Plan Review Details - Permit 21091179
Plan Review Stops For Permit 21091179
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-09-30 Cont ID  
Sent By cpuell Date 2021-09-30 Time 14:45 Rev Time 0.00
Received By cpuell Date 2021-09-30 Time 14:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-03-21 Cont ID  
Sent By rmcdouga Date 2022-03-21 Time 08:35 Rev Time 0.00
Received By rmcdouga Date 2022-03-21 Time 08:20 Sent To  
Notes
2022-03-21 08:35:56BUILDING AUDIT COMPLETE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 14:27 Rev Time 0.00
Received By rmcdouga Date 2022-02-10 Time 13:25 Sent To  
Notes
2022-02-10 14:22:382ND AUDIT
 COMMENTS FROM THE FIRST AUDIT HAVE NOT BEEN ADDRESSED.
  
 1) [NOT RESOLVED.] ON SHEET 3 OF 12 THE ENGINEERING
 CRITERIA SPECIFIES THAT ASCE7 - 10 IS BEING USED. THE
 2020 FBC - R REFERENCES ASCE7 -16. THE 2016 EDITION OF
 ASCE7 SHOULD BE USED FOR THE 2020 FBC.
  
 2) [NOT RESOLVED.THIS CAN NOT BE DEFFERED.] THERE WAS
 NO PRODUCT APPROVAL OR SITE SPECIFIC ENGINEERING
 SUBMITTED FOR THE 3' X 8' ENTRY DOOR, TRANSOM AND
 SIDELITES. R609.2.1 CUSTOM DOORS. CUSTOM
 (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY OR BE DESIGNED
 AND ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICES BY A FLORIDA REGISTERED DESIGN PROFESSIONAL.
 SIGNED AND SEALED COPIES OF THE RATIONAL ANALYSIS AND
 CALCULATIONS SHALL BE PROVIDED TO THE BUILDING OFFICIAL
 UPON PERMIT APPLICATION. WIND-BOURNE DEBRIS PROTECTION
 IS REQUIRED FOR GLAZED OPENINGS PER FBC-R301.2.1.2.
  
 3) [NOT RESOLVED. THE PLANS SPECIFY A 1" FOAM BOARD
 INSULATION ON THE FLAT PART OF THE ROOF.] THERE WERE NO
 COMPONENT AND CLADDING PRESSURES SPECIFIED FOR THE FLAT
 ROOF. THE PRODUCT APPROVAL FOR THE CERTAINTEED MODIFIED
 BITUMEN ROOF SYSTEM, FL16709-R16, HAS THE ROOF CLADDING
 DESIGN PRESSURES HI-LITED ON TABLE 2C ON PAGE 5 OF 25
 FOR EXPOSURE D, ENCLOSED, GREATER THAN 30 FT AND THE
 ULTIMATE DESIGN WIND SPEED VASD OF 180MPH. THIS PROJECT
 IS LOCATED IN THE 170 MPH VULT WIND SPEED AND THE PLANS
 CORRECTLY SPECIFY THIS. ON TABLE 6 ON PAGE 21 OF THE
 PRODUCT APPROVAL FOR SYSTEM W-4 YOU HI-LITED #1
 (AS-LISTED) IN THE 180 MPH COLUMN. YOU SHOULD BE USING
 THE 170 MPH COLUMN. PLEASE NOTE THAT THERE ARE FOUR
 ROOF ZONES AND THE FASTENING REQUIREMENTS FOR EACH ZONE
 IS SPECIFIED IN THE COLUMNS OF THE TABLE. ALSO NOTE
 THAT N/A IN THE TABLE INDICATES THAT THE SYSTEM CAN NOT
 BE USED WITHIN THE PRESSURE ZONE. THEREFORE, THIS
 SYSTEM CAN NOT BE USED.
  
 4) SUBMIT A RESPONSE LETTER STATING HOW EACH OF THE
 AUDIT COMMENTS HAS BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By rmcdouga Date 2021-12-15 Time 12:51 Rev Time 0.00
Received By rmcdouga Date 2021-12-15 Time 12:51 Sent To  
Notes
2021-12-15 12:55:301ST AUDIT
  
 1) ON SHEET 3 OF 12 THE ENGINEERING CRITERIA SPECIFIES
 THAT ASCE7 - 10 IS BEING USED. THE 2020 FBC - R
 REFERENCES ASCE7 -16. THE 2016 EDITION OF ASCE7 SHOULD
 BE USED FOR THE 2020 FBC.
  
 2) THERE WAS NO PRODUCT APPROVAL OR SITE SPECIFIC
 ENGINEERING SUBMITTED FOR THE 3' X 8' ENTRY DOOR,
 TRANSOM AND SIDELITES. R609.2.1 CUSTOM DOORS. CUSTOM
 (ONE-OF-A-KIND) EXTERIOR DOOR ASSEMBLIES SHALL BE
 TESTED BY AN APPROVED TESTING LABORATORY OR BE DESIGNED
 AND ENGINEERED IN ACCORDANCE WITH ACCEPTED ENGINEERING
 PRACTICES BY A FLORIDA REGISTERED DESIGN PROFESSIONAL.
 SIGNED AND SEALED COPIES OF THE RATIONAL ANALYSIS AND
 CALCULATIONS SHALL BE PROVIDED TO THE BUILDING OFFICIAL
 UPON PERMIT APPLICATION. WIND-BOURNE DEBRIS PROTECTION
 IS REQUIRED FOR GLAZED OPENINGS PER FBC-R301.2.1.2.
  
 3) THERE WERE NO COMPONENT AND CLADDING PRESSURES
 SPECIFIED FOR THE FLAT ROOF. THE PRODUCT APPROVAL FOR
 THE CERTAINTEED MODIFIED BITUMEN ROOF SYSTEM,
 FL16709-R16, HAS THE ROOF CLADDING DESIGN PRESSURES
 HI-LITED ON TABLE 2C ON PAGE 5 OF 25 FOR EXPOSURE D,
 ENCLOSED, GREATER THAN 30 FT AND THE ULTIMATE DESIGN
 WIND SPEED VASD OF 180MPH. THIS PROJECT IS LOCATED IN
 THE 170 MPH VULT WIND SPEED AND THE PLANS CORRECTLY
 SPECIFY THIS. ON TABLE 6 ON PAGE 21 OF THE PRODUCT
 APPROVAL FOR SYSTEM W-4 YOU HI-LITED #1 (AS-LISTED) IN
 THE 180 MPH COLUMN. YOU SHOULD BE USING THE 170 MPH
 COLUMN. PLEASE NOTE THAT THERE ARE FOUR ROOF ZONES AND
 THE FASTENING REQUIREMENTS FOR EACH ZONE IS SPECIFIED
 IN THE COLUMNS OF THE TABLE. ALSO NOTE THAT N/A IN THE
 TABLE INDICATES THAT THE SYSTEM CAN NOT BE USED WITHIN
 THE PRESSURE ZONE. THEREFORE, THIS SYSTEM CAN NOT BE
 USED.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-03-21 Cont ID  
Sent By jleahy Date 2022-03-21 Time 07:56 Rev Time 0.00
Received By jleahy Date 2022-03-21 Time 07:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2022-02-11 Cont ID  
Sent By jleahy Date 2022-02-11 Time 10:36 Rev Time 0.00
Received By jleahy Date 2022-02-11 Time 09:36 Sent To  
Notes
2022-02-11 10:39:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM SHOWS MAIN BREAKER PANELS, PANEL
 SCHECULES SHOW MAIN LUG PANELS PLEASE COORDINATE PLAN
 TO SHOW MAIN BREAKERS IN PANELS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-12-15 Cont ID  
Sent By jleahy Date 2021-12-15 Time 12:57 Rev Time 0.00
Received By jleahy Date 2021-12-15 Time 12:11 Sent To  
Notes
2021-12-15 13:09:02ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM SHOW PANEL A AND PANEL B BOTH ARE FED
 WITH SMALLER THAN REQUIRED CONDUCTORS UNLESS THE MAINS
 IN THE METER MAIN ARE SMALLER.
  
 LOAD CALCULATION SHOWS CONDUCTORS SHOULD BE SIZE A FULL
 CAPACITY FOR THE INTENDED LOAD. 215.5
  
 PLEASE SHOW SIZE OF MAINS IN THE METER MAIN COMBO.
 215.5

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2022-08-23 Cont ID  
Sent By rwbrown Date 2022-08-23 Time 05:40 Rev Time 0.00
Received By rwbrown Date 2022-08-23 Time 05:40 Sent To  
Notes
2022-08-23 05:41:21GAS PERMIT 22080804

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By ccole Date 2022-02-10 Time 12:45 Rev Time 0.00
Received By ccole Date 2022-02-10 Time 12:20 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By ccole Date 2021-12-16 Time 09:31 Rev Time 0.00
Received By ccole Date 2021-12-15 Time 15:13 Sent To  
Notes
2021-12-16 09:32:551ST REVIEW FBC-2020 RES. FUEL GAS
 PERMIT 21091179
 12/16/21
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 11 & 12: THE GAS PIPING PLAN SHOWS AN
 INDIVIDUAL BRANCH PIPE TO THE FIREPLACE DIRECTLY
 CONNECTED TO THE MAIN 2 PSI PE PIPE, BUT THE GAS
 ISOMETRIC SHOWS THE FIREPLACE PIPE CONNECTION ON THE
 BRANCH LINE SUPPLYING THE WATER HEATER- SEC. G2413.1
 FBC RES.
  
 2) SHEET 12 GAS ISOMETRIC: PLEASE LIST THE PIPE SIZING
 TABLES FOR THE LOW PRESSURE SCHEDULE 40 METALLIC-
 G2413.4(1), AND THE LOW PRESSURE CSST- G2413.4(5) FBC
 RES.
  
 3) GAS ISOMETRIC: BASED ON TABLE G2413.4(1) THE
 3/4-INCH SCHEDULE 40 BRANCH SUPPLYING TANKLESS WH #1
 AND FIREPLACE IS UNDERSIZED- MINIMUM 1-INCH REQUIRED.
  
 3) GAS ISOMETRIC: SHOW THE TYPES AND SIZES OF GAS
 PIPING FROM THE LOW PRESSURE REGULATOR TO TANKLESS WH
 #2 AND THE DRYER- SEC. G2413.3.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2022-03-21 Cont ID  
Sent By rmcdouga Date 2022-03-21 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2022-03-16 Time 11:09 Sent To  
Notes
2022-03-17 13:58:48NEEDS B, E ADDED AFTER Z PASSES
  

Review Stop I INCOMING/PROCESSING
Rev No 10 Status F Date 2022-03-09 Cont ID  
Sent By shill Date 2022-03-09 Time 09:27 Rev Time 0.00
Received By shill Date 2022-03-07 Time 07:26 Sent To  
Notes
2022-03-09 09:28:42THE PRIVATE PROVIDER'S REQUEST FOR A PROVISO FROM THE
 BUILDING OFFICIAL IS UNDER CONSIDERATION. PER FS553.791
 THERE IS NO PROVISION IN THE FLORIDA STATUTE FOR A
 PROVISO FOR A PLAN REVIEW AFFIDAVIT. THEREFORE THIS
 DECISION MUST BE MADE BY THE BUILDING OFFICIAL.
  
  

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2022-03-04 Cont ID  
Sent By shill Date 2022-03-04 Time 07:08 Rev Time 0.00
Received By shill Date 2022-03-03 Time 05:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2022-02-11 Cont ID  
Sent By lmarchan Date 2022-02-11 Time 12:29 Rev Time 0.00
Received By lmarchan Date 2022-01-27 Time 07:48 Sent To  
Notes
2022-02-07 13:08:03ZONING PASSED 1/26, NO NEW PAGES SUBMITTED (1/12) SH
  

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2022-01-30 Cont ID  
Sent By cpuell Date 2022-01-30 Time 08:53 Rev Time 0.00
Received By cpuell Date 2022-01-28 Time 07:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2022-01-26 Cont ID  
Sent By lmarchan Date 2022-01-26 Time 12:15 Rev Time 0.00
Received By lmarchan Date 2022-01-13 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-12-16 Time   Rev Time 0.00
Received By lmarchan Date 2021-11-23 Time 11:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-11-23 Cont ID  
Sent By lmarchan Date 2021-11-23 Time 11:02 Rev Time 0.00
Received By lmarchan Date 2021-11-17 Time 06:41 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-09 Cont ID  
Sent By shill Date 2021-11-09 Time 08:29 Rev Time 0.00
Received By shill Date 2021-11-03 Time 08:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-01 Cont ID  
Sent By shill Date 2021-11-01 Time 17:57 Rev Time 0.00
Received By shill Date 2021-10-15 Time 11:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-08 Cont ID  
Sent By lmarchan Date 2021-10-08 Time 14:54 Rev Time 0.00
Received By lmarchan Date 2021-09-28 Time 12:38 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2022-03-18 Cont ID  
Sent By lmarchan Date 2022-03-18 Time 10:34 Rev Time 0.00
Received By lmarchan Date 2022-02-09 Time 07:52 Sent To  
Notes
2022-03-17 14:11:08RECEIPT MU-2022-07013 - $459.33 PAID
2022-02-09 07:53:062/9/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By rmcdouga Date 2021-12-16 Time 10:02 Rev Time 0.00
Received By rmcdouga Date 2021-12-16 Time 10:02 Sent To  
Notes
2021-12-16 10:04:40PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE
 DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS
 OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST
 FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE
 OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL
 IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME
 THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM
 CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS
 TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON
 APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO
 YOUR PROJECT OR EMAIL IT TO [email protected] .
  
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By medwards Date 2022-02-10 Time 13:30 Rev Time 0.00
Received By medwards Date 2022-02-10 Time 13:29 Sent To  
Notes
2022-02-10 13:30:37MECHANICAL AUDIT APPROVED ME

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-12-08 Cont ID  
Sent By medwards Date 2021-12-08 Time 15:06 Rev Time 0.00
Received By medwards Date 2021-12-08 Time 14:03 Sent To  
Notes
2021-12-08 15:06:061ST AUDIT
  
  
 1) THE PLAN REVIEW AFFIDAVIT INCLUDES THE HVAC LOAD
 CALCULATIONS DATED AUG. 18, 2021, FORM R405-2020,
 8/30/2021 BY BRUCE TSCHOSIK. I DO NOT SEE THE LOAD
 SIZING CALCULATIONS IN THIS SUBMITTAL.
  
 2) WHERE IS THE CONDENSATE PIPE MATERIAL, SIZE AND
 TERMINATION LOCATION? FBC RES M1411.3
  
 3) WHERE IS THE BATH EXHAUST SPECIFICATIONS AND THE
 EXHAUST DUCT TERMINATION LOCATIONS? FBC RES M1507.4;
 FBC RES M1506.3
  
 4) WHERE IS THE APPLIANCE TIE DOWN PRODUCT APPROVALS
 FOR THE CONDENSING UNITS? FBC RES M1307.2
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-02-10 Cont ID  
Sent By ccole Date 2022-02-10 Time 12:45 Rev Time 0.00
Received By ccole Date 2022-02-10 Time 12:19 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By ccole Date 2021-12-16 Time 09:33 Rev Time 0.00
Received By ccole Date 2021-12-15 Time 15:13 Sent To  
Notes
2021-12-16 09:35:301ST REVIEW FBC-2020 RES. PLUMBING
 PERMIT- 21091179
 12/16/2021
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET 12: THE 3/8-INCH SUPPLY LINES TO THE KITCHEN
 SINK, BATHTUBS AND SHOWERS ARE UNDERSIZED PER TABLE
 604.5 FBC P- MINIMUM 1/2-INCH LINES REQUIRED.
  
 2) SHEETS 11 & 12: THE SUPPLY LINES TO THE OUTDOOR
 SHOWER AND DISHWASHERS ARE NOT SHOWN IN THE ISOMETRIC
 DRAWING- SECTION 107.3.5.3 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 9 Status N Date 2022-11-18 Cont ID  
Sent By shill Date 2022-11-18 Time 14:15 Rev Time 0.00
Received By shill Date 2022-11-18 Time 14:15 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 8 Status P Date 2022-03-17 Cont ID  
Sent By rmcphers Date 2022-03-17 Time 10:36 Rev Time 0.00
Received By rmcphers Date 2022-03-17 Time 10:36 Sent To  
Notes
2022-03-17 10:36:53PLAN REVIEW AFFIDAVIT COMPLETE

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 7 Status F Date 2022-03-15 Cont ID  
Sent By shill Date 2022-03-15 Time 09:52 Rev Time 0.00
Received By shill Date 2022-03-08 Time 11:26 Sent To  
Notes
2022-03-15 09:54:231. PROVIDE ADDITIONAL INFORMATION AS TO WHY THE PRODUCT
 APPROVAL DOES NOT COMPLY WITH ZONE 3. IT APPEARS THAT
 IS NOT THE CASE.
  
 2. THERE IS NO PROVISION IN THE FLORIDA STATUTE FOR A
 PROVISO FOR AN AFFIDAVIT, FS553.791. HOWEVER UNTIL ITEM
 #1 IS CLARIFIED IT DOES NOT APPEAR THAT A PROVISO IT
 NECESSARY.

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 6 Status F Date 2022-03-03 Cont ID  
Sent By rmcphers Date 2022-03-03 Time 09:44 Rev Time 0.00
Received By rmcphers Date 2022-03-03 Time 09:44 Sent To  
Notes
2022-03-03 09:52:26PRIVATE PROVIDER PLAN REVIEW COMPLIANCE AFFIDAVIT
  
 NEEDS CORRECTIONS -
  
 1) THERE IS A NOTE ON THE AFFIDAVIT REFERRING TO
 PRODUCT APPROVAL FL1609.01 - DRAWING 3 OF 12 DOES NOT
 LIST PRODUCT APPROVAL FL1609.01

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 5 Status P Date 2022-02-09 Cont ID  
Sent By cthroop Date 2022-02-09 Time 17:43 Rev Time 0.00
Received By cthroop Date 2022-02-09 Time 12:35 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 4 Status F Date 2022-01-15 Cont ID  
Sent By shill Date 2022-01-15 Time 15:16 Rev Time 0.00
Received By shill Date 2022-01-15 Time 15:07 Sent To  
Notes
2022-01-06 10:14:45FS553.791, PRIVATE PROVIDER IS REQUIRED TO REVIEW THE
 PLANS PRIOR TO SUBMITTING TO BUILDING DIVISION AUDIT.
  
 SHEET H-1 WAS UPLOADED BUT IS NOT INCLUDED ON THE
 AFFIDAVIT.
 PRIVATE PROVIDER REFERS TO PRODUCT APPROVALS ON SHEET
 3/12 AS REVIEWED, BUT FL7849.25 WAS NOT UPLOADED.
 FL7849 ON FLORIDABUILDING.ORG STOPS AT OPTION 20.
 I WAS UNABLE TO LOCATE FORM R405 BUT IT IS INCLUDED ON
 THE AFFIDAVIT.
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 3 Status P Date 2021-11-23 Cont ID  
Sent By dbattles Date 2021-11-23 Time 10:53 Rev Time 0.00
Received By dbattles Date 2021-11-23 Time 10:48 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 2 Status F Date 2021-11-09 Cont ID  
Sent By shill Date 2021-11-09 Time 08:26 Rev Time 0.00
Received By shill Date 2021-11-09 Time 08:26 Sent To  
Notes
2021-11-09 08:29:51FS553.791, THIS PROJECT IS PRIVATE PROVIDER PLAN
 REVIEW. PLANS ARE TO BE REVIEWED BY THE PRIVATE
 PROVIDER PRIOR TO SUBMITTAL TO THE BUILDING DIVISION.
  
 AFFIDAVITS REQUIRED PRIOR TO AUDIT FS553.791(1)H. THE
 AFFIDAVIT UPLOADED ON 9/27/2021 IS NOT SIGNED.
  
  
  
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status F Date 2021-09-28 Cont ID  
Sent By dbattles Date 2021-09-28 Time 12:42 Rev Time 0.00
Received By dbattles Date 2021-09-28 Time 12:42 Sent To  
Notes
2021-09-28 12:43:48CREDENTIALS-OK
 REVIEW OF PLAN REVIEW AFFIDAVIT TO OCCUR AFTER OTHER
 AGENCY APPROVALS.
  
 DYLAN BATTLES
 561-805-6718
 [email protected]
  
  

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status N Date 2022-03-21 Cont ID  
Sent By rmcdouga Date 2022-03-21 Time 07:28 Rev Time 0.00
Received By rmcdouga Date 2022-03-21 Time 07:28 Sent To  
Notes
2022-03-21 07:50:34ROOFING PRODUCT APPROVALS ARE DEFERRED. THE ROOFING
 PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED AND
 APPROVED BY THE PRIVATE PROVIDER THEN SUBMITTED TO THE
 CITY OF WEST PALM BEACH'S BUILDING DIVISION FOR AUDIT
 BEFORE THEY ARE INSTALLED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2022-02-10 Cont ID  
Sent By rmcdouga Date 2022-02-10 Time 14:23 Rev Time 0.00
Received By rmcdouga Date 2022-02-10 Time 14:22 Sent To  
Notes
2022-02-10 14:26:22THE ROOFING ASSEMBLY/SYSTEM THAT IS SELECTED IN THE
 PRODUCT APPROVAL FOR THE FLAT ROOF IS INCORRECT. SEE
 BUILDING REVIEW.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By rmcdouga Date 2021-12-16 Time 09:49 Rev Time 0.00
Received By rmcdouga Date 2021-12-16 Time 09:49 Sent To  
Notes
2021-12-16 09:52:00THE ROOF COVERING FOR THE FLAT ROOF SECTION IS DENIED.
 SEE BUILDING COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-03-21 Cont ID  
Sent By rmcdouga Date 2022-03-21 Time 08:57 Rev Time 0.00
Received By rmcdouga Date 2022-03-21 Time 08:57 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-02-09 Cont ID  
Sent By cthroop Date 2022-02-09 Time 17:43 Rev Time 0.00
Received By cthroop Date 2022-02-09 Time 12:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-12-16 Cont ID  
Sent By ccole Date 2021-12-16 Time 09:49 Rev Time 0.00
Received By ccole Date 2021-12-16 Time 09:49 Sent To  
Notes
2021-12-16 09:54:02DIGITAL SIGNATURE REVIEW FBC- 2020
 PERMIT- 21091179
 12/16/2021
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET H-1 IS NOT DIGITALLY SIGNED AND SEALED BY THE
 LANDSCAPE ARCHITECT OF RECORD- FL STATUTE 481.221 AND
 SECTION 61G1-16.005 FLORIDA ADMINISTRATIVE CODE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop Z ZONING
Rev No 5 Status P Date 2022-03-18 Cont ID  
Sent By llouie Date 2022-03-18 Time   Rev Time 0.00
Received By llouie Date 2022-03-18 Time   Sent To  
Notes
2022-03-18 12:58:26ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) LANDSCAPE PERMIT SHALL BE SUBMITTED, REVIEWED,
 APPROVED AND INSTALLED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 2.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING,
 SWIMMING POOL.
  
  
 NOTE:
  
 * CONDITIONAL APPROVAL FOR LANDSCAPING SIGNED BY AVANN
 ON 11/3. FORM SENT TO RGATHRIGHT AND DBATTLES FOR
 SIGNATURE FROM BUILDING. RESPONSE FROM RGATHRIGHT.

Review Stop Z ZONING
Rev No 4 Status P Date 2022-01-26 Cont ID  
Sent By llouie Date 2022-01-26 Time   Rev Time 0.00
Received By llouie Date 2022-01-26 Time   Sent To  
Notes
2022-01-26 10:03:48ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) LANDSCAPE PERMIT SHALL BE SUBMITTED, REVIEWED,
 APPROVED AND INSTALLED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 2.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING,
 SWIMMING POOL.
  
  
 NOTE:
  
 * CONDITIONAL APPROVAL FOR LANDSCAPING SIGNED BY AVANN
 ON 11/3. FORM SENT TO RGATHRIGHT AND DBATTLES FOR
 SIGNATURE FROM BUILDING. RESPONSE FROM RGATHRIGHT.
  

Review Stop Z ZONING
Rev No 3 Status P Date 2021-11-08 Cont ID  
Sent By llouie Date 2021-11-08 Time   Rev Time 0.00
Received By llouie Date 2021-11-08 Time   Sent To  
Notes
2021-11-08 07:58:53ZONING APPROVED WITH THE FOLLOWING PROVISOS:
  
 1.) LANDSCAPE PERMIT SHALL BE SUBMITTED, REVIEWED,
 APPROVED AND INSTALLED PRIOR TO THE ISSUANCE OF A
 CERTIFICATE OF OCCUPANCY (C.O.).
  
 2.) SEPARATE PERMITS REQUIRED FOR: LANDSCAPING,
 SWIMMING POOL.
  
  
  
 NOTE:
  
 * CONDITIONAL APPROVAL FOR LANDSCAPING SIGNED BY AVANN
 ON 11/3. FORM SENT TO RGATHRIGHT AND DBATTLES FOR
 SIGNATURE FROM BUILDING. RESPONSE FROM RGATHRIGHT.
  
  
  
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2021-11-01 Cont ID  
Sent By llouie Date 2021-11-01 Time   Rev Time 0.00
Received By llouie Date 2021-11-01 Time   Sent To  
Notes
2021-11-01 13:52:05** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE. RESPONSES TO STAFF'S COMMENTS AND
 REFERENCES TO PLANS REQUIRED:
  
 1.) THERE SEEMS TO BE UTILITIES WITHIN THE PROPERTY
 LINES; HOWEVER, NO EASEMENTS ARE SHOWN ON THE SURVEY.
 SURVEY MUST SHOW ALL UTILITY EASEMENTS WITHIN THE
 PROPERTY.
  
 2.) THE MAXIMUM BUILDING HEIGHT CANNOT EXCEED 30 FT.
 FROM GRADE. THE STRUCTURE EXCEEDS THE REQUIRED HEIGHT
 LIMITATION. [ZLDR S.94-72(A)(2)]
  
 3.) HEIGHT OF NEW WALL/FENCE/GATE(S) SHALL BE PROVIDED
 IN THE SITE PLAN. THE HEIGHT SHALL NOT EXCEED THE
 STANDARDS PROVIDED IN ZLDR S.94-302(B).
  
 4.) SETBACK DISTANCE (FROM THE PROPERTY LINE(S)) SHALL
 BE PROVIDED FOR THE FOLLOWING: POOL EQUIPMENT AND A/C
 PAD, PROPOSED WALK (EAST SIDE OF RESIDENCE).
  
 5.) PROVIDE MORE INFORMATION ON THE "SPORT COURT"
 ILLUSTRATED ON THE SOUTHEAST SIDE OF THE PROPOSED
 RESIDENCE. SETBACK DISTANCE FROM THE PROPERTY LINE(S)
 SHALL BE PROVIDED IN THE SITE PLAN.
  
 6.) A CIRCULAR DRIVEWAY IS PERMITTED; HOWEVER, EACH
 DRIVEWAY OPENING SHALL NOT EXCEED 10 FT. IN WIDTH.
 PLEASE PROVIDE DIMENSIONS TO DEMONSTRATE COMPLIANCE.
 [ZLDR S.94-312(1)]
  
 7.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED AND
 APPROVED PRIOR TO ZONING APPROVAL OF THIS PERMIT.
  
 8.) THERE SHALL BE AT LEAST 1,000 SQ. FT. OF LANDSCAPED
 AREA WITHIN THE REQUIRED FRONT YARD OF THE PROPERTY
 (AREA WITHIN THE FIRST 25 FT. FROM THE NORTH PROPERTY).
 PLEASE PROVIDE FRONT YARD CALCULATIONS TO DEMONSTRATE
 COMPLIANCE. [ZLDR S.94-482(A)]
  
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: SWIMMING POOL,
 LANDSCAPING
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-08 Cont ID  
Sent By llouie Date 2021-10-08 Time   Rev Time  
Received By llouie Date 2021-10-08 Time   Sent To  
Notes
2021-10-08 14:49:12** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE
 COMMENTS IN WRITING AND/OR ON THE PLANS WHERE
 APPLICABLE:
  
 1.) THERE SEEMS TO BE UTILITIES WITHIN THE PROPERTY
 LINES; HOWEVER, NO EASEMENTS ARE SHOWN ON THE SURVEY.
 SURVEY MUST SHOW ALL UTILITY EASEMENTS WITHIN THE
 PROPERTY.
  
 2.) THE MAXIMUM BUILDING HEIGHT CANNOT EXCEED 30 FT.
 FROM GRADE. THE STRUCTURE EXCEEDS THE REQUIRED HEIGHT
 LIMITATION. [ZLDR S.94-72(A)(2)]
  
 3.) HEIGHT OF NEW WALL/FENCE/GATE(S) SHALL BE PROVIDED
 IN THE SITE PLAN. THE HEIGHT SHALL NOT EXCEED THE
 STANDARDS PROVIDED IN ZLDR S.94-302(B).
  
 4.) SETBACK DISTANCE (FROM THE PROPERTY LINE(S)) SHALL
 BE PROVIDED FOR THE FOLLOWING: POOL EQUIPMENT AND A/C
 PAD, PROPOSED WALK (EAST SIDE OF RESIDENCE).
  
 5.) PROVIDE MORE INFORMATION ON THE "SPORT COURT"
 ILLUSTRATED ON THE SOUTHEAST SIDE OF THE PROPOSED
 RESIDENCE. SETBACK DISTANCE FROM THE PROPERTY LINE(S)
 SHALL BE PROVIDED IN THE SITE PLAN.
  
 6.) A CIRCULAR DRIVEWAY IS PERMITTED; HOWEVER, EACH
 DRIVEWAY OPENING SHALL NOT EXCEED 10 FT. IN WIDTH.
 PLEASE PROVIDE DIMENSIONS TO DEMONSTRATE COMPLIANCE.
 [ZLDR S.94-312(1)]
  
 7.) A SEPARATE LANDSCAPE PERMIT SHALL BE SUBMITTED AND
 APPROVED PRIOR TO ZONING APPROVAL OF THIS PERMIT.
  
 8.) THERE SHALL BE AT LEAST 1,000 SQ. FT. OF LANDSCAPED
 AREA WITHIN THE REQUIRED FRONT YARD OF THE PROPERTY
 (AREA WITHIN THE FIRST 25 FT. FROM THE NORTH PROPERTY).
 PLEASE PROVIDE FRONT YARD CALCULATIONS TO DEMONSTRATE
 COMPLIANCE. [ZLDR S.94-482(A)]
  
  
  
 NOTES:
  
 * SEPARATE PERMITS REQUIRED FOR: SWIMMING POOL,
 LANDSCAPING
  
 * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS.
  
 * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE
 QUESTIONS.
  
 * ZONE: SF7
  