| Plan Review Stops For Permit 21091144 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-16 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-16 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2022-03-16 17:13:57 | GENERATORS REQUIRE A SEPARATE PERMIT. SEE SHEET A-110. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-12-06 |
Time |
17:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-11-19 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2021-12-06 17:47:51 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | REVISION DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) I SAW AN INDEX PAGE FOR THE STRUCTURAL SHEETS. | | | HOWEVER, I DID NOT SEE A REVISED INDEX PAGE WITH THE | | | PLAN SHEETS AND THE REVISIONS OF EACH SHEET LISTED FOR | | | THE ARCHITECTURAL, LIFE SAFETY OR MEP PLANS. FBC | | | 107.2.1 | | | | | | 2) SPECIFY THE WIND PRESSURES FOR THE ROOF TOP | | | GENERATOR FOR THE PENTHOUSE. PROVIDE ANCHORING DETAILS | | | AND CALCULATIONS FOR THE GENERATOR TO SHOW THAT IT WILL | | | RESIST THE WINDLOAD PRESSURES. FBC 107.2.1.2 | | | | | | 3) SUBMIT THE MANUFACTURER'S SPECIFICATIONS WITH THE | | | WEIGHT AND DIMENSIONS FOR THE PENTHOUSE GENERATOR. FBC | | | 107.2.1 | | | | | | 4) CLEARLY SHOW THAT THE GENERATOR'S EXHAUST IS TEN | | | FEET FROM ANY OPENINGS INTO THE BUILDING. R303.5.1 | | | INTAKE OPENINGS. MECHANICAL AND GRAVITY OUTDOOR AIR | | | INTAKE OPENINGS SHALL BE LOCATED NOT LESS THAN 10 FEET | | | (3048 MM) FROM ANY HAZARDOUS OR NOXIOUS CONTAMINANT, | | | SUCH AS VENTS, CHIMNEYS, PLUMBING VENTS, STREETS, | | | ALLEYS, PARKING LOTS AND LOADING DOCKS. | | | | | | 5) ON SHEET A-790 DETAIL 1, THE UNIT A KITCHEN FLOOR | | | PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40" | | | CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES | | | REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 2-3/8") | | | | | | 6) ON SHEET A-792 DETAIL 2, THE UNIT F KITCHEN FLOOR | | | PLAN HAS A DIMENSION OF LESS THAN THE REQUIRED 40" | | | CLEARANCE BETWEEN THE ISLAND AND THE OPPOSING FEATURES | | | REQUIRED BY THE FAIR HOUSING GUIDELINES. (3' 3-1/2") | | | | | | 7) THERE WERE SOME REVISED PAGES THAT DID NOT APPEAR ON | | | YOUR NARRATIVE, SUCH AS SHEETS A-137, A-138 AND A-139. | | | THERE WERE ALSO SOME SHEETS ON THE NARRATIVE THAT I | | | COULD NOT FIND IN THE REVISED PLANS SUCH AS G-9 AND | | | G-10. FBC 107.2.1 | | | | | | 8) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-11-18 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-11-18 |
Time |
13:47 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-11-18 |
Time |
13:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2022-02-14 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-02-14 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-02-14 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2021-11-08 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-11-08 |
Time |
09:18 |
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-08 09:32:49 | RESPONSE LETTER MENTIONS 3 IN. SPRINKLER LINE ADDED TO | | | STORM. PLEASE CLARIFY, AND SHOW CLEARLY ON UTILITY | | | SHEET C6.00 WITH CLOUD/NOTE/ETC. PLEASE NOTE THAT | | | CHANGE IN WATER DEMANDS REQUIRES ASBUILT REVISION VIA | | | FORMAL ENGINEERING RESUBMITTAL. | | | | | | FEEL FREE TO CONTACT US IF YOU HAVE ANY QUESTIONS OR | | | CONCERNS, THANKS. | | | RICK ROSSANO, SENIOR PROJECT COORDINATOR, | | | CITY OF WPB ENGINEERING SERVICES DEPARTMENT | | | DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE: | | | (561) 246-9525 | | | EMAIL: [email protected] | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING- | | | STANDARDS-DETAILS | | 2021-11-08 08:59:19 | PLEASE ADDRESS PLUMBING COMMENTS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-10-29 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-10-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
bdolan |
Date |
2021-10-29 |
Time |
12:25 |
Sent To |
|
|
| Notes |
| 2021-10-29 12:26:17 | THE DIVISION OF FIRE PREVENTION HAS NO OBJECTIONS TO | | | THE REVISIONS IN THE PLAN SET. | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-26 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-26 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-26 |
Time |
11:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-26 |
Time |
10:27 |
Sent To |
|
|
| Notes |
| 2022-07-26 11:45:26 | 3RD REVIEW FBC-2017 FUEL GAS | | | PERMIT- 21091144 | | | 7/26/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P-101B, P-242, & P-505: THE UPDATED PLAN | | | SHEETS DO NOT MATCH. | | | | | | A) SHEET P-101B SHOWS ONLY ONE METER AND THE PIPE RUNS | | | AND PIPE SIZES DO NOT MATCH THE ENLARGED PIPING LAYOUT | | | DRAWING (P-242) AND THE RISER (P-505. | | | | | | B) P-242 SHOWS A 2-1/2 LOW PRESSURE SUPPLY LINE ON | | | LEVEL 01 FROM THE METER TO THE VERTICAL RISER PIPE, | | | HOWEVER THE ISOMETRIC DRAWING (P-505) SHOWS A 3-INCH | | | PIPE. WHICH IS IT? | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-17 |
Time |
10:53 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-17 |
Time |
08:22 |
Sent To |
|
|
| Notes |
| 2022-05-17 10:54:31 | 2ND REVIEW FBC-2017 FUEL GAS | | | PERMIT- 21091144 | | | 2/17/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE ENGINEER OF RECORD HAS STATED IN HIS COMMENT | | | RESPONSES THAT THE TWO GAS GENERATORS SHOWN IN THE | | | REVISION ARE LEVEL 2 EMERGENCY POWER SUPPLY SYSTEMS | | | (EPSS). SEC. 4.4.2 NFPA 11 STATES THAT LEVEL 2 SYSTEMS | | | SHALL BE INSTALLED WHERE FAILURE OF THE EPSS TO PERFORM | | | IS LESS CRITICAL TO HUMAN LIFE AND SAFETY. AS | | | PREVIOUSLY REQUESTED, PLEASE PROVIDE A SPECIFIC LIST OF | | | ALL LEVEL 2 LOADS TO BE SUPPLIED BY THE GAS GENERATORS. | | | | | | 2) REFER TO SEC. 7.9.7- 7.9.8 NFPA 110 AND REVISE THE | | | DRAWINGS TO SHOW COMPLIANCE: THE GAS SUPPLY LINES TO | | | THE GENERATORS SHALL BE CONNECTED ON THE SUPPLY SIDE OF | | | THE MAIN GAS SHUTOFF VALVE AND MARKED AS SUPPLYING AN | | | EMERGENCY GENERATOR. THE BUILDING?S MAIN GAS SHUTOFF | | | VALVE SHALL BE MARKED OR TAGGED TO INDICATE THE | | | EXISTENCE OF THE SEPARATE EPS SHUTOFF VALVE. | | | | | | 3) THE FINAL APPROVAL OF THE REVISED MAIN BUILDING | | | PLANS CANNOT BE ACCOMPLISHED WITHOUT A FINAL APPROVAL | | | OF THE GAS GENERATOR PERMIT- 21021355. PLEASE RESUBMIT | | | CORRECTED PLANS CONSISTENT WITH THESE COMMENTS, THE | | | GENERATOR PERMIT COMMENTS, AND IN COMPLIANCE WITH NFPA | | | 37, 54,110 AND THE FBC FG-2017. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-17 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-17 |
Time |
14:39 |
Sent To |
|
|
| Notes |
| 2022-02-17 14:48:05 | 2ND REVIEW FBC-2017 FUEL GAS | | | PERMIT- 21091144 | | | 2/17/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. PLEASE PROVIDE ADDITIONAL | | | INFORMATION FOR THE TWO GAS GENERATORS. IN REPONSE TO | | | THE 1ST REVIEW COMMENTS LISTED BELOW, THE EOR IS | | | STATING IN THE COMMENT RESPONSE NARRATIVE THAT THE | | | GENERATORS ARE LEVEL 2, NOT 1. THE RISER ON SHEET P-505 | | | INDICATES LEVEL 2 "STAND-BY" GENERATORS. PLEASE | | | INDICATE ON THE PLANS THE SPECIFIC SYSTEMS THAT THE | | | GENERATORS ARE SUPPLYING POWER TO. LEVEL 1 STAND-BY | | | GENERATORS ACCORDING TO SEC. 4.4.1 NFPA 110 ARE | | | INSTALLED WHERE FAILURE OF THE EQUIPMENT TO PERFORM | | | COULD RESULT IN LOSS OF HUMAN LIFE OR SERIOUS INJURIES. | | | REFER TO SEC. 403.8.3 FBC B.- THE FOLLOWING ARE | | | CLASSIFIED AS STANDBY POWER LOADS IN HIGH RISE | | | BUILDINGS- | | | | | | 1.VENTILATION AND AUTOMATIC FIRE DETECTION EQUIPMENT | | | FOR SMOKEPROOF ENCLOSURES. | | | 2.ELEVATORS. | | | 3.WHERE ELEVATORS ARE PROVIDED IN A HIGH-RISE BUILDING | | | FOR ACCESSIBLE MEANS OF EGRESS, FIRE SERVICE ACCESS OR | | | OCCUPANT SELF-EVACUATION, THE STANDBY POWER SYSTEM | | | SHALL ALSO COMPLY WITH SECTIONS 1009, 3007 OR 3008, AS | | | APPLICABLE. | | | | | | SEC. 4.4.1 NFPA 110 LEVEL 1 ESSENTIAL ELECTRICAL | | | SYSTEMS: | | | LIFE SAFETY ILLUMINATION | | | FIRE DETECTION AND ALARM SYSTEMS | | | ELEVATORS | | | FIRE PUMPS | | | PUBLIC SAFETY COMMUNICATIONS SYSTEMS | | | INDUSTRIAL PROCESSES WHERE CURRENT INTERRUPTION WOULD | | | PRODUCE SERIOUS LIFE SAFETY OR HEALTH HAZARDS | | | ESSENTIAL VENTILATING AND SMOKE REMOVAL SYSTEMS | | | | | | SEE SECTION 403.4.8.4 FBC B FOR LIST OF EMERGENCY POWER | | | LOADS. PLEASE NOTE THERE ARE RELATIVE GAS COMMENTS FOR | | | THE 30KW GENERATOR INSTALLATION UNDER PERMIT- 21021355. | | | | | | 1ST REVIEW COMMENTS- 11/5/21 | | | | | | 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110 | | | WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO | | | SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON | | | LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED | | | FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER | | | PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO | | | SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A | | | BOILER. | | | A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 110 AND | | | SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED | | | GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE | | | POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE | | | SEPARATE EPS SHUTOFF VALVES. | | | | | | 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING | | | PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW | | | COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE | | | A BUILDING SHALL BE SEPARATED FROM AREAS OF THE | | | BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED | | | IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE | | | THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC | | | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE | | | RATING SHALL BE REDUCED TO 1 HOUR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-11-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-11-05 |
Time |
17:07 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-11-05 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2021-11-05 17:08:12 | 1ST REVIEW FBC-2017 FUEL GAS | | | PERMIT- 21091144 | | | 11/5/2021 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | | 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P505 & P110: PLEASE PLACE A NOTE ON THE PLAN | | | INDICATING A SEPARATE PERMIT IS REQUIRED FOR THE | | | GENERATOR ON THE ROOF. A FULL GAS REVIEW FOR THE | | | GENERATOR IS NOT BEING PERFORMED AT THIS TIME- SECTIONS | | | 105.1 & 107.1 WPB. | | | | | | 2) P505 & P110: REFER TO SECTIONS 5.1 & 5.5.1 NFPA 110 | | | WHICH APPEARS TO BE REQUIRING DEDICATED GAS LINES TO | | | SUPPLY THE EPS (GENERATORS) ON THE ROOF TOP AND ON | | | LEVEL 3. FUEL SUPPLIES TO ENERGY CONVERTERS INTENDED | | | FOR LEVEL 1 USE SHALL NOT BE USED FOR ANY OTHER | | | PURPOSE. THE RISER SHOWS THE 2 PSI SERVICE LINE ALSO | | | SUPPLYING GAS TO 3 WATER HEATERS, 2 POOL HEATERS, AND A | | | BOILER. | | | | | | A) RISER: REFER TO SECTIONS 7.9.7 & 7.9.8 NFPA 1110 AND | | | SHOW THE SEPARATE SHUTOFF VALVES FOR THE DEDICATED | | | GENERATOR LINES AND INDICATE THAT SIGNAGE WILL BE | | | POSTED AT THE VALVE TO INDICATE THE EXISTENCE OF THE | | | SEPARATE EPS SHUTOFF VALVES. | | | | | | 3) REFER TO SECTION 403.4.8.2 FBC B- FUEL LINE PIPING | | | PROTECTION AND SUBMIT DRAWINGS AND DETAILS SHOW | | | COMPLIANCE- FUEL LINES SUPPLYING A GENERATOR SET INSIDE | | | A BUILDING SHALL BE SEPARATED FROM AREAS OF THE | | | BUILDING OTHER THAN THE ROOM THE GENERATOR IS LOCATED | | | IN BY AN APPROVED METHOD OR ASSEMBLY THAT HAS A | | | FIRE-RESISTANCE RATING OF NOT LESS THAN 2 HOURS. WHERE | | | THE BUILDING IS PROTECTED THROUGHOUT WITH AN AUTOMATIC | | | SPRINKLER SYSTEM INSTALLED IN ACCORDANCE WITH SECTION | | | 903.3.1.1 OR 903.3.1.2, THE REQUIRED FIRE-RESISTANCE | | | RATING SHALL BE REDUCED TO 1 HOUR. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | CCOLE@WPB | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-08-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-08-21 |
Time |
08:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-07-26 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-07-17 |
Time |
08:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-20 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-05 |
Time |
08:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-04-05 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-04-05 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-11 |
Time |
15:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-07 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-01-07 |
Time |
08:14 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-21 |
Time |
16:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2022-05-20 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-05-20 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-05-20 |
Time |
09:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-02-25 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-25 |
Time |
07:36 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-25 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2022-02-25 07:48:48 | 2ND REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091144 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE HEAT LOAD COMPARISON TABLE FOR AC UNITS AND THE | | | HEAT LOAD REPORT FOR AC UNITS DO NOT MATCH. | | | EXAMPLE: COMPARISON TABLE- UNIT B-LEVEL-5- 4.8 TONS- | | | HEAT LOAD REPORT- UNIT B- AC-1- 5.6 TONS. PLEASE | | | PROVIDE MATCHING DOCUMENTS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-08 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-08 |
Time |
08:31 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-08 |
Time |
07:11 |
Sent To |
|
|
| Notes |
| 2021-11-08 08:31:34 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091144 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE EXPLAIN WHY THE RESIDENTIAL MECHANICAL | | | SYSTEMS ARE BEING UPSIZED. PLEASE PROVIDE THE | | | MECHANICAL EQUIPMENT SIZING CALCULATIONS FOR THIS | | | CHANGE. FBC EC C403.2.1 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-26 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-26 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-26 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-26 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-17 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-17 |
Time |
11:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-02-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-02-17 |
Time |
07:45 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-02-16 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2022-02-17 08:43:33 | 2ND REVIEW FBC-2017 PLUMBING | | | PERMIT- 21091144 | | | 2/17/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) AS PREVIOUSLY NOTED IN 1ST REVIEW COMMENT #1C COPIED | | | BELOW, THE POOL WATER (INCLUDING RECIRCULATION SYSTEM | | | BACKWASH) SHALL NOT DRAIN INTO THE SANITARY SYSTEM. ALL | | | POOL WASTE WATER SHALL DRAIN INTO THE STORM SYSTEM AND | | | BE DECHLORINATED PRIOR TO DRAINING INTO THE SYSTEM. WPB | | | GUIDELINES FOR WASTE WATER DISPOSAL ARE COPIED BELOW. | | | THE CORRECTED PLANS DO NOT SHOW DECHLORINATION FOR THE | | | POOL LEAKAGE WATER, AND ARE STILL SHOWING THE BACKWASH | | | DRAINING INTO SANITARY SYSTEM. PLEASE CONTACT THE | | | PARTIES LISTED IN THE GUIDELINES FOR FURTHER | | | INFORMATION. | | | | | | 1ST REVIEW- 1C) THE PLAN SHOWS THE POOL WATER LEAKAGE | | | WILL DRAIN INTO THE POOL EQUIPMENT ROOM. THERE ARE TWO | | | HUB DRAINS IN THE ROOM DEDICATED TO STORM AND TO | | | SANITARY. PLEASE NOTE THAT POOL WASTE WATER SHALL NOT | | | DRAIN INTO THE SANITARY SYSTEM. AN ALTERNATE MEANS MUST | | | BE PROVIDED FOR BOTH THE EMERGENCY POOL DRAINAGE AND | | | THE POOL BACKWASH- SEC. 90- 126(5) WPB MUNI. CODE OF | | | ORDINANCES. PLEASE NOTE THAT ONLY DECHLORINATED POOL | | | WASTE SHALL DRAIN INTO THE CITY STORM DRAIN SYSTEM- | | | SECTION 90-205 EXCEPTION 1. | | | | | | SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY | | | STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED | | | ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM | | | BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER'S | | | SPECIFICATION FOR THE DECHLORINATION SYSTEM FOR REVIEW | | | AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL | | | WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: | | | THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO | | | KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE | | | INLET). | | | NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE | | | INLET TO DISCHARGE EFFLUENT. | | | WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED | | | TO FILTER THROUGH GRASS AREA ON THE POOL OWNER'S | | | PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. | | | DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING | | | PROPERTY. | | | FOR TECHNICAL QUESTIONS, CONTACT O&M SUPERINTENDENT | | | STEPHON HARRIS AT [email protected] OR 561-822-2168. | | | FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE | | | CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE | | | SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) | | | 822-2062 [email protected], OR STORMWATER ENGINEER | | | TRACEY WARD- 561-493-4787. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | | | 2022-02-17 07:48:58 | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-11-05 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-11-05 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-11-05 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2021-11-05 15:50:48 | 1ST REVIEW FBC-2017 PLUMBING | | | PERMIT- 21091144 | | | 11/5/21 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE SIXTH EDITION 2017 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE SIXTH ADDITION 2017 | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | | 2017 | | | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | | EDITION 2017 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEETS P101A, P101B, P102B: PLEASE PROVIDE MORE | | | INFORMATION AND DETAILS FOR THE EMERGENCY DRAINS IN THE | | | INTERSTITIAL SPACE. IT APPEARS THAT A PLAN SHEET MAY BE | | | MISSING WHICH WOULD BE SHOWING THE SECTION A PART OF | | | THE 2ND FLOOR AND ONE OF THE EMERGENCY POOL DRAINS- | | | SECTION 107.2.1 WPB. | | | | | | A) PROVIDE A SECTION CUT SHOWING THE LOCATIONS, SPACING | | | OF THE DRAINS, AND FLOOR SLOPE TO THE DRAINS. ARE THERE | | | EXACT INSTALLATION LOCATIONS OR ARE THEY TO BE RANDOMLY | | | PLACED?- SECTION 107.2.1 WPB. | | | | | | B) CLARIFY HOW THIS SYSTEM WAS DESIGNED AND SIZED- | | | SECTIONS 107.2.1 WPB. | | | | | | C) THE PLAN SHOWS THE POOL WATER LEAKAGE WILL DRAIN | | | INTO THE POOL EQUIPMENT ROOM. THERE ARE TWO HUB DRAINS | | | IN THE ROOM DEDICATED TO STORM AND TO SANITARY. PLEASE | | | NOTE THAT POOL WASTE WATER SHALL NOT DRAIN INTO THE | | | SANITARY SYSTEM. AN ALTERNATE MEANS MUST BE PROVIDED | | | FOR BOTH THE EMERGENCY POOL DRAINAGE AND THE POOL | | | BACKWASH- SEC. 90- 126(5) WPB MUNI. CODE OF ORDINANCES. | | | PLEASE NOTE THAT ONLY DECHLORINATED POOL WASTER SHALL | | | DRAIN INTO THE CITY STORM DRAIN SYSTEM- SECTION 90-205 | | | EXCEPTION 1. | | | | | | 2) P501A: PLEASE NOTE ON THE PLAN THAT THE BFP SHALL BE | | | UNDER SEPARATE PERMIT- SECTION 105.1 & 107.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-08-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-26 |
Time |
17:03 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-26 |
Time |
16:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-26 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-26 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
P |
Date |
2022-05-17 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-05-17 |
Time |
11:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-05-17 |
Time |
11:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-16 |
Time |
15:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-16 |
Time |
15:05 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-11-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2021-11-19 |
Time |
17:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2021-11-19 |
Time |
17:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-04-04 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-04-04 |
Time |
16:38 |
Rev Time |
1.00 |
| Received By |
eschneid |
Date |
2022-04-04 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2022-04-04 16:39:40 | PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE | | | BUILDING, AN AS BUILT MINOR PLANNED DEVELOPMENT | | | AMENDMENT SHOWING ALL THE CHANGES SINCE THE LAST MINOR | | | AMENDMENT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-06 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2022-01-06 |
Time |
19:04 |
Rev Time |
4.00 |
| Received By |
eschneid |
Date |
2022-01-06 |
Time |
14:28 |
Sent To |
|
|
| Notes |
| 2022-01-06 19:04:23 | FAILED | | | | | | 1) PRIOR TO THE FIRST CERTIFICATE OF OCCUPANCY FOR THE | | | BUILDING, AN AS BUILT MINOR PLANNED DEVELOPMENT | | | AMENDMENT SHOWING ALL THE CHANGES SINCE THE LAST MINOR | | | AMENDMENT. | | | | | | 2) THE PARKING TABLE SHEET NEEDS TO BE AMENDED AND | | | SUBMITTED TO REFLECT THE CHANGE OF PARKING SPACE 55 TO | | | A COMPACT PARKING SPACE (SHOWN ON SHEET A-100A). | | | ADDITIONALLY, SHEET A-100 MUST BE UPDATED AND PROVIDED | | | TO REFLECT THIS CHANGE. | | | | | | 3) PROVIDE REVISED SHEET A-102 TO REFLECT THE CHANGES | | | ON SHEET A-101B. | | | | | | 4) PROVIDE VERIFICATION THAT THE NEW SPF 2 GV 1 SHOWN | | | ON THE ROOF DOES NOT EXCEED THE PERMITTED HEIGHT. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | | | | | | | | |
|
|