Plan Review Details - Permit 21091144
Plan Review Stops For Permit 21091144
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-03-16 Cont ID  
Sent By rmcdouga Date 2022-03-16 Time 17:14 Rev Time 0.00
Received By rmcdouga Date 2022-03-16 Time 14:06 Sent To  
Notes
2022-03-16 17:13:57GENERATORS REQUIRE A SEPARATE PERMIT. SEE SHEET A-110.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-12-06 Cont ID  
Sent By rmcdouga Date 2021-12-06 Time 17:16 Rev Time 0.00
Received By rmcdouga Date 2021-11-19 Time 16:07 Sent To  
Notes
2021-12-06 17:47:51PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SEVENTH EDITION (2020)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) I SAW AN INDEX PAGE FOR THE STRUCTURAL SHEETS.
 HOWEVER, I DID NOT SEE A REVISED INDEX PAGE WITH THE
 PLAN SHEETS AND THE REVISIONS OF EACH SHEET LISTED FOR
 THE ARCHITECTURAL, LIFE SAFETY OR MEP PLANS. FBC
 107.2.1
  
 2) SPECIFY THE WIND PRESSURES FOR THE ROOF TOP
 GENERATOR FOR THE PENTHOUSE. PROVIDE ANCHORING DETAILS
 AND CALCULATIONS FOR THE GENERATOR TO SHOW THAT IT WILL
 RESIST THE WINDLOAD PRESSURES. FBC 107.2.1.2
  
 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS WITH THE
 WEIGHT AND DIMENSIONS FOR THE PENTHOUSE GENERATOR. FBC
 107.2.1
  
 4) CLEARLY SHOW THAT THE GENERATOR'S EXHAUST IS TEN
 FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1
 INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR
 INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET
 (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT,
 SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS,
 ALLEYS, PARKING LOTS AND LOADING DOCKS.
  
 5) ON SHEET A-790 DETAIL 1, THE UNIT A KITCHEN FLOOR
 PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40"
 CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES
 REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 2-3/8")
  
 6) ON SHEET A-792 DETAIL 2, THE UNIT F KITCHEN FLOOR
 PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40"
 CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES
 REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 3-1/2")
  
 7) THERE WERE SOME REVISED PAGES THAT DID NOT APPEAR ON
 YOUR NARRATIVE, SUCH AS SHEETS A-137, A-138 AND A-139.
 THERE WERE ALSO SOME SHEETS ON THE NARRATIVE THAT I
 COULD NOT FIND IN THE REVISED PLANS SUCH AS G-9 AND
 G-10. FBC 107.2.1
  
 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH
 OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-11-18 Cont ID  
Sent By jleahy Date 2021-11-18 Time 13:47 Rev Time 0.00
Received By jleahy Date 2021-11-18 Time 13:47 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2022-02-14 Cont ID  
Sent By rrossano Date 2022-02-14 Time   Rev Time 0.00
Received By rrossano Date 2022-02-14 Time   Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2021-11-08 Cont ID  
Sent By rrossano Date 2021-11-08 Time 09:18 Rev Time 0.00
Received By rrossano Date   Time   Sent To  
Notes
2021-11-08 09:32:49RESPONSE LETTER MENTIONS 3 IN. SPRINKLER LINE ADDED TO
 STORM. PLEASE CLARIFY, AND SHOW CLEARLY ON UTILITY
 SHEET C6.00 WITH CLOUD/NOTE/ETC. PLEASE NOTE THAT
 CHANGE IN WATER DEMANDS REQUIRES ASBUILT REVISION VIA
 FORMAL ENGINEERING RESUBMITTAL.
  
 FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR
 CONCERNS, THANKS.
 RICK ROSSANO, SENIOR PROJECT COORDINATOR,
 CITY OF WPB ENGINEERING SERVICES DEPARTMENT
 DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE:
 (561) 246-9525
 EMAIL: [email protected]
 HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING-
 STANDARDS-DETAILS
2021-11-08 08:59:19PLEASE ADDRESS PLUMBING COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By pleduc Date 2021-10-29 Time   Rev Time 0.00
Received By bdolan Date 2021-10-29 Time 12:25 Sent To  
Notes
2021-10-29 12:26:17THE DIVISION OF FIRE PREVENTION HAS NO OBJECTIONS TO
 THE REVISIONS IN THE PLAN SET.
  
 LT. BRIAN DOLAN
 DIVISION OF FIRE PREVENTION
 561-804-4752
 [email protected]

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2022-08-26 Cont ID  
Sent By ccole Date 2022-08-26 Time 17:03 Rev Time 0.00
Received By ccole Date 2022-08-26 Time 16:49 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 4 Status F Date 2022-07-26 Cont ID  
Sent By ccole Date 2022-07-26 Time 11:44 Rev Time 0.00
Received By ccole Date 2022-07-26 Time 10:27 Sent To  
Notes
2022-07-26 11:45:263RD REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 7/26/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN
 SHEETS DO NOT MATCH.
  
 A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS
 AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT
 DRAWING (P-242) AND THE RISER (P-505.
  
 B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON
 LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE,
 HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH
 PIPE. WHICH IS IT?
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2022-05-17 Cont ID  
Sent By ccole Date 2022-05-17 Time 10:53 Rev Time 0.00
Received By ccole Date 2022-05-17 Time 08:22 Sent To  
Notes
2022-05-17 10:54:312ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 2/17/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE ENGINEER OF RECORD HAS STATED IN HIS COMMENT
 RESPONSES THAT THE TWO GAS GENERATORS SHOWN IN THE
 REVISION ARE LEVEL 2 EMERGENCY POWER SUPPLY SYSTEMS
 (EPSS). SEC. 4.4.2 NFPA 11 STATES THAT LEVEL 2 SYSTEMS
 SHALL BE INSTALLED WHERE FAILURE OF THE EPSS TO PERFORM
 IS LESS CRITICAL TO HUMAN LIFE AND SAFETY. AS
 PREVIOUSLY REQUESTED, PLEASE PROVIDE A SPECIFIC LIST OF
 ALL LEVEL 2 LOADS TO BE SUPPLIED BY THE GAS GENERATORS.
  
 2) REFER TO SEC. 7.9.7- 7.9.8 NFPA 110 AND REVISE THE
 DRAWINGS TO SHOW COMPLIANCE: THE GAS SUPPLY LINES TO
 THE GENERATORS SHALL BE CONNECTED ON THE SUPPLY SIDE OF
 THE MAIN GAS SHUTOFF VALVE AND MARKED AS SUPPLYING AN
 EMERGENCY GENERATOR. THE BUILDING?S MAIN GAS SHUTOFF
 VALVE SHALL BE MARKED OR TAGGED TO INDICATE THE
 EXISTENCE OF THE SEPARATE EPS SHUTOFF VALVE.
  
 3) THE FINAL APPROVAL OF THE REVISED MAIN BUILDING
 PLANS CANNOT BE ACCOMPLISHED WITHOUT A FINAL APPROVAL
 OF THE GAS GENERATOR PERMIT- 21021355. PLEASE RESUBMIT
 CORRECTED PLANS CONSISTENT WITH THESE COMMENTS, THE
 GENERATOR PERMIT COMMENTS, AND IN COMPLIANCE WITH NFPA
 37, 54,110 AND THE FBC FG-2017.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By ccole Date 2022-02-17 Time 14:39 Rev Time 0.00
Received By ccole Date 2022-02-17 Time 14:39 Sent To  
Notes
2022-02-17 14:48:052ND REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 2/17/2022
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE ADDITIONAL
 INFORMATION FOR THE TWO GAS GENERATORS. IN REPONSE TO
 THE 1ST REVIEW COMMENTS LISTED BELOW, THE EOR IS
 STATING IN THE COMMENT RESPONSE NARRATIVE THAT THE
 GENERATORS ARE LEVEL 2, NOT 1. THE RISER ON SHEET P-505
 INDICATES LEVEL 2 "STAND-BY" GENERATORS. PLEASE
 INDICATE ON THE PLANS THE SPECIFIC SYSTEMS THAT THE
 GENERATORS ARE SUPPLYING POWER TO. LEVEL 1 STAND-BY
 GENERATORS ACCORDING TO SEC. 4.4.1 NFPA 110 ARE
 INSTALLED WHERE FAILURE OF THE EQUIPMENT TO PERFORM
 COULD RESULT IN LOSS OF HUMAN LIFE OR SERIOUS INJURIES.
 REFER TO SEC. 403.8.3 FBC B.- THE FOLLOWING ARE
 CLASSIFIED AS STANDBY POWER LOADS IN HIGH RISE
 BUILDINGS-
  
 1.VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT
 FOR SMOKEPROOF ENCLOSURES.
 2.ELEVATORS.
 3.WHERE ELEVATORS ARE PROVIDED IN A HIGH-RISE BUILDING
 FOR ACCESSIBLE MEANS OF EGRESS, FIRE SERVICE ACCESS OR
 OCCUPANT SELF-EVACUATION, THE STANDBY POWER SYSTEM
 SHALL ALSO COMPLY WITH SECTIONS 1009, 3007 OR 3008, AS
 APPLICABLE.
  
 SEC. 4.4.1 NFPA 110 LEVEL 1 ESSENTIAL ELECTRICAL
 SYSTEMS:
 LIFE SAFETY ILLUMINATION
 FIRE DETECTION AND ALARM SYSTEMS
 ELEVATORS
 FIRE PUMPS
 PUBLIC SAFETY COMMUNICATIONS SYSTEMS
 INDUSTRIAL PROCESSES WHERE CURRENT INTERRUPTION WOULD
 PRODUCE SERIOUS LIFE SAFETY OR HEALTH HAZARDS
 ESSENTIAL VENTILATING AND SMOKE REMOVAL SYSTEMS
  
 SEE SECTION 403.4.8.4 FBC B FOR LIST OF EMERGENCY POWER
 LOADS. PLEASE NOTE THERE ARE RELATIVE GAS COMMENTS FOR
 THE 30KW GENERATOR INSTALLATION UNDER PERMIT- 21021355.
  
 1ST REVIEW COMMENTS- 11/5/21
  
 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110
 WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO
 SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON
 LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED
 FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER
 PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO
 SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A
 BOILER.
 A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 110 AND
 SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED
 GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE
 POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE
 SEPARATE EPS SHUTOFF VALVES.
  
 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING
 PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW
 COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE
 A BUILDING SHALL BE SEPARATED FROM AREAS OF THE
 BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED
 IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE
 THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE
 RATING SHALL BE REDUCED TO 1 HOUR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By ccole Date 2021-11-05 Time 17:07 Rev Time 0.00
Received By ccole Date 2021-11-05 Time 14:24 Sent To  
Notes
2021-11-05 17:08:121ST REVIEW FBC-2017 FUEL GAS
 PERMIT- 21091144
 11/5/2021
  
 CODES IN EFFECT:
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P505 & P110: PLEASE PLACE A NOTE ON THE PLAN
 INDICATING A SEPARATE PERMIT IS REQUIRED FOR THE
 GENERATOR ON THE ROOF. A FULL GAS REVIEW FOR THE
 GENERATOR IS NOT BEING PERFORMED AT THIS TIME- SECTIONS
 105.1 & 107.1 WPB.
  
 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110
 WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO
 SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON
 LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED
 FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER
 PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO
 SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A
 BOILER.
  
 A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 1110 AND
 SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED
 GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE
 POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE
 SEPARATE EPS SHUTOFF VALVES.
  
 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING
 PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW
 COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE
 A BUILDING SHALL BE SEPARATED FROM AREAS OF THE
 BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED
 IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A
 FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE
 THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION
 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE
 RATING SHALL BE REDUCED TO 1 HOUR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 CCOLE@WPB
  

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2022-08-26 Time   Rev Time 0.00
Received By lmarchan Date 2022-08-21 Time 08:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2022-07-26 Time   Rev Time 0.00
Received By lmarchan Date 2022-07-17 Time 08:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2022-05-20 Cont ID  
Sent By medwards Date 2022-05-20 Time 09:46 Rev Time 0.00
Received By medwards Date 2022-05-05 Time 08:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-04-05 Cont ID  
Sent By lmarchan Date 2022-04-05 Time 08:06 Rev Time 0.00
Received By lmarchan Date 2022-02-11 Time 15:02 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2022-01-07 Cont ID  
Sent By lmarchan Date 2022-01-07 Time 08:14 Rev Time 0.00
Received By lmarchan Date 2021-10-21 Time 16:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2022-05-20 Cont ID  
Sent By medwards Date 2022-05-20 Time 09:45 Rev Time 0.00
Received By medwards Date 2022-05-20 Time 09:45 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2022-02-25 Cont ID  
Sent By medwards Date 2022-02-25 Time 07:36 Rev Time 0.00
Received By medwards Date 2022-02-25 Time 07:36 Sent To  
Notes
2022-02-25 07:48:482ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21091144
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE HEAT LOAD COMPARISON TABLE FOR AC UNITS AND THE
 HEAT LOAD REPORT FOR AC UNITS DO NOT MATCH.
  EXAMPLE: COMPARISON TABLE- UNIT B-LEVEL-5- 4.8 TONS-
 HEAT LOAD REPORT- UNIT B- AC-1- 5.6 TONS. PLEASE
 PROVIDE MATCHING DOCUMENTS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-11-08 Cont ID  
Sent By medwards Date 2021-11-08 Time 08:31 Rev Time 0.00
Received By medwards Date 2021-11-08 Time 07:11 Sent To  
Notes
2021-11-08 08:31:341ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21091144
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE EXPLAIN WHY THE RESIDENTIAL MECHANICAL
 SYSTEMS ARE BEING UPSIZED. PLEASE PROVIDE THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS
 CHANGE. FBC EC C403.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2022-08-26 Cont ID  
Sent By ccole Date 2022-08-26 Time 17:03 Rev Time 0.00
Received By ccole Date 2022-08-26 Time 16:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2022-07-26 Cont ID  
Sent By ccole Date 2022-07-26 Time 11:46 Rev Time 0.00
Received By ccole Date 2022-07-26 Time 10:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2022-05-17 Cont ID  
Sent By ccole Date 2022-05-17 Time 11:30 Rev Time 0.00
Received By ccole Date 2022-05-17 Time 11:30 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2022-02-17 Cont ID  
Sent By ccole Date 2022-02-17 Time 07:45 Rev Time 0.00
Received By ccole Date 2022-02-16 Time 16:35 Sent To  
Notes
2022-02-17 08:43:332ND REVIEW FBC-2017 PLUMBING
 PERMIT- 21091144
 2/17/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) AS PREVIOUSLY NOTED IN 1ST REVIEW COMMENT #1C COPIED
 BELOW, THE POOL WATER (INCLUDING RECIRCULATION SYSTEM
 BACKWASH) SHALL NOT DRAIN INTO THE SANITARY SYSTEM. ALL
 POOL WASTE WATER SHALL DRAIN INTO THE STORM SYSTEM AND
 BE DECHLORINATED PRIOR TO DRAINING INTO THE SYSTEM. WPB
 GUIDELINES FOR WASTE WATER DISPOSAL ARE COPIED BELOW.
 THE CORRECTED PLANS DO NOT SHOW DECHLORINATION FOR THE
 POOL LEAKAGE WATER, AND ARE STILL SHOWING THE BACKWASH
 DRAINING INTO SANITARY SYSTEM. PLEASE CONTACT THE
 PARTIES LISTED IN THE GUIDELINES FOR FURTHER
 INFORMATION.
  
 1ST REVIEW- 1C) THE PLAN SHOWS THE POOL WATER LEAKAGE
 WILL DRAIN INTO THE POOL EQUIPMENT ROOM. THERE ARE TWO
 HUB DRAINS IN THE ROOM DEDICATED TO STORM AND TO
 SANITARY. PLEASE NOTE THAT POOL WASTE WATER SHALL NOT
 DRAIN INTO THE SANITARY SYSTEM. AN ALTERNATE MEANS MUST
 BE PROVIDED FOR BOTH THE EMERGENCY POOL DRAINAGE AND
 THE POOL BACKWASH- SEC. 90- 126(5) WPB MUNI. CODE OF
 ORDINANCES. PLEASE NOTE THAT ONLY DECHLORINATED POOL
 WASTE SHALL DRAIN INTO THE CITY STORM DRAIN SYSTEM-
 SECTION 90-205 EXCEPTION 1.
  
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S
 SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT
 STEPHON HARRIS AT [email protected] OR 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 [email protected], OR STORMWATER ENGINEER
 TRACEY WARD- 561-493-4787.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  
2022-02-17 07:48:58 
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-11-05 Cont ID  
Sent By ccole Date 2021-11-05 Time 15:49 Rev Time 0.00
Received By ccole Date 2021-11-05 Time 12:05 Sent To  
Notes
2021-11-05 15:50:481ST REVIEW FBC-2017 PLUMBING
 PERMIT- 21091144
 11/5/21
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017
 FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS P101A, P101B, P102B: PLEASE PROVIDE MORE
 INFORMATION AND DETAILS FOR THE EMERGENCY DRAINS IN THE
 INTERSTITIAL SPACE. IT APPEARS THAT A PLAN SHEET MAY BE
 MISSING WHICH WOULD BE SHOWING THE SECTION A PART OF
 THE 2ND FLOOR AND ONE OF THE EMERGENCY POOL DRAINS-
 SECTION 107.2.1 WPB.
  
 A) PROVIDE A SECTION CUT SHOWING THE LOCATIONS, SPACING
 OF THE DRAINS, AND FLOOR SLOPE TO THE DRAINS. ARE THERE
 EXACT INSTALLATION LOCATIONS OR ARE THEY TO BE RANDOMLY
 PLACED?- SECTION 107.2.1 WPB.
  
 B) CLARIFY HOW THIS SYSTEM WAS DESIGNED AND SIZED-
 SECTIONS 107.2.1 WPB.
  
 C) THE PLAN SHOWS THE POOL WATER LEAKAGE WILL DRAIN
 INTO THE POOL EQUIPMENT ROOM. THERE ARE TWO HUB DRAINS
 IN THE ROOM DEDICATED TO STORM AND TO SANITARY. PLEASE
 NOTE THAT POOL WASTE WATER SHALL NOT DRAIN INTO THE
 SANITARY SYSTEM. AN ALTERNATE MEANS MUST BE PROVIDED
 FOR BOTH THE EMERGENCY POOL DRAINAGE AND THE POOL
 BACKWASH- SEC. 90- 126(5) WPB MUNI. CODE OF ORDINANCES.
 PLEASE NOTE THAT ONLY DECHLORINATED POOL WASTER SHALL
 DRAIN INTO THE CITY STORM DRAIN SYSTEM- SECTION 90-205
 EXCEPTION 1.
  
 2) P501A: PLEASE NOTE ON THE PLAN THAT THE BFP SHALL BE
 UNDER SEPARATE PERMIT- SECTION 105.1 & 107.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-08-26 Cont ID  
Sent By ccole Date 2022-08-26 Time 17:03 Rev Time 0.00
Received By ccole Date 2022-08-26 Time 16:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2022-07-26 Cont ID  
Sent By ccole Date 2022-07-26 Time 11:47 Rev Time 0.00
Received By ccole Date 2022-07-26 Time 10:27 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2022-05-17 Cont ID  
Sent By ccole Date 2022-05-17 Time 11:31 Rev Time 0.00
Received By ccole Date 2022-05-17 Time 11:31 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-03-16 Cont ID  
Sent By rmcdouga Date 2022-03-16 Time 15:05 Rev Time 0.00
Received By rmcdouga Date 2022-03-16 Time 15:05 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-11-19 Cont ID  
Sent By rmcdouga Date 2021-11-19 Time 17:04 Rev Time 0.00
Received By rmcdouga Date 2021-11-19 Time 17:04 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-04-04 Cont ID  
Sent By eschneid Date 2022-04-04 Time 16:38 Rev Time 1.00
Received By eschneid Date 2022-04-04 Time 14:14 Sent To  
Notes
2022-04-04 16:39:40PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE
 BUILDING, AN AS BUILT MINOR PLANNED DEVELOPMENT
 AMENDMENT SHOWING ALL THE CHANGES SINCE THE LAST MINOR
 AMENDMENT.

Review Stop Z ZONING
Rev No 1 Status F Date 2022-01-06 Cont ID  
Sent By eschneid Date 2022-01-06 Time 19:04 Rev Time 4.00
Received By eschneid Date 2022-01-06 Time 14:28 Sent To  
Notes
2022-01-06 19:04:23FAILED
  
 1) PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE
 BUILDING, AN AS BUILT MINOR PLANNED DEVELOPMENT
 AMENDMENT SHOWING ALL THE CHANGES SINCE THE LAST MINOR
 AMENDMENT.
  
 2) THE PARKING TABLE SHEET NEEDS TO BE AMENDED AND
 SUBMITTED TO REFLECT THE CHANGE OF PARKING SPACE 55 TO
 A COMPACT PARKING SPACE (SHOWN ON SHEET A-100A).
 ADDITIONALLY, SHEET A-100 MUST BE UPDATED AND PROVIDED
 TO REFLECT THIS CHANGE.
  
 3) PROVIDE REVISED SHEET A-102 TO REFLECT THE CHANGES
 ON SHEET A-101B.
  
 4) PROVIDE VERIFICATION THAT THE NEW SPF 2 GV 1 SHOWN
 ON THE ROOF DOES NOT EXCEED THE PERMITTED HEIGHT.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
  
  