 Rev Time 0.00
Received By cpuell Date 2021-12-01 Time 12:01 Sent To  
Notes
2021-12-01 12:01:28AN ADDRESS NEEDS TO BE ESTABLISHED FOR THE BUILDING
 WHERE THE WORK IS DONE, PLEASE PROVIDE A SITE PLAN OR
 AERIAL MAP SHOWING THE EXACT BUILDING TO BE WORKED ON.
 PLEASE EMAIL RESPONSE TO [email protected] OR CALL
 561-805-6659.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By rmcphers Date 2022-04-05 Time 15:53 Rev Time 0.00
Received By rmcphers Date 2022-04-05 Time 15:53 Sent To  
Notes
2022-04-05 15:54:12PLUMBING AND MECHANICAL WORK ONLY

Review Stop E ELECTRICAL
Rev No 4 Status N Date 2022-09-21 Cont ID  
Sent By shill Date 2022-09-21 Time 12:38 Rev Time 0.00
Received By shill Date 2022-09-21 Time 12:38 Sent To  
Notes
2022-09-21 12:38:41DOT - EXEMPT FROM PERMITTING
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2022-08-26 Cont ID  
Sent By fgiaquin Date 2022-08-26 Time 18:50 Rev Time 0.00
Received By fgiaquin Date 2022-08-25 Time 19:44 Sent To  
Notes
2022-08-26 18:50:44SEE LAST PLAN REVIEW COMMENTS. NO ELEC PLANS UPLOADED.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 20:01 Rev Time 0.00
Received By fgiaquin Date 2022-05-23 Time 19:13 Sent To  
Notes
2022-05-23 20:01:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SUBMIT ELECTRICAL PLAN PERTAINING TO HVAC INSTALL AS
 PER LAST PLAN REVIEW COMMENTS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2022-03-23 Cont ID  
Sent By fgiaquin Date 2022-03-23 Time 22:40 Rev Time 0.00
Received By fgiaquin Date 2022-03-23 Time 21:45 Sent To  
Notes
2022-03-23 22:40:51ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND
 SEALED BY A LICENSED DESIGN PROFESSIONAL OR SIGNED BY
 THE ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H);
 471.025; WPB FBC 107.2.1, 107.3.5
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-09-21 Cont ID  
Sent By aoliver Date 2022-09-21 Time 12:55 Rev Time 0.00
Received By aoliver Date 2022-09-21 Time 12:55 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-08-26 Cont ID  
Sent By fgiaquin Date 2022-08-26 Time 18:51 Rev Time 0.00
Received By fgiaquin Date 2022-08-24 Time 17:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 20:02 Rev Time 0.00
Received By fgiaquin Date 2022-05-07 Time 11:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-04-05 Cont ID  
Sent By rmcphers Date 2022-04-05 Time 15:55 Rev Time 0.00
Received By rmcphers Date 2022-03-09 Time 10:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-05-11 Cont ID  
Sent By medwards Date 2022-05-11 Time 15:37 Rev Time 0.00
Received By medwards Date 2022-05-11 Time 15:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 08:03 Rev Time 0.00
Received By medwards Date 2022-03-15 Time 08:03 Sent To  
Notes
2022-03-15 08:05:32PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THESE NEW MINI-SPLITS. FBC EC C403.2.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status N Date 2022-09-21 Cont ID  
Sent By shill Date 2022-09-21 Time 12:39 Rev Time 0.00
Received By shill Date 2022-09-21 Time 12:39 Sent To  
Notes
2022-09-21 12:39:16SEPARATE PERMIT

Review Stop P PLUMBING
Rev No 3 Status F Date 2022-08-25 Cont ID  
Sent By ccole Date 2022-08-25 Time 11:55 Rev Time 0.00
Received By ccole Date 2022-08-25 Time 10:34 Sent To  
Notes
2022-08-25 12:01:093RD REVIEW FBC-2020 PLUMBING
 PERMIT- 21091249
 8/25//2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW AND 2ND REVIEWS THAT STILL EXIST ARE COPIED
 BELOW. ON THIS THIRD REVIEW CYCLE AN UNSIGNED NARRATIVE
 RESPONSE HAS BEEN PROVIDED FOR COMMENTS #3- #10. THE
 NARRATIVE ALSO ADDRESSES SOME OF THE PLUMBING COMMENTS
 LISTED UNDER PERMIT- 21100653. CONCERNING 21091249, THE
 NARRATOR INDICATES CORRECTIONS HAVE BEEN MADE TO THE
 PLANS, HOWEVER NO CORRECTED PLANS WERE UPLOADED FOR
 REVIEW. THE APPLICANT SHALL PROVIDE CORRECTED PLANS, OR
 AS AN ALTERNATIVE, MAY REQUEST TO HAVE THE PLUMBING
 REVIEW ELIMINATED FOR 21091249 AND HAVE THE COMMENTS
 INCORPORATED INTO THE PLUMBING REVIEW COMMENTS FOR
 21100652. THE PLANS ARE THE SAME FOR BOTH PERMITS.
 PLEASE CONTACT ME AS SOON AS POSSIBLE TO RESOLVE THE
 ISSUES.
  
 1) SHEET MP-1 & MP-2 STORM DRAIN SUMP PUMP SYSTEM: A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP, THE PUMP
 CURVE AND SIZING CALCULATIONS- SEC. 1113.1.1 FBC P. B)
 PROVIDE A DIMENSIONED DETAIL SHOWING THE SUMP PIT, SUMP
 PUMP, AND DISCHARGE PIPING RUN. PLEASE INCLUDE THE
 LOCATIONS OF THE REQUIRED GATE AND CHECK VALVES-
 SEC.1113.2- 1113.1.4 FBC P. C) SUBMIT SHEET B1-424
 WHICH IS REFERENCED ON THE DRAWING BUT NOT INCLUDED IN
 THE PLAN SET- SEC. 107.2.1 WPB.
  
 2) MP-1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER
 HEATERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC.
 502.1 FBC P.
  
 3) MP-4 & MP-8: HOT WATER SHALL BE DELIVERED FROM THE
 SERVICE SINK, HOWEVER NO HW LINE HAS BEEN PROVIDED-
 SEC. 607.1 FBC P.
  
 4) MP-4 & MP-8: THE EWH SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM HOT WATER
 DELIVERY TEMPERATURE AT THE P3 & P4 SINKS- SEC 607.1.1
 FBC P. PLEASE PROVIDE A THERMOSTATIC MIXING VALVE. A)
 COLD OR TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORY SINK- P2- SEC. 419.5 FBC P. IF USING A MIXING
 VALVE FOR THAT PURPOSE, THE DEVICE SHALL CONFORM TO
 ASSE 1070- SEC. 607.1.2 FBC P.
  
 5) MP-4: PROVIDE A BACKWATER VALVE DETAIL, AND INDICATE
 HOW ACCESS TO THE VALVE WILL BE PROVIDED- SEC. 714.1-
 714.3 FBC P.
  
 6) MP-1 & MP-8: ADA WATER CLOSET AND SINK ARE SPECIFIED
 FOR THE NEW TOILET ROOM. THERE ARE NO ARCHITECTURAL
 DRAWINGS INCLUDED IN THE PLAN SETS AND NO INTERIOR
 ELEVATION DETAILS. IF THE INTENTION IS TO DESIGN THE
 TOILET ROOM AS ACCESSIBLE, PLEASE PROVIDE THE FOLLOWING
 LIST OF FBC ACC COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SEC. 606.2.
 C) TURNING SPACE DIAMETER- SEC. 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SEC. 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SEC. 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACES SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC.
 606.2.
  
 7) MP-8: BASED ON SEC. 212.3 FBC ACC, THE P-3 SINK
 SHALL BE ACCESSIBLE. PLEASE CLARIFY THE USE OF THE SINK
 AND PROVIDE ENLARGED DETAILS IN ACCORDANCE WITH SECTION
 606.2 FBC ACC.
  
 8) MP-8: PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDE NUMBER
 OF PLUMBING FIXTURES. A) PLEASE LABEL THE TOILET ROOM
 AS EITHER MALE, FEMALE, OR FAMILY- SECS. 403.2 & 403.4
 FBC P.
  
 9) B1-62: PROVIDE HANGER SPACINGS FOR EACH OF THE DRAIN
 PIPE RUNS- TABLE 308.5 FBC P.
  
 10) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A ULL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 11) DEFERRED SUBMITTALS: MANUFACTURER'S SPECIFICATIONS,
 PRODUCT DATA SHEETS FOR ALL PLUMBING FIXTURES,
 APPLIANCES AND DEVICES SHALL BE UPLOADED FOR REVIEW OR
 SHOULD BE DESIGNATED AS DEFERRED SUBMITTALS- SEC.
 107.3.4.1 WPB. ALL ITEMS NOT SUBMITTED FOR REVIEW SHALL
 BE LISTED AS DEFERRED SUBMITTALS INCLUDING BUT NOT
 LIMITED TO:
 WATER HEATERS
 PLUMBING FIXTURES
 SUMP PUMPS AND PITS
 MIXING VALVES
 BACKWATER VALVE
 FIRESTOPPING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-05-11 Cont ID  
Sent By ccole Date 2022-05-11 Time 08:50 Rev Time 0.00
Received By ccole Date 2022-05-11 Time 06:48 Sent To  
Notes
2022-05-11 09:05:022ND REVIEW FBC-2020 PLUMBING
 PERMIT- 21091249
 5/11/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENTS FROM THE 1ST
 REVIEW COPIED BELOW WERE NOT ADDRESSED. NO CORRECTED
 PLANS OR COMMENT RESPONSES WERE UPLOADED FOR REVIEW.
  
 1) SHEET MP-1 & MP-2 STORM DRAIN SUMP PUMP SYSTEM: A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP, THE PUMP
 CURVE AND SIZING CALCULATIONS- SEC. 1113.1.1 FBC P. B)
 PROVIDE A DIMENSIONED DETAIL SHOWING THE SUMP PIT, SUMP
 PUMP, AND DISCHARGE PIPING RUN. PLEASE INCLUDE THE
 LOCATIONS OF THE REQUIRED GATE AND CHECK VALVES-
 SEC.1113.2- 1113.1.4 FBC P. C) SUBMIT SHEET B1-424
 WHICH IS REFERENCED ON THE DRAWING BUT NOT INCLUDED IN
 THE PLAN SET- SEC. 107.2.1 WPB.
  
 2) MP-1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER
 HEATERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC.
 502.1 FBC P.
  
 3) MP-4 & MP-8: HOT WATER SHALL BE DELIVERED FROM THE
 SERVICE SINK, HOWEVER NO HW LINE HAS BEEN PROVIDED-
 SEC. 607.1 FBC P.
  
 4) MP-4 & MP-8: THE EWH SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM HOT WATER
 DELIVERY TEMPERATURE AT THE P3 & P4 SINKS- SEC 607.1.1
 FBC P. PLEASE PROVIDE A THERMOSTATIC MIXING VALVE. A)
 COLD OR TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORY SINK- P2- SEC. 419.5 FBC P. IF USING A MIXING
 VALVE FOR THAT PURPOSE, THE DEVICE SHALL CONFORM TO
 ASSE 1070- SEC. 607.1.2 FBC P.
  
 5) MP-4: PROVIDE A BACKWATER VALVE DETAIL, AND INDICATE
 HOW ACCESS TO THE VALVE WILL BE PROVIDED- SEC. 714.1-
 714.3 FBC P.
  
 6) MP-1 & MP-8: ADA WATER CLOSET AND SINK ARE SPECIFIED
 FOR THE NEW TOILET ROOM. THERE ARE NO ARCHITECTURAL
 DRAWINGS INCLUDED IN THE PLAN SETS AND NO INTERIOR
 ELEVATION DETAILS. IF THE INTENTION IS TO DESIGN THE
 TOILET ROOM AS ACCESSIBLE, PLEASE PROVIDE THE FOLLOWING
 LIST OF FBC ACC COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SEC. 606.2.
 C) TURNING SPACE DIAMETER- SEC. 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SEC. 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SEC. 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACES SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC.
 606.2.
  
 7) MP-8: BASED ON SEC. 212.3 FBC ACC, THE P-3 SINK
 SHALL BE ACCESSIBLE. PLEASE CLARIFY THE USE OF THE SINK
 AND PROVIDE ENLARGED DETAILS IN ACCORDANCE WITH SECTION
 606.2 FBC ACC.
  
 8) MP-8: PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDE NUMBER
 OF PLUMBING FIXTURES. A) PLEASE LABEL THE TOILET ROOM
 AS EITHER MALE, FEMALE, OR FAMILY- SECS. 403.2 & 403.4
 FBC P.
  
 9) B1-62: PROVIDE HANGER SPACINGS FOR EACH OF THE DRAIN
 PIPE RUNS- TABLE 308.5 FBC P.
  
 10) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A ULL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 11) DEFERRED SUBMITTALS: MANUFACTURER'S SPECIFICATIONS,
 PRODUCT DATA SHEETS FOR ALL PLUMBING FIXTURES,
 APPLIANCES AND DEVICES SHALL BE UPLOADED FOR REVIEW OR
 SHOULD BE DESIGNATED AS DEFERRED SUBMITTALS- SEC.
 107.3.4.1 WPB. ALL ITEMS NOT SUBMITTED FOR REVIEW SHALL
 BE LISTED AS DEFERRED SUBMITTALS INCLUDING BUT NOT
 LIMITED TO:
 WATER HEATERS
 PLUMBING FIXTURES
 SUMP PUMPS AND PITS
 MIXING VALVES
 BACKWATER VALVE
 FIRESTOPPING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2022-03-14 Cont ID  
Sent By ccole Date 2022-03-14 Time 13:26 Rev Time 0.00
Received By ccole Date 2022-03-14 Time 09:57 Sent To  
Notes
2022-03-14 13:27:091ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091249
 3/14/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET MP-1 & MP-2 STORM DRAIN SUMP PUMP SYSTEM: A)
 PROVIDE AN EQUIPMENT SCHEDULE FOR THE PUMP, THE PUMP
 CURVE AND SIZING CALCULATIONS- SEC. 1113.1.1 FBC P. B)
 PROVIDE A DIMENSIONED DETAIL SHOWING THE SUMP PIT, SUMP
 PUMP, AND DISCHARGE PIPING RUN. PLEASE INCLUDE THE
 LOCATIONS OF THE REQUIRED GATE AND CHECK VALVES-
 SEC.1113.2- 1113.1.4 FBC P. C) SUBMIT SHEET B1-424
 WHICH IS REFERENCED ON THE DRAWING BUT NOT INCLUDED IN
 THE PLAN SET- SEC. 107.2.1 WPB.
  
 2) MP-1: PROVIDE EQUIPMENT SCHEDULES FOR THE NEW WATER
 HEATERS AND SUBMIT MANUFACTURER'S SPECIFICATIONS- SEC.
 502.1 FBC P.
  
 3) MP-4 & MP-8: HOT WATER SHALL BE DELIVERED FROM THE
 SERVICE SINK, HOWEVER NO HW LINE HAS BEEN PROVIDED-
 SEC. 607.1 FBC P.
  
 4) MP-4 & MP-8: THE EWH SHALL NOT SERVE AS THE
 TEMPERATURE LIMITING MEANS FOR MAXIMUM HOT WATER
 DELIVERY TEMPERATURE AT THE P3 & P4 SINKS- SEC 607.1.1
 FBC P. PLEASE PROVIDE A THERMOSTATIC MIXING VALVE. A)
 COLD OR TEMPERED WATER SHALL BE DELIVERED FROM THE
 LAVATORY SINK- P2- SEC. 419.5 FBC P. IF USING A MIXING
 VALVE FOR THAT PURPOSE, THE DEVICE SHALL CONFORM TO
 ASSE 1070- SEC. 607.1.2 FBC P.
  
 5) MP-4: PROVIDE A BACKWATER VALVE DETAIL, AND INDICATE
 HOW ACCESS TO THE VALVE WILL BE PROVIDED- SEC. 714.1-
 714.3 FBC P.
  
 6) MP-1 & MP-8: ADA WATER CLOSET AND SINK ARE SPECIFIED
 FOR THE NEW TOILET ROOM. THERE ARE NO ARCHITECTURAL
 DRAWINGS INCLUDED IN THE PLAN SETS AND NO INTERIOR
 ELEVATION DETAILS. IF THE INTENTION IS TO DESIGN THE
 TOILET ROOM AS ACCESSIBLE, PLEASE PROVIDE THE FOLLOWING
 LIST OF FBC ACC COMPLIANCE DETAILS:
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 WATER CLOSET- SEC. 604.3.
 B) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SEC. 606.2.
 C) TURNING SPACE DIAMETER- SEC. 304.3.
 D) CENTERLINE OF THE WATER CLOSETS FROM THE SIDE WALLS-
 SEC. 604.2.
 E) HEIGHT OF THE WATER CLOSET SEAT FROM THE FINISHED
 FLOOR- SEC. 604.4.
 F) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 G) HEIGHT OF THE MIRRORS FROM THE FINISHED FLOOR TO THE
 REFLECTIVE SURFACES SEC. 603.3
 H) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE WATER CLOSETS- SECS. 604.5 & 609.4,
 FIGURES 604.5.1 & 604.5.2.
 I) LOCATION OF THE WATER CLOSET FLUSH CONTROLS- SEC.
 604.6.
 J) CENTERLINE OF THE TOILET PAPER DISPENSERS MEASURED
 FROM THE FRONTS OF THE WATER CLOSETS- SECTION AND
 FIGURE 604.7.
 K) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC.
 606.2.
  
 7) MP-8: BASED ON SEC. 212.3 FBC ACC, THE P-3 SINK
 SHALL BE ACCESSIBLE. PLEASE CLARIFY THE USE OF THE SINK
 AND PROVIDE ENLARGED DETAILS IN ACCORDANCE WITH SECTION
 606.2 FBC ACC.
  
 8) MP-8: PLEASE PROVIDE PLUMBING FIXTURE CALCULATIONS
 IN COMPLIANCE WITH TABLE 403.1 FBC P. PROVIDE A
 SCHEDULE THAT INDICATES THE REQUIRED AND PROVIDE NUMBER
 OF PLUMBING FIXTURES. A) PLEASE LABEL THE TOILET ROOM
 AS EITHER MALE, FEMALE, OR FAMILY- SECS. 403.2 & 403.4
 FBC P.
  
 9) B1-62: PROVIDE HANGER SPACINGS FOR EACH OF THE DRAIN
 PIPE RUNS- TABLE 308.5 FBC P.
  
 10) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A ULL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 11) DEFERRED SUBMITTALS: MANUFACTURER'S SPECIFICATIONS,
 PRODUCT DATA SHEETS FOR ALL PLUMBING FIXTURES,
 APPLIANCES AND DEVICES SHALL BE UPLOADED FOR REVIEW OR
 SHOULD BE DESIGNATED AS DEFERRED SUBMITTALS- SEC.
 107.3.4.1 WPB. ALL ITEMS NOT SUBMITTED FOR REVIEW SHALL
 BE LISTED AS DEFERRED SUBMITTALS INCLUDING BUT NOT
 LIMITED TO:
 WATER HEATERS
 PLUMBING FIXTURES
 SUMP PUMPS AND PITS
 MIXING VALVES
 BACKWATER VALVE
 FIRESTOPPING
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-05-23 Cont ID  
Sent By fgiaquin Date 2022-05-23 Time 20:01 Rev Time 0.00
Received By fgiaquin Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2022-03-15 Cont ID  
Sent By medwards Date 2022-03-15 Time 08:05 Rev Time 0.00
Received By medwards Date 2022-03-15 Time 08:05 Sent To  
Notes
2022-03-15 08:07:25DIGITAL SUBMITTALS REQUIRE A DIGITAL SIGNATURE OF THE
 ENGINEER. PLEASE PROVIDE DRAWINGS WITH THE DIGITAL
 SIGNATURE OF THE ENGINEER, MAKE SURE THE SIGNATURES ARE
 3RD PARTY VERIFIED. FS 468/478
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status N Date 2022-03-25 Cont ID  
Sent By aaponte Date 2022-03-25 Time 09:26 Rev Time 0.00
Received By ckimmerl Date 2022-03-25 Time 09:26 Sent To  
Notes
***NONE***