Plan Review Details - Permit 21091170
Plan Review Stops For Permit 21091170
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2021-11-05 Cont ID  
Sent By cpuell Date 2021-11-05 Time 15:10 Rev Time 0.00
Received By cpuell Date 2021-11-05 Time 15:10 Sent To  
Notes
2021-11-05 15:13:11ADDRESS IS OK FOR PROJECT

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2022-03-01 Cont ID  
Sent By lmarchan Date 2022-03-01 Time 14:55 Rev Time 0.00
Received By lmarchan Date 2022-03-01 Time 14:55 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 07:57 Rev Time 0.00
Received By jwitmer Date 2022-03-01 Time 06:43 Sent To  
Notes
2022-03-01 07:57:26COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected] THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 08:43 Rev Time 0.00
Received By jwitmer Date 2021-12-27 Time 08:42 Sent To  
Notes
2021-12-27 08:43:24COMMERCIAL ASBESTOS
 TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-04-26 Cont ID  
Sent By jwitmer Date 2022-04-26 Time 15:38 Rev Time 0.00
Received By jwitmer Date 2022-04-26 Time 15:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2022-03-21 Cont ID  
Sent By jwitmer Date 2022-03-21 Time 08:16 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2022-03-21 08:16:37WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. MARCH 21ST/ 2021
 ACTION: DENIED
  
 1) COMPLIED.
 2) COMPLIED.
  
 3)SEMI-COMPLIED.
 3A)
  
 4B)
  
 4C) 3RD REQUEST. SEE 4D. 206.2.5 206.2.5 RESTAURANTS
 AND CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 BARS, INCLUDING RAISED OR SUNKEN DINING AREAS, AND
 OUTDOOR DINING AREAS.
  
 4D) 3RD REQUEST. PLEASE NOTE THE MAIN BAR NO LONGER HAS
 AN ACCESSIBLE SEAT AT THE BAR THAT NEEDS TO SHOW
 COMPLIANCE WITH WEST PALM BEACH DEVELOPMENT
 SERVICES-CONSTRUCTION SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 27TH/ 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 104 THE CONFERENCE ROOM NOR THE
 DIMENSIONS TO DETERMINE THE OCCUPANT LOAD. SHEET G1-1
 AREA OF WORK SHOWS THE SQ. FT. OF AREA PER ROOM BUT NOT
 THE OCCUPANT LOAD, NOR THE OCCUPANT LOAD FACTOR. 2020
 FBC-BUILDING TABLE 1005.4.
  
 2-3) COMPLIED.
  
 4A-D) COMPLIED.
  
  
 5) SHEET A4.4 NOW SHOWS A RETRACTABLE STAGE BUT THE
 PLAN DOES NOT SHOW THE HEIGHT OF THE STAGE WHEN IN THE
 HORIZONTAL POSITION, NOR COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY CODE SECTION 405.2 SLOPE, EDGE
 PROTECTION 405.9 AND POSSIBLY 405.8 HANDRAILS.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 07:58 Rev Time 0.00
Received By jwitmer Date 2022-03-01 Time 06:43 Sent To  
Notes
2022-03-01 07:58:44WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 27TH/ 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 104 THE CONFERENCE ROOM NOR THE
 DIMENSIONS TO DETERMINE THE OCCUPANT LOAD. SHEET G1-1
 AREA OF WORK SHOWS THE SQ. FT. OF AREA PER ROOM BUT NOT
 THE OCCUPANT LOAD, NOR THE OCCUPANT LOAD FACTOR. 2020
 FBC-BUILDING TABLE 1005.4.
  
 2) COMPLIED.
  
 2A) COMPLIED.
  
 2B) 2ND REQUEST. MEETING ROOMS 110A & B BOTH AE MISSING
 EXIT LIGHTS SHOWING THE MEANS OF EGRESS TO AN EXIT.
 SECONDLY TO GET TO THE MEETING ROOM 110A YOU WILL NEED
 TO GO THROUGH ROOM 110B, THIS CAN BE COMPLETED IF EXITS
 LIGHT IS SHOWN IN ROOM !!0 A. THIS ACCORDION WALL WOULD
 NEED TO BECOME A PANEL WALL SYSTEM FOR A MAN DOOR TO
 OCCUR. 2020 FBC-BUILDING CODE 1016.2 EGRESS THROUGH
 INTERVENING SPACES. THE 2ND ISSUE IS THE ISSUE OF
 EXITING THROUGH EXTERIOR SERVICE YARD, SEE SECTION
 1016.2.5.
 1ST ROUND COMMENT. MEETING ROOM 110A AND PREP AREA,
 KITCHEN SHOW EXITING THROUGH TO THE SERVICE YARD 120,
 YOU CANNOT EXIT THROUGH A KITCHEN SUPPLY ROOMS OR AREAS
 USED FOR SIMILAR PURPOSES. SEE SECTION 1016.2.5.
  
 2C) 2ND REQUEST. MEETING ROOM 110A PLEASE SHOW PATH OF
 TRAVEL TO THE RESTROOMS. PATH OF TRAVEL TO THE
 RESTROOMS CAN NOT GO THROUGH THE PREP AREA. THE PREP
 AREA IS TO BE USED ONLY FOR THE BACK OF HOUSE STAFF
 ONLY.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES. CONSTRUCTION DOCUMENTS
 SHALL BE SUFFICIENT CLARITY TO INDICATE THE LOCATION,
 NATURE AND EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE PROVISIONS OF THIS
 CODE AND RELEVANT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL.
  
 2020FBC-B 1016.2 .5. EGRESS THROUGH INTERVENING SPACES.
  
  
  
 2D-E) COMPLIED.
  
  
 3A-B) COMPLIED.
  
 3C)2ND REQUEST. THE CORRIDOR 101 MAY HAVE A OCCUPANT
 LOAD OF 45, THERE HAS BEEN NO IDENTIFICATION OF WHAT
 EXITING ROOMS 110 A& B WILL USE, AGAIN THESE ROOMS
 CANNOT EXIT THROUGH THE KITCHEN PREP AREA MEANING THEY
 HAVE TO USE THE CORRIDOR 101 TO GAIN ACCESS TO ONE OF
 THE 2 EXIT DIRECTIONAL LIGHTS SHOWN ON THE LIFE SAFETY
 PLAN.
  
 1ST ROUND OF COMMENTS.
 THE RECONFIGURATION OF CORRIDOR 101 WITH AN OCCUPANT
 LOAD OF OVER 30 ASSEMBLY OCCUPANCY REQUIRES THE
 CORRIDOR AND OPENING PROTECTIVES TO BE IN ACCORDANCE
 WITH THE 2020 FBC-BUILDING CODE TABLE 1020.1, SECTION
 1020.1 CONSTRUCTION AND TABLE 716.5.
  
 3D) 2ND REQUEST. THE RECONFIGURATION OF CORRIDOR 101
 WITH AN OCCUPANT LOAD OF OVER 30 ASSEMBLY OCCUPANCY
 REQUIRES THE CORRIDOR TO BE 1-HOUR FIRE RATED AS PER
 SECTION & TABLE 1020.1. SHEET M2-0 DOES NOT SHOW FIRE
 DAMPERS IN EITHER THE WALLS OR CEILING. SEE SECTION
 1020.5 AIR MOVEMENT IN CORRIDORS, ALSO SECTION
 717.5.4.1 CORRIDORS.
  
 3)SEMI-COMPLIED.
 3A) THE FLOOR PLAN SHOWS 6 ACCESSIBLE SEATS WHEREAS THE
 OCCUPANT LOAD IS SHOW AS 194 X 0.05= 9.7 OR 10
 ACCESSIBLE SEATS REQUIRED.
  
 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4B) SEMI-COMPLIED, NEEDS MORE ACCESSIBLE SEATING. 226.2
 DISPERSION. DINING SURFACES AND WORK SURFACES REQUIRED
 TO COMPLY WITH 902 SHALL BE DISPERSED THROUGHOUT THE
 SPACE OR FACILITY CONTAINING DINING SURFACES AND WORK
 SURFACES.
  
 4C) SEMI-COMPLIED. SEE 4D. 206.2.5 206.2.5 RESTAURANTS
 AND CAFETERIAS. IN RESTAURANTS AND CAFETERIAS, AN
 ACCESSIBLE ROUTE SHALL BE PROVIDED TO ALL DINING AREAS,
 BARS, INCLUDING RAISED OR SUNKEN DINING AREAS, AND
 OUTDOOR DINING AREAS.
  
 4D) A ACCESSIBLE BAR, THERE ARE NOTES 1 & 2 ON THE
 PLANS FOE CLEAR FLOOR SPACE AND COUNTER TOPS BUT SAYING
 THIS WILL BE COMPLETED DOES NOT SHOW CODE COMPLIANCE.
 SHEET A4.2 DETAIL A1 SHOWS A FLIP UP ACCESSIBLE PORTION
 OF THE BAR, THIS IS NOT CONSIDERED AN ACCESSIBLE
 ELEMENT. THE PATRON ONLY NEEDS TO WHEEL UP IN THEIR
 WHEELCHAIR FOR THE BAR TO BE CONSIDERED ACCESSIBLE.
  
 2020 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.2.1.
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "CODE SECTIONS SHALL
 NOT BE CITED AS A WHOLE OR IN PART, NOR THE TERM
 "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR
 SPECIFIC INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1SR ROUND OF COMMENTS. 902.1. DINING SURFACES AND WORK
 SURFACES SHALL COMPLY WITH 902.2 AND 902.3. ADVISORY
 902.1 GENERAL. DINING SURFACES INCLUDE, BUT ARE NOT
 LIMITED TO, BARS, TABLES, LUNCH COUNTERS, AND BOOTHS.
 EXAMPLES OF WORK SURFACES INCLUDE WRITING SURFACES,
 STUDY CARRELS, STUDENT LABORATORY STATIONS, BABY
 CHANGING AND OTHER TABLES OR FIXTURES FOR PERSONAL
 GROOMING, COUPON COUNTERS, AND WHERE COVERED BY THE ADA
 SCOPING PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 4E)(1) SEMI-COMPLIED. NEED ADDITIONAL ACCESSIBLE SEATS
 IN ROOM 107. 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR
 FLOOR SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(2) 2ND REQUEST. PLEASE NOTE STATING THE OWNER IS
 GOING TO PURCHASE THE FURNITURE DOES NOT RELINQUISH THE
 DESIGNER OF RECORD SHOWING CODE COMPLIANCE UNDER THE
 2020 FBC-ACCESSIBILITY CODE NOR THE FEDRAL ADA WHERE
 LAWSUITS ARE FILED PLEASE TAKE NOTE OF THIS!!!!!
 1ST ROUND OF COMMENTS. 902.3 HEIGHT. THE TOPS OF DINING
 SURFACES AND WORK SURFACES SHALL BE 28 INCHES MINIMUM
 AND 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) COMPLIED.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-27 Cont ID  
Sent By jwitmer Date 2021-12-27 Time 13:14 Rev Time 0.00
Received By jwitmer Date 2021-12-27 Time 08:42 Sent To  
Notes
2021-12-27 13:14:31WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21091170
 ADD: 1900 PALM BEACH LAKES BLVD.
 CONT: CONKLING & LEWIS
 TEL: 561-833-4441
 E-MAIL: KLEWIS@CONKLING AND LEWIS.COM
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. DEC. 27TH/ 2021
 ACTION: DENIED
  
 1) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 104 THE CONFERENCE ROOM NOR THE
 DIMENSIONS TO DETERMINE THE OCCUPANT LOAD. SHEET G1-1
 AREA OF WORK SHOWS THE SQ. FT. OF AREA PER ROOM BUT NOT
 THE OCCUPANT LOAD, NOR THE OCCUPANT LOAD FACTOR. 2020
 FBC-BUILDING TABLE 1005.4.
  
 2) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 110 A & B THE MEETING ROOM NOR THE
 DIMENSIONS TO DETERMINE THE OCCUPANT LOAD. SHEET G1-1
 AREA OF WORK SHOWS THE SQ. FT. OF AREA 332SQ. FT. BUT
 NOT THE OCCUPANT LOAD, NOR THE OCCUPANT LOAD FACTOR.
 2020 FBC-BUILDING TABLE 1005.4.
 STANDING 332/5 = 67 OCCUPANTS, CHAIRS 332/7= 48 WITH
 THE MOST RESTRICTIVE USE THE OCCUPANT LOAD WOULD BE
 OVER 50 REQUIRING THE DOORS TO SWING IN THE DIRECTION
 OF EXIT TRAVEL. 1010.1.2.1.
  
 2A) MEETING ROOMS 110A & 100B THE COMBINED OCCUPANT
 LOADS OF BOTH ROOMS IS OVER 30 WHICH WOULD REQUIRE THE
 CORRIDOR OUTSIDE ROOM 110 A TO BE A 1 HOUR FIRE RATED
 CORRIDOR. WHEN YOU TAKE THE OCCUPANT LOAD OF ROOM 110A
 AND THE ROOMS 121 PREP AREA, STORAGE 119, MECH. 118,
 STORAGE 117 AND DISHWASHING ROOM 121 THE TOTAL AREA,
 THE OCCUPANT LOAD IS OVER 30 REQUIRING A FIRE RATED
 CORRIDOR, THE OTHER ISSUE IS YOU CAN NOT EXIT THROUGH A
 KITCHEN SUPPLY ROOMS OR AREAS USED FOR SIMILAR
 PURPOSES. SEE SECTION 1016.2.5.
  
 2B) MEETING ROOM 110A AND PREP AREA, KITCHEN SHOW
 EXITING THROUGH TO THE SERVICE YARD 120, YOU CAN NOT
 EXIT THROUGH A KITCHEN SUPPLY ROOMS OR AREAS USED FOR
 SIMILAR PURPOSES. SEE SECTION 1016.2.5.
  
 2C) MEETING ROOM 110A PLEASE SHOW PATH OF TRAVEL TO THE
 RESTROOMS. 107.2.1.2. ADDITIONAL INFORMATION IS
 REQUIRED.
  
 2D) WILL THIS BANQUET HALL EVER BE RENTED OUT? WILL THE
 BUILDING EVER BE RENTED TO MORE THAN ONE PARTY AT THE
 SAME TIME, ANOTHER WORDS MULTIPLE MEETING AND OR
 PARTIES BY DIFFERENT PEOPLE?
  
 2E) DOORS 120A & 120B SHEET A6.0 INDICATE EXISTING, MAG
 LOCK, MOTION, REQUEST TO EXIT, RELEASE CARD, THESE
 DOORS NOW WITH THE RECONFIGURE OF SPACE AND USE NEED TO
 HAVE COMPLIANCE WITH 2020 FBC-BUILDING SECTION
 1010.1.10 PANIC AND FIRE EXIT HARDWARE.
  
 3) THE LIFE SAFETY PLAN DOES NOT PROVIDE THE FURNITURE
 LAYOUT FOR THE ROOM 108 THE BAR ROOM THE PLAN INDICATES
 AN OCCUPANT LOAD OF 35. SHEET G1-1 AREA OF WORK SHOWS
 THE SQ. FT. OF AREA PER ROOM AT 756 SQ. FT. AND
 OCCUPANT LOAD OF 35. THE OCCUPANT LOAD FACTOR IS NOT
 GIVEN PER 2020 FBC-BUILDING TABLE 1005.4.
 PLEASE NOTE ROOM 108 (BAR) SHOULD HAVE THE OCCUPANT
 LOAD BROKEN UP TO BAR TAKEN AT 5 SQ. FT. STANDING /
 OCCUPANT, 15 SQ. FT. TABLE AND CHAIRS & BACK OF BAR @
 200. IF THE OCCUPANT LOAD, THEN IS 50 AND OVER THE 2
 EGRESS DOORS WILL NEED TO ALSO SHOW COMPLIANCE WITH:
 2020 FBC-BUILDING SECTION 1010.1.2.1 WHEN THE OCCUPANT
 LOAD WOULD BE 50 OR MORE THE DOORS TO SWING IN THE
 DIRECTION OF EXIT TRAVEL. PLEASE SHOW 2 MEANS OF
 EGRESS.
  
 3A) PLEASE NOTE THE BANQUET HALL ROOM 107 NO WORK
 OCCURRING AS SHOWN. ASSUMING DOOR 107A THE DOOR SET IS
 72 INCHES WIDE YOU CAN NOT TAKE 360 OCCUPANT LOAD. YOU
 MUST TAKE THE REDUCED OPENING OF 70 INCHES DOOR STOPS
 DOORS SWING 180 DEGREES GIVING YOU A OCCUPANT LOAD OF
 340. THE SAME WITH DOOR 107B A REDUCED OPENING OF 34
 INCHES AND OCCUPANT LOAD OF 170. EVEN THOUGH NO WORK IS
 SHOWN FOR THIS ROOM IF THE DOUBLE DOORS 107A CAN NOT BE
 USED (FIRE) PART OF THE OCCUPANT LOAD WOULD NEED TO BE
 DIRECTED TO THE FRONT ENTRY DOORS. THE ISSUE WOULD BE
 DOOR 101 WOULD NEED TO BE IN THE DIRECTION OF EGRESS
 TRAVEL. THE FRONT ENTRY DOOR 101 IS SHOWN ON THIS PLAN
 AS THE ENTRY LOBBY. 2020 FBC-B 1005.5.
  
 3B) DOOR 101 WILL NEED TO SWING IN THE DIRECTION OF
 EGRESS TRAVEL TOWARD THE FRONT ENTRANCE. 2020
 FBC-BUILDING SECTION 1010.1.2.1 WHEN THE OCCUPANT LOAD
 WOULD BE 50 OR MORE THE DOORS TO SWING IN THE DIRECTION
 OF EXIT TRAVEL.
 3C) THE RECONFIGURATION OF CORRIDOR 101 WITH AN
 OCCUPANT LOAD OF OVER 30 ASSEMBLY OCCUPANCY REQUIRES
 THE CORRIDOR AND OPENING PROTECTIVES TO BE IN
 ACCORDANCE WITH THE 2020 FBC-BUILDING CODE TABLE
 1020.1, SECTION 1020.1 CONSTRUCTION AND TABLE 716.5.
  
 3D) THE RECONFIGURATION OF CORRIDOR 101 WITH AN
 OCCUPANT LOAD OF OVER 30 ASSEMBLY OCCUPANCY REQUIRES
 THE CORRIDOR TO BE 1-HOUR FIRE RATED AS PER SECTION &
 TABLE 1020.1. SHEET M2-0 DOES NOT SHOW FIRE DAMPERS IN
 EITHER THE WALLS OR CEILING. SEE SECTION 1020.5 AIR
 MOVEMENT IN CORRIDORS, ALSO SECTION 717.5.4.1
 CORRIDORS.
  
 4) THE LIFE SAFETY SHEET DOES NOT SHOW COMPLIANCE WITH
 THE 2020 FBC-ACCESSIBILITY CODE.
 3A) 226.1 WHERE DINING SURFACES ARE PROVIDED FOR THE
 CONSUMPTION OF FOOD OR DRINK, AT LEAST 5 PERCENT OF THE
 SEATING SPACES AND STANDING SPACES AT THE DINING
 SURFACES SHALL COMPLY WITH 902.
  
 4B) 226.2 DISPERSION. DINING SURFACES AND WORK SURFACES
 REQUIRED TO COMPLY WITH 902 SHALL BE DISPERSED
 THROUGHOUT THE SPACE OR FACILITY CONTAINING DINING
 SURFACES AND WORK SURFACES.
  
 4C) 206.2.5 206.2.5 RESTAURANTS AND CAFETERIAS. IN
 RESTAURANTS AND CAFETERIAS, AN ACCESSIBLE ROUTE SHALL
 BE PROVIDED TO ALL DINING AREAS, BARS, INCLUDING RAISED
 OR SUNKEN DINING AREAS, AND OUTDOOR DINING AREAS.
  
 4D) 902.1. DINING SURFACES AND WORK SURFACES SHALL
 COMPLY WITH 902.2 AND 902.3. ADVISORY 902.1 GENERAL.
 DINING SURFACES INCLUDE, BUT ARE NOT LIMITED TO, BARS,
 TABLES, LUNCH COUNTERS, AND BOOTHS. EXAMPLES OF WORK
 SURFACES INCLUDE WRITING SURFACES, STUDY CARRELS,
 STUDENT LABORATORY STATIONS, BABY CHANGING AND OTHER
 TABLES OR FIXTURES FOR PERSONAL GROOMING, COUPON
 COUNTERS, AND WHERE COVERED BY THE ADA SCOPING
 PROVISIONS, EMPLOYEE WORKSTATIONS.
  
 4E)(1) 902.2 CLEAR FLOOR OR GROUND SPACE. A CLEAR FLOOR
 SPACE COMPLYING WITH 305 POSITIONED FOR A FORWARD
 APPROACH SHALL BE PROVIDED. KNEE AND TOE CLEARANCE
 COMPLYING WITH 306 SHALL BE PROVIDED.
  
 4E)(2) 902.3 HEIGHT. THE TOPS OF DINING SURFACES AND
 WORK SURFACES SHALL BE 28 INCHES MINIMUM AND 34 INCHES
 MAXIMUM ABOVE THE FINISH FLOOR OR GROUND.
  
 5) SHEET A1.1 INDICATES THERE IS TO BE A NEW
 RETRACTABLE WALL MOUNTED STAGE, REFER TO STRUCTURAL
 DRAWINGS? WHERE. PLEASE PROVIDE FOR THE RETRACTABLE
 STAGE HOW VERTICAL ACCESSIBILITY IS GOING TO BE
 ACHIEVED. SHOW COMPLIANCE WITH THE 2020
 FBC-ACCESSIBILITY SECTION 201.1.1 VERTICAL
 ACCESSIBILITY.
  
 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE WORKING
 FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-04-12 Cont ID  
Sent By fgiaquin Date 2022-04-12 Time 21:25 Rev Time 0.00
Received By fgiaquin Date 2022-04-12 Time 20:48 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2022-01-04 Cont ID  
Sent By fgiaquin Date 2022-01-04 Time 21:53 Rev Time 0.00
Received By fgiaquin Date 2022-01-04 Time 20:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2022-03-17 Cont ID  
Sent By   Date 2022-03-17 Time   Rev Time 0.00
Received By jcclark Date 2022-03-17 Time 12:57 Sent To  
Notes
2022-03-17 13:00:39OCCUPANCY IS REQUIRED TO HAVE A MONITORED FIRE ALARM
 THAT NOTIFIES THE OCCUPANTS IN CASE OF EMERGENCY.
 ENSURE THE FIRE ALARM IS MAINTAINED AND REMAINS IN
 SERVICE CHANGES TO THE FACILITY MAY REQUIRE AN
 EVALUATION OF THE FIRE ALARM BY A LICENSED CONTRACTOR.
 ANY FIRE ALARM WORK WOULD REQUIRE A SEPARATE FIRE ALARM
 PERMIT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-02-28 Cont ID  
Sent By   Date 2022-02-28 Time   Rev Time 0.00
Received By bdolan Date 2022-02-28 Time 13:26 Sent To  
Notes
2022-02-28 13:37:21OCCUPANCY IS REQUIRED TO HAVE A MONITORED ALARM SYSTEM
 THAT PROVIDES NOTIFICATION TO OCCUPANTS IN CASE OF A
 FIRE INCIDENT. SYSTEM MUST ALSO SUPERVISE KITCHEN
 PROTECTION EQUIPMENT.
  
 ENSURE THAT EXISTING ALARM IS MAINTAINED AND REMAINS IN
 SERVICE. ANY CHANGES TO THE FACILITY MAY REQUIRE AN
 EVALUATION OF FIRE ALARM SYSTEM BY A LICENSED
 CONTRACTOR. ANY FIRE ALARM WORK WILL REQUIRE A SEPERATE
 PERMIT.
  
 PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date   Cont ID  
Sent By   Date 2021-11-17 Time   Rev Time 0.00
Received By jcclark Date 2021-11-17 Time 12:26 Sent To  
Notes
2021-11-17 12:27:04PER CITY CODES, ALL WORK IS SUBJECT TO FIELD
 INSPECTIONS AND APPROVAL.
  
 JOSEPH CLARK
 OFFICE OF THE FIRE MARSHAL
 561-804-4748
 [email protected]
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2022-04-13 Cont ID  
Sent By aoliver Date 2021-11-17 Time 08:06 Rev Time 0.00
Received By aoliver Date 2021-11-17 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 17:22 Rev Time 0.00
Received By medwards Date 2022-04-15 Time 09:59 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2022-03-16 Time 07:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-03-01 Cont ID  
Sent By lmarchan Date 2022-03-01 Time 14:54 Rev Time 0.00
Received By lmarchan Date 2022-02-03 Time 09:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-04 Cont ID  
Sent By fgiaquin Date 2022-01-04 Time 21:53 Rev Time 0.00
Received By fgiaquin Date 2021-11-05 Time 11:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 17:21 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 17:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2022-04-06 Cont ID  
Sent By medwards Date 2022-04-06 Time 16:12 Rev Time 0.00
Received By medwards Date 2022-04-06 Time 16:12 Sent To  
Notes
2022-04-06 16:12:563RD REVIEW FMC
 PERMIT: 21091170
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE TAKE ANOTHER LOOK AT THE VAV-5 CALCULATIONS.
 I BELIEVE THE NUMBERS ARE INCORRECT. THE REQUIRED
 OUTDOOR AIR- CFM?S PER PERSON SHOULD BE 7.5 NOT 0. THE
 REQUIRED OUTDOOR AIR- CFM?S PER FT. SHOULD BE 0.12 NOT
 0.06. PLEASE ADJUST AND PROVIDE THE CORRECT TOTALS. FMC
 403.3.1.1 AND TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-24 Cont ID  
Sent By medwards Date 2022-02-24 Time 13:10 Rev Time 0.00
Received By medwards Date 2022-02-24 Time 13:10 Sent To  
Notes
2022-02-24 13:10:422ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091170
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.0: THE BANQUET HALL VAV-1 AND VAV-2 REQUIRE
 1017 CFM OF OUTDOOR AIR EACH. THE PROVIDED AIR FOR EACH
 SHOULD AT LEAST BE THE MINIMUM REQUIRED OUTDOOR AIR.
  
 2) PLEASE TAKE A SECOND LOOK AT VAV-3, VAV-5, VAV-7,
 VAV-9. IT APPEARS THAT THE OCCUPANCY DENSITY IS THE
 DIFFERENCE BETWEEN THE NUMBERS SHOWN ON SHEET M3.0 IN
 THESE AREAS AND THE NUMBERS THAT I CALCULATE FOR EACH
 USE OF SPACE LISTED ABOVE. PLEASE SEE THE SECOND
 SENTENCE OF SECTION 403.3.1.1 COPIED BELOW FOR YOUR
 CONVENIENCE.
  
 FBC M 403.3.1.1 : THE OCCUPANT LOAD UTILIZED FOR DESIGN
 OF THE VENTILATION SYSTEM SHALL BE NOT LESS THAN THE
 NUMBER DETERMINED FROM THE ESTIMATED MAXIMUM OCCUPANT
 LOAD RATE INDICATED IN TABLE 403.3.1.1. VENTILATION
 RATES FOR OCCUPANCIES NOT REPRESENTED IN TABLE
 403.3.1.1 SHALL BE THOSE FOR A LISTED OCCUPANCY
 CLASSIFICATION THAT IS MOST SIMILAR
 IN TERMS OF OCCUPANT DENSITY, ACTIVITIES AND BUILDING
 CONSTRUCTION; OR SHALL BE DETERMINED BY AN APPROVED
 ENGINEERING ANALYSIS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-30 Cont ID  
Sent By medwards Date 2021-11-30 Time 16:18 Rev Time 0.00
Received By medwards Date 2021-11-30 Time 15:54 Sent To  
Notes
2021-11-30 16:18:561ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091170
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M3.0: PLEASE PROVIDE THE OUTDOOR AIR
 CALCULATIONS BASED ON THE OCCUPANCY CLASSIFICATION IN
 FBC M TABLE 403.3.1.1.
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE BASED ON FBC M 403.3.1.1 AND TABLE
 403.3.1.1 AND NOT THE ARCHITECTURAL DRAWINGS. REMINDER:
 FOOTNOTE A OF TABLE 403.3.1.1 ALLOWS THE DESIGNER TO
 USE THE NET OCCUPIABLE FLOOR AREA FOR THE CALCULATIONS.
 I ASSUME WHEN I SEE THE SQUARE FOOTAGE IN THE
 CALCULATIONS THAT THIS IS WHAT WAS USED. THE
 CALCULATIONS APPEAR TO BE LOW.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By rwbrown Date 2022-04-04 Time 09:31 Rev Time 0.00
Received By rwbrown Date 2022-04-04 Time 09:31 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2021-12-14 Cont ID  
Sent By abelisle Date 2021-12-14 Time 16:57 Rev Time 0.00
Received By abelisle Date 2021-12-07 Time 18:22 Sent To  
Notes
***NONE***

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2022-06-08 Cont ID  
Sent By shill Date 2022-06-08 Time 09:08 Rev Time 0.00
Received By shill Date 2022-06-08 Time 09:08 Sent To  
Notes
2022-06-08 09:08:59INSPECTIONS, REVIEWED BY REG

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-05-05 Cont ID  
Sent By medwards Date 2022-05-05 Time 17:22 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 17:22 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-04-13 Cont ID  
Sent By pvalenti Date 2022-04-13 Time 16:02 Rev Time 0.00
Received By pvalenti Date 2022-04-13 Time 15:48 Sent To  
Notes
2022-04-06 16:14:02MECHANICAL DIGITAL SIGNATURES APPROVED ME

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-01 Cont ID  
Sent By jwitmer Date 2022-03-01 Time 07:59 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2022-01-04 Cont ID  
Sent By fgiaquin Date 2022-01-04 Time 21:53 Rev Time 0.00
Received By fgiaquin Date 2022-01-04 Time 21:53 Sent To  
Notes
***NONE***