Plan Review Details - Permit 21091118
Plan Review Stops For Permit 21091118
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 10:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 14:01 Rev Time 0.00
Received By shill Date 2021-10-10 Time 14:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2022-01-12 Cont ID  
Sent By fgiaquin Date 2022-01-12 Time 19:02 Rev Time 0.00
Received By fgiaquin Date 2022-01-12 Time 18:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-26 Cont ID  
Sent By fgiaquin Date 2021-10-26 Time 20:08 Rev Time 0.00
Received By fgiaquin Date 2021-10-26 Time 18:55 Sent To  
Notes
2021-10-26 20:08:55ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE WIRING DIAGRAM FOR SIGNS. FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-805-6744
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2022-01-18 Cont ID  
Sent By lmarchan Date 2022-01-18 Time 14:44 Rev Time 0.00
Received By lmarchan Date 2021-12-16 Time 09:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-26 Cont ID  
Sent By fgiaquin Date 2021-10-26 Time 20:09 Rev Time 0.00
Received By fgiaquin Date 2021-09-29 Time 09:25 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2022-01-13 Cont ID  
Sent By rmcdouga Date 2022-01-13 Time 10:47 Rev Time 0.00
Received By rmcdouga Date 2022-01-13 Time 10:47 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-10 Cont ID  
Sent By shill Date 2021-10-10 Time 14:01 Rev Time 0.00
Received By shill Date 2021-10-10 Time 14:01 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2022-01-18 Cont ID  
Sent By eschneid Date 2022-01-18 Time 11:59 Rev Time 0.75
Received By eschneid Date 2022-01-18 Time 10:56 Sent To  
Notes
2022-01-18 11:59:41ARCADE IDENTITY SIGN TYPE 1C - STOREFRONT TYPE 1
  
 PERMITTED SIGN SIZE: 30.3 SF
 PROPOSED SIGN SIZE: 22.33
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By eshneide Date 2021-10-20 Time 15:02 Rev Time 0.75
Received By eschneid Date 2021-10-20 Time 15:02 Sent To  
Notes
2021-10-20 15:04:15FAILED
  
 1) THE CITYPLACE RETAIL MANAGEMENT APPROVAL STAMP IS
 REQUIRED ON THE PLANS. ALTERNATIVELY, YOU MAY PROVIDE A
 LETTER FROM CITYPLACE RETAIL MANAGEMENT WHICH APPROVES
 THE SPECIFIC PLANS SUBMITTED AS PART OF THE PERMIT.
  
 ARCADE IDENTITY SIGN TYPE 1D - STOREFRONT TYPE 1
  
 2) THE PROPOSED SIGN IS USING OPTION D ? SIGN MOUNTED
 TO RACEWAYS SPANNING THE VERTICAL COLUMNS.
  
 A. THE ROSEMARY SQUARE TENANT SIGN CRITERIA PROHIBIT
 ARCADE IDENTITY SIGNS FROM EXTENDING PAST THE WIDTH OF
 THE ARCADE OPENING.
  
 B. OPTION D ONLY PERMITS LETTERS TO BE MOUNTED TO THE
 RACEWAY, NOT MOUNTED TO A BACKER PANEL THAT IS MOUNTED
 TO A RACEWAY. NOTE: LETTERS MOUNTED TO A BACKER PANEL
 ARE ONLY PERMITTED AS OPTION C, WHICH REQUIRES THE
 PANEL TO BE MOUNTED TO SUPPORTS SUSPENDED FROM TOP OF
 THE ARCADE OPENING.
  
 3) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN AREA INCLUDE ALL ELEMENTS OF THE SIGN, TO
 INCLUDE THE BACKER PANEL. PROVIDE THE FULL VERTICAL
 DIMENSION OF THE SIGN.
  
 4) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT REVERSE CHANNEL LETTERS ARE FABRICATED OUT OF
 ALUMINUM WITH A MINIMUM METAL THICKNESS OF .060 INCHES.
 THE RETURNS DO NOT MEET THIS REQUIREMENT.
  
 5) THE ROSEMARY SQUARE TENANT SIGN CRITERIA DO NOT
 SPECIFICALLY PERMIT LEXAN AS A SIGN MATERIAL;
 THEREFORE, THIS USE OF ALTERNATIVE MATERIALS ON THE
 SIGN REQUIRES A WAIVER I WRITTEN APPROVAL FROM
 CITYPLACE RETAIL TO BE SUBMITTED WITH THE PERMIT.
  
 6) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT RIVETS, SCREWS AND OTHER FASTENERS THAT EXTEND TO
 VISIBLE SURFACES SHALL BE FLUSH, FILLED AND FINISHED SO
 AS TO BE UNNOTICEABLE. THE BOLT ENDS/NUTS THAT EXTEND
 PAST THE BACKER PANEL DO NOT MEET THIS STANDARD. IF THE
 BOLT ENDS/NUTS MUST EXTEND PAST THE BACKER PANEL, THEY
 NEED TO BE CONCEALED BY CAPS MATCHING THE COLOR OF THE
 MOUNTING PLATE.
  
 7) THE ROSEMARY SQUARE TENANT SIGN CRITERIA PERMIT A
 MAXIMUM LETTER HEIGHT OF 18 INCHES FOR A ARCADE
 IDENTITY SIGN. PROVIDE THE FULL DIMENSION OF THE "T"
 AND THE "G" ("G" DIMENSION PROVIDED DOES NOT CLEARLY
 SHOW THE FULL HEIGHT).
  
 8) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE ALL
 CONDUIT, RACEWAYS, WIRING, BALLAST BOXES, TRANSFORMERS,
 JUNCTION BOXES, BELL BOXES, POWER SUPPLY AND OTHER
 EQUIPMENT NECESSARY FOR SIGN CONNECTION SHALL BE
 CONCEALED AND NOT VISIBLE TO THE PUBLIC. NOTE: EXPOSED
 CONDUIT, EVEN IF PAINTED, ATTACHED TO THE COLUMN AND
 INSIDE OF THE FASCIA DOES NOT MATCH THIS REQUIREMENT.
  
 PERMITTED SIGN SIZE: 30.3 SF
 PROPOSED SIGN SIZE: UNKNOWN
  
 BLADE SIGN
  
 9) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT BLADE SIGNS BE MOUNTED WITHIN THE TENANT'S LEASE
 LINE. THE ELEVATION DRAWING SHOWS THE BLADE SIGN
 OUTSIDE OF THE SWEETGREEN LEASE LINE.
  
 10) THE ROSEMARY SQUARE TENANT SIGN CRITERIA LIMIT THE
 SIGN COPY TO TRADE NAMES ONLY. THE USE OF THE LOGO "SG"
 IS ONLY PERMITTED AS A WAIVER I. A WAIVER I REQUIRES
 WRITTEN APPROVAL FROM CITYPLACE RETAIL.
  
 11) THE ROSEMARY SQUARE TENANT SIGN CRITERIA REQUIRE
 THAT THE SIGN COPY AREA SHALL MAINTAIN A MARGIN AT
 LEAST THREE (3) INCHES FROM ANY EDGE OF THE PERCEIVED
 SIGN AREA. PROVIDE VERTICAL DIMENSION FROM EITHER SIDE
 OF THE LETTERS TO THE EDGE OF THE SIGN FACE THAT
 VERIFIES THIS REQUIREMENT.
  
 12) PROVIDE VERIFICATION THAT THE DEDICATED PRIMARY
 SIGN CIRCUIT AND DISCONNECT ARE BEHIND THE WALL WITHIN
 THE STORE AND THE WIRING FROM THOSE TO THE SIGN WILL BE
 THROUGH THE WALL TO THE INTERNAL POWER SUPPLY AND NOT
 VISIBLE TO THE PUBLIC IN ACCORDANCE WITH THE ROSEMARY
 SQUARE TENANT SIGN CRITERIA. THIS MAY BE DONE AS A NOTE
 ON THE PLANS.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446