Plan Review Details - Permit 21091154
Plan Review Stops For Permit 21091154
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By jleahy Date 2021-10-22 Time 10:26 Rev Time 0.00
Received By jleahy Date 2021-10-22 Time 10:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-06 Cont ID  
Sent By pleduc Date 2021-10-06 Time   Rev Time 0.00
Received By pleduc Date 2021-10-06 Time 11:36 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-27 Time   Rev Time 0.00
Received By aoliver Date 2021-10-25 Time 11:38 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-22 Cont ID  
Sent By jleahy Date 2021-10-22 Time 10:27 Rev Time 0.00
Received By jleahy Date 2021-10-04 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2021-10-14 Cont ID  
Sent By medwards Date 2021-10-14 Time 08:01 Rev Time 0.00
Received By medwards Date 2021-10-14 Time 08:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By ccole Date 2021-10-27 Time 13:21 Rev Time 0.00
Received By ccole Date 2021-10-27 Time 12:50 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-19 Cont ID  
Sent By ccole Date 2021-10-19 Time 07:21 Rev Time 0.00
Received By ccole Date 2021-10-18 Time 17:20 Sent To  
Notes
2021-10-19 07:23:221ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21091154
 10/18/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P2 & P4: PROVIDE EQUIPMENT SCHEDULES AND
 SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE NEW DRAIN
 PUMP AND WASTE EVAC UNIT- SECTIONS 712.1 & 713.1 FBC P.
  
 2) P2 & P4: PROVIDE AN ENLARGED PIPING DRAWING FOR THE
 DRAIN PUMP SHOWING THE LOCATIONS OF THE REQUIRED FULL
 OPEN VALVE AND CHECK VALVE- SECTION 712.2. FBC P. SHOW
 ALL COMPONENTS OF THE SYSTEM WILL BE IN ACCESSIBLE
 LOCATIONS.
  
 3) P2 & P4: PLEASE REFER TO SECTIONS 713.4- 713.7 FBC
 P. AND PROVIDE MORE INFORMATION ABOUT THE WASTE EVAC
 UNIT. INDICATE THE PURPOSE OF THE UNIT, AND WHAT TYPE
 OF FLUIDS WILL BE DRAINED THROUGH IT. IS THE UNIT A
 COMPONENT OF A LARGER VACUUM SYSTEM?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By ccole Date 2021-10-27 Time 13:04 Rev Time 0.00
Received By ccole Date 2021-10-27 Time 13:04 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-22 Cont ID  
Sent By jleahy Date 2021-10-22 Time 10:26 Rev Time 0.00
Received By jleahy Date 2021-10-22 Time 10:23 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved