Plan Review Details - Permit 21091132
Plan Review Stops For Permit 21091132
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-01-11 Cont ID  
Sent By rmcdouga Date 2022-01-11 Time 09:30 Rev Time 0.00
Received By rmcdouga Date 2022-01-11 Time 09:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-12-08 Cont ID  
Sent By rmcdouga Date 2021-12-08 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2021-12-08 Time 10:07 Sent To  
Notes
2021-12-08 10:38:08PLAN
 REVIEW COMMENTS
  
 3RD REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) PREVIOUS COMMENT HAS NOT BEEN RESOLVED. THE
 UNDERLAYMENT LETTER FROM THE TECHNICAL SERVICES
 DIRECTOR OF PLITEQ INC. IS FOR FLOOR COVERING SYSTEMS
 AND THIS PRODUCT IS A SOUND INSULATION UNDERLAYMENT.
 THE TESTING THAT WAS USED IS NOT EQUIVALENT TO THE TEST
 REQUIRED BY ASTM E84-2016 FOR FLAME SPREAD. DUE TO
 THESE ISSUES I AM NOT ABLE TO ACCEPT THIS LETTER IN
 LIEU OF THE REQUIRED TEST REPORT. [THE TECHNICAL NOTE
 FOR THE GENIEMAT STATES THAT THE FLAME SPREAD IS 65 AND
 THE SMOKE DEVELOPED IS 105 PER ASTM E84. WE REQUIRE THE
 ACTUAL TEST REPORT FROM AN ACCREDITED TESTING
 LABORATORY. THE TECHNICAL NOTE FROM THE MANUFACTURER IS
 NOT ACCEPTABLE. IF THE TEST REPORT IS NOT AVAILABLE,
 ANOTHER SOUND INSULATION WILL BE REQUIRED.] SUBMIT THE
 FLAME SPREAD TEST REPORT PER ASTM E 84-09. FBC603.1
  
 2) IN REGARD TO THE EMAIL FROM WILSON BYRICK, THE FBC
 CODE SECTION 805.1.3 IS FOR INSULATING BOARDS NOT MORE
 THAN 1/2 INCH THICK. THE INSULATION THAT IS BEING
 PROPOSED IS A SHEET THAT COMES IN ROLLS AND NOT A RIGID
 BOARD. IF YOU ARE NOT ABLE TO PROVIDE THE REQUIRED TEST
 REPORTS FOR THE SOUND INSULATING UNDERLAYMENT, SELECT
 ANOTHER PRODUCT THAT DOES HAVE THE REQUIRED TEST
 REPORTS.
  
 3) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW THE
 REVIEW COMMENTS HAVE BEEN ADDRESSED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 07:47 Rev Time 0.00
Received By rmcdouga Date 2021-11-02 Time 07:47 Sent To  
Notes
2021-11-02 07:47:30PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING - PREVIOUS COMMENT WAS NOT ADDRESSED
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) [THE TECHNICAL NOTE FOR THE GENIEMAT STATES THAT THE
 FLAME SPREAD IS 65 AND THE SMOKE DEVELOPED IS 105 PER
 ASTM E84. WE REQUIRE THE ACTUAL TEST REPORT FROM AN
 ACCREDITED TESTING LABORATORY. THE TECHNICAL NOTE FROM
 THE MANUFACTURER IS NOT ACCEPTABLE. IF THE TEST REPORT
 IS NOT AVAILABLE, ANOTHER SOUND INSULATION WILL BE
 REQUIRED.] SUBMIT THE FLAME SPREAD TEST REPORT PER ASTM
 E 84-09. FBC603.1

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-08 Cont ID  
Sent By rmcdouga Date 2021-10-08 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2021-10-08 Time 08:38 Sent To  
Notes
2021-10-08 09:22:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SUBMIT THE FLAME SPREAD TEST REPORT PER ASTM E
 84-09. FBC603.1

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-11 Cont ID  
Sent By rmcdouga Date 2022-01-11 Time 09:31 Rev Time 0.00
Received By rmcdouga Date 2022-01-05 Time 16:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-08 Cont ID  
Sent By rmcdouga Date 2021-12-08 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2021-11-03 Time 09:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-02 Cont ID  
Sent By rmcdouga Date 2021-11-02 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2021-10-12 Time 06:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-08 Cont ID  
Sent By rmcdouga Date 2021-10-08 Time 09:23 Rev Time 0.00
Received By rmcdouga Date 2021-09-27 Time 08:49 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status N Date 2021-10-08 Cont ID  
Sent By rmcdouga Date 2021-10-08 Time 08:38 Rev Time 0.00
Received By rmcdouga Date 2021-10-08 Time 08:38 Sent To  
Notes
***NONE***