| Plan Review Stops For Permit 21091104 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-11-22 |
Time |
12:47 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-11-22 |
Time |
12:47 |
Sent To |
|
|
| Notes |
| 2021-11-22 12:47:36 | PROJECT GIVEN ADDRESS OF 1136 21ST ST. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-10-31 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-31 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-31 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2021-10-31 12:06:36 | PLEASE CONTACT [email protected] FOR GYM TO BE ISSUED AN | | | ADDRESS OR CALL 561-805-6659 |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
2 |
Status |
P |
Date |
2022-08-04 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
2022-06-29 |
Time |
09:46 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
2022-08-04 |
Time |
14:48 |
Sent To |
|
|
| Notes |
| 2022-06-29 09:51:42 | | | | REQUIREMENT COMPLETED - PASSED | | | PUBLIC PROJECT SUBJECT TO PUBLIC ART REQUIREMENT PER | | | CITY ORDINANCE - EMAIL [email protected]. | | | | | | | | | |
|
|
| Review Stop |
AIPP |
ART IN PUBLIC PLACES |
| Rev No |
1 |
Status |
F |
Date |
2021-09-27 |
|
|
Cont ID |
|
| Sent By |
scwelter |
Date |
2021-09-27 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
scwelter |
Date |
2021-09-27 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2021-09-27 14:37:32 | SUBJECT TO PUBLIC ART REQ UNDER PUBLIC PROJECTS. 1% OF | | | TOAL CONSTRUCTION MUST BE ALLOCATED WITIN THE PUBLIC | | | ART ACCOUNT. | | | ALL APPROPRIATIONS AND AUTHORIZATIONS FOR THE NEW | | | CONSTRUCTION, RENOVATION OR REMODELING OF ELIGIBLE | | | PUBLIC IMPROVEMENTS SHALL INCLUDE AN AMOUNT OF NOT LESS | | | THAN ONE PERCENT OF THE TOTAL CONSTRUCTION COSTS TO BE | | | DEPOSITED IN THE PUBLIC ART ACCOUNT. | | | (1) ELIGIBLE PUBLIC PROJECTS SUBJECT TO THE PUBLIC ART | | | ASSESSMENT SHALL BE: | | | (I) ANY PUBLIC BUILDING, FACILITY OR STRUCTURE WHICH | | | PERMITS PUBLIC OCCUPANCY OF ALL OR A PORTION THEREOF, | | | INCLUDING BUT NOT LIMITED TO FIRE STATIONS, POLICE | | | STATIONS, AND PUBLIC COMMUNITY CENTERS. | | | (II) ANY VERTICAL CONSTRUCTION WITHIN A PUBLIC PARK OR | | | RECREATION FACILITY. | | | (III) A SIDEWALK, PEDESTRIAN OR BICYCLE PATH PROJECT | | | WHERE SUFFICIENT LOCATION, SPACE, UTILITIES AND OTHER | | | ELEMENTS TO ACCOMMODATE PUBLIC ART EXIST, AS DETERMINED | | | BY ENGINEERING AND PLANNING STAFF AND THE PUBLIC ART | | | ADMINISTRATOR. | | | CONTAT SYBILLE [email protected] OR X1521 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-02 |
Time |
09:24 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-02 |
Time |
09:24 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-20 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-20 |
Time |
10:26 |
Sent To |
|
|
| Notes |
| 2022-07-20 10:38:50 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT). | | | | | | 2) SURVEY PROVIDED APPEARS TO BE OUT OF DATE - SHOWING | | | THE INCORRECT FLOOD ZONE INFORMATION - PLEASE PROVIDE | | | AN UPDATED SURVEY. | | | | | | 3) THE DRAWINGS SHOW OCCUPANCY TYPE AS A3 (WHICH IS FOR | | | A GYMNASIUM WITHOUT SEATING) - SHOULD BE A4. FBC | | | CHAPTER 3 | | | | | | 4) THE DRAWING SHOWS A KITCHEN - IF THE BUILDING WILL | | | BE USED FOR OTHER USES OTHER THAN A GYMNASIUM - PLEASE | | | SPECIFY USE AND SHOW EGRESS CALCULATIONS FOR SUCH - FBC | | | 1004.3 MULTIPLE FUNCTION OCCUPANT LOAD. | | | WHERE AN AREA UNDER CONSIDERATION CONTAINS MULTIPLE | | | FUNCTIONS HAVING DIFFERENT OCCUPANT LOAD FACTORS, THE | | | DESIGN OCCUPANT LOAD FOR SUCH AREA SHALL BE BASED ON | | | THE FLOOR AREA OF EACH FUNCTION CALCULATED | | | INDEPENDENTLY. | | | | | | 5) SEPARATE PERMITS ARE REQUIRED FOR THE EXISTING | | | BUILDING ADDITIONS (EXISTING BUILDING IS A SEPARATE | | | BUILDING), EXTERIOR SIGNS, SITE LIGHTING, SIDE WALKS - | | | PLEASE ACKNOWLEDGE THIS. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-09 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-09 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2021-12-09 15:03:55 | NEW BUILDING | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | 1) PLEASE PROVIDE A SOIL REPORT (GEOTECHNICAL REPORT). | | | | | | 2) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, EXTERIOR | | | DOORS, EXTERIOR GLASS BLOCKS, ROOFING SYSTEMS, ETC. - | | | ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | | APPROVED BY THE BUILDING DESIGNER OF RECORD FBC 107.3.4 | | | | | | 3) ACCESSIBLE RESTROOMS - PLEASE STATE THAT THE MIRROR | | | DIMENSIONS ARE FROM THE FINISHED FLOOR TO THE | | | "REFLECTIVE SURFACE" FBC A 603.3 MIRRORS. | | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | | FLOOR OR GROUND. | | | | | | 4) DRAWING A-5.20 DETAIL NUMBER 8 STAIR SECTION - | | | PLEASE SHOW THE BOTTOM STAIR HANDRAIL EXTENSION TO | | | SLOPE DOWN PER FBC 1014.6 HANDRAIL EXTENSIONS. | | | HANDRAILS SHALL RETURN TO A WALL, GUARD OR THE WALKING | | | SURFACE OR SHALL BE CONTINUOUS TO THE HANDRAIL OF AN | | | ADJACENT FLIGHT OF STAIRS OR RAMP RUN. WHERE HANDRAILS | | | ARE NOT CONTINUOUS BETWEEN FLIGHTS, THE HANDRAILS SHALL | | | EXTEND HORIZONTALLY NOT LESS THAN 12 INCHES (305 MM) | | | BEYOND THE TOP RISER AND CONTINUE TO SLOPE FOR THE | | | DEPTH OF ONE TREAD BEYOND THE BOTTOM RISER. | | | | | | 5) PLEASE SHOW HAND RAILS TO RETURN TO A WALL, GUARD OR | | | THE WALKING SURFACE - FBC 1014.6 | | | | | | 6) SEPARATE PERMITS ARE REQUIRED FOR THE EXISTING | | | BUILDING ADDITIONS (EXISTING BUILDING IS A SEPARATE | | | BUILDING), EXTERIOR SIGNS, SITE LIGHTING, SIDE WALKS - | | | PLEASE ACKNOWLEDGE THIS. | | | | | | 7) ROOFING SYSTEMS, WINDOW AND DOOR PRODUCT APPROVALS, | | | ETC. - MAY BE DEFERRED SUBMITTALS BY LISTING ITEMS TO | | | BE DEFERRED ON THE CONSTRUCTION DOCUMENTS - 107.3.4.1 | | | DEFERRED SUBMITTALS. FOR THE PURPOSES OF THIS SECTION, | | | DEFERRED SUBMITTALS ARE DEFINED AS THOSE PORTIONS OF | | | THE DESIGN THAT ARE NOT SUBMITTED AT THE TIME OF THE | | | APPLICATION AND THAT ARE TO BE SUBMITTED TO THE | | | BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. DEFERRAL | | | OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR APPROVAL OF | | | THE BUILDING OFFICIAL. THE REGISTERED DESIGN | | | PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST THE | | | DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS FOR | | | REVIEW BY THE BUILDING OFFICIAL. DOCUMENTS FOR DEFERRED | | | SUBMITTAL ITEMS SHALL BE SUBMITTED TO THE REGISTERED | | | DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE WHO SHALL | | | REVIEW THEM AND FORWARD THEM TO THE BUILDING OFFICIAL | | | WITH A NOTATION INDICATING THAT THE DEFERRED SUBMITTAL | | | DOCUMENTS HAVE BEEN REVIEWED AND FOUND TO BE IN GENERAL | | | CONFORMANCE TO THE DESIGN OF THE BUILDING. THE DEFERRED | | | SUBMITTAL ITEMS SHALL NOT BE INSTALLED UNTIL THE | | | DEFERRED SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE | | | BUILDING OFFICIAL. | | | | | | 8) PLEASE PROVIDE A SURVEY. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-26 |
Time |
11:42 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-26 |
Time |
11:18 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-12-21 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2021-12-21 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2021-12-21 |
Time |
14:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E-LOWVOLT |
ELECTRICAL LOW VOLTAGE |
| Rev No |
1 |
Status |
P |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-26 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-07-26 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2022-07-26 11:41:00 | VOICE AND DATA AS PER PLANS JLEAHY |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
P |
Date |
2022-07-05 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2022-07-05 |
Time |
|
Rev Time |
0.00 |
| Received By |
rrossano |
Date |
2022-07-05 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2021-11-08 |
|
|
Cont ID |
|
| Sent By |
rrossano |
Date |
2021-11-08 |
Time |
|
Rev Time |
|
| Received By |
rrossano |
Date |
2021-11-08 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-08 11:43:30 | PLEASE PROVIDE STATUS OF SITE PLAN APPROVAL. | | | | | | RICK ROSSANO, SENIOR PROJECT COORDINATOR, | | | CITY OF WPB ENGINEERING SERVICES DEPARTMENT | | | DIRECT: (561) 494-1098, FAX: (561) 494-1116, MOBILE: | | | (561) 246-9525 | | | EMAIL: [email protected] | | | HTTPS://WWW.WPB.ORG/GOVERNMENT/ENGINEERING/ENGINEERING- | | | STANDARDS | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2022-07-01 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2022-07-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2022-06-30 |
Time |
11:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-11-03 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-11-03 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-10-28 |
Time |
15:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-30 |
Time |
11:43 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-29 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2022-08-30 11:44:50 | GAS WORK DELETED- NO REVIEW, NO PERMIT REQUIRED. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-07-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-11 |
Time |
10:31 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-08 |
Time |
16:49 |
Sent To |
|
|
| Notes |
| 2022-07-11 10:31:37 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT-21091104 | | | 7/11/2022 | | | | | | CODES IN EFFECT: | | | FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLAN SHEET K301 DETAIL 1 IS LABELED WATER & GAS PLAN | | | HOWEVER NO GAS APPLIANCES ARE IDENTIFIED ON THE | | | DRAWING. PLEASE PROVIDE A GAS APPLIANCE EQUIPMENT | | | LAYOUT PLAN AND EQUIPMENT SCHEDULE- SEC. 107.2.1 WPB. | | | | | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL NEW | | | APPLIANCES AND EQUIPMENT- SECTIONS 305.1 AND 623.1 FBC | | | FG. | | | | | | 3) PROVIDE COMBUSTION AIR CALCULATIONS FOR ALL NEW | | | GAS-FIRED APPLIANCES AND EQUIPMENT AND INDICATE HOW THE | | | AIR WILL BE SUPPLIED- SECTION 304.1 FBC FG. | | | | | | 4) PROVIDE A COMPLETE GAS RISER DRAWING- SEC. | | | 107.3.5.1.5 WPB. THE RISER SHALL INCLUDE THE FOLLOWING | | | ITEMS: | | | A) TYPE OF GAS- NATURAL OR LP. | | | B) DELIVERY PRESSURE AT THE METER. | | | C) TOTAL BTU LOAD AND INDIVIDUAL APPLIANCE BTU LOADS. | | | D) TYPES AND SIZES OF PIPING. | | | E) TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM THE METER | | | TO THE MOST REMOTE APPLIANCE OUTLET. | | | F) BRANCH AND CUT PIPE LENGTH MEASUREMENTS. | | | G) LOCATIONS OF REGULATORS, SHUTOFF VALVES, AND PIPE | | | UNIONS. | | | H) OUTLET PRESSURES AT REGULATORS. | | | I) LOCATIONS AND TYPES OF PIPE SLEEVES. | | | K) PIPE SIZING TABLES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-02 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-10-26 |
Time |
15:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-10-11 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-10-11 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-09-14 |
Time |
12:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-02 |
Time |
09:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-08-17 |
Time |
06:14 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2022-07-26 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-07-26 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-06-29 |
Time |
06:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2022-01-14 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-01-14 |
Time |
14:28 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-10-27 |
Time |
09:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-11-08 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2022-11-08 |
Time |
20:01 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2022-10-26 |
Time |
15:31 |
Sent To |
|
|
| Notes |
| 2022-11-08 20:03:26 | 11/8/22 PER THE 11/3/22 EMAIL FROM MARGGARETT CHARLES, | | | FINANCIAL ANALYST II, PALM BEACH COUNTY, ARTICLE 13 | | | STATES THAT THE CONSTRUCTION OF PUBLICLY OWNED AND | | | OPERATED GOVERNMENTAL BUILDINGS OR FACILITIES IS EXEMPT | | | FROM PAYMENT OF IMPACT FEES. | | | | | 2022-10-26 15:31:43 | 10/26/22 EMAILED IMPACT OFFICE TO REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-09 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-09 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2021-12-09 15:36:33 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | | | | UPON APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE | | | RECEIPT TO YOUR PROJECT OR EMAIL IT TO | | | [email protected] . | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-02 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-02 |
Time |
10:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2022-09-21 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-09-21 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-09-21 |
Time |
13:19 |
Sent To |
|
|
| Notes |
| 2022-09-21 13:20:13 | 4TH REVIEW FMC | | | PERMIT: 21091104 | | | | | | CODES IN EFFECT: 2020 | | | | | | FBC- FLORIDA BUILDING CODE | | | FMC- FLORIDA MECHANICAL CODE | | | FEC- FLORIDA ENERGY CONSERVATION | | | FGC- FLORIDA FUEL GAS | | | FEX- FLORIDA EXISTING BUILDING CODE | | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | | F.S.- FLORIDA STATUTES | | | FAC- FLORIDA ACCESSIBILITY CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THERE ARE 2 M.03 SHEETS AND NO M.04. THE M.03 THAT | | | HAS THE IONIZER VENTILATION CALCULATIONS FOR AHU-1 IS | | | GOOD. THE M.03 SHEET THAT IS THE NEWLY ADDED SHEET | | | SHOULD BE LABELED M0.4 AND THE GPS INFORMATION IS | | | BLURRY AND CANNOT BE READ. PLEASE SUBMIT A CLEAR M0.4 | | | DRAWING TO BE REVIEWED. FBC 107.3.5 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2022-08-31 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-08-31 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-08-31 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2022-08-31 13:31:43 | PROVIDE THE GLOBAL PLASMA CALCULATIONS SHOWING THE | | | REQUIRED OUTDOOR AIR PER FMC 403.3.1.1 AND THE REDUCED | | | OUTDOOR AIR TOTAL. ALSO PROVIDE ON THE GPS CALCULATIONS | | | THE CONTAMINANTS THAT WILL BE REDUCED. SHEET M03 IS NOT | | | READABLE. FMC 403.2 | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2022-07-12 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-07-12 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-07-12 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2022-07-12 10:48:20 | PLEASE PROVIDE STATISTICAL DATA FOR OUR BUILDING | | | OFFICIAL TO APPROVE THE USE OF THE EXCEPTION TO FMC | | | 403.3.1.1 AS CHOSING TO USE THE ARCHITECTS EGRESS | | | NUMBERS IS NOT STATISTICAL DATA. | | | | | | AS AN ALTERNATIVE THE DESIGNER COULD USE THE EXCEPTION | | | FOR FMC 403.2 | | | | | | 403.2 OUTDOOR AIR REQUIRED. THE MINIMUM OUTDOOR AIRFLOW | | | RATE SHALL BE DETERMINED IN ACCORDANCE WITH SECTION | | | 403.3. | | | | | | EXCEPTION: WHERE THE REGISTERED DESIGN PROFESSIONAL | | | DEMONSTRATES THAT AN ENGINEERED VENTILATION SYSTEM | | | DESIGN WILL PREVENT THE MAXIMUM CONCENTRATION OF | | | CONTAMINANTS | | | FROM EXCEEDING THAT OBTAINABLE BY THE RATE OF OUTDOOR | | | AIR VENTILATION DETERMINED IN ACCORDANCE WITH SECTION | | | 403.3, THE MINIMUM REQUIRED RATE OF OUTDOOR AIR SHALL | | | BE REDUCED | | | IN ACCORDANCE WITH SUCH ENGINEERED SYSTEM DESIGN. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-22 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2021-11-22 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2021-11-22 |
Time |
08:41 |
Sent To |
|
|
| Notes |
| 2021-11-22 08:42:08 | 1ST REVIEW FBC-2020 MECHANICAL | | | PERMIT-21091104 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING | | | THAT THE KITCHEN HOODS WILL REQUIRE A SEPARATE PERMIT | | | APPLICATION, DOCUMENTS AND PLAN REVIEW AS THEY WILL NOT | | | BE REVIEWED UNDER THIS PERMIT. FBC 107.2.1 | | | | | | 2) PLEASE SHOW THE OUTDOOR AIR CALCULATIONS USING FBC M | | | 403.3.1.1 AND TABLE 403.3.1.1. THE SPECTATOR AREAS | | | APPEAR TO BE LOW. | | | | | | 3) SHEET M1.1 PLEASE SHOW THE FIRE DAMPERS IN THE RATED | | | WALLS SEPARATING THE STAGE FROM THE STORAGE AREAS. FBC | | | M 607 | | | | | | 4) SHEET M1.1: PLEASE SHOW THE FIRE DAMPER FOR THE | | | EXHAUST DUCT LEAVING THE MOP SINK AREA IN THE KITCHEN. | | | FBC M 607 | | | | | | 5) PLEASE PROVIDE THE CONDENSATE DRAINAGE PIPING | | | DIAGRAM INCLUDING PIPE MATERIAL, SIZES AND OUTDOOR | | | TERMINATION LOCATION. FBC M 307 | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2022-09-22 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-09-22 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-09-22 |
Time |
13:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2022-08-30 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-08-30 |
Time |
12:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-08-29 |
Time |
17:00 |
Sent To |
|
|
| Notes |
| 2022-08-30 12:52:15 | 3RD REVIEW FBC-2020 PLUMBING | | | PERMIT- 21091104 | | | 8/30 2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. THE SUBMITTED PERMIT | | | APPLICATIONSA FOR THE BACKFLOW PREVENTER AND GREASE | | | INTERCEPTOR HAVE BEEN LOCKED OUT OF THE REVIEW FOR THE | | | MAIN PERMIT. THE APPLICATIONS AND PLANS SHALL BE | | | SUBMITTED SEPARATELY AS PRIMARY PERMITS. PLEASE REVIEW | | | THE NOTICE PROVIDED ON THE PREVIOUS REVIEWS BELOW- | | | | | | 1) DUE TO A CHANGE IN PROCESS, THE POTABLE WATER | | | BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMIT ARE | | | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE | | | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO | | | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED | | | BY EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL | | | CHANGE THE REVIEW STATUS TO PASS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-08 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-08 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-07-08 16:49:11 | 2ND REVIEW FBC-2020 PLUMBING | | | PERMIT- 21091104 | | | 7/8/2022 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | | | | 16) FAILED. A5.30: PROVIDE DOWNSPOUT CONNECTION SUPPORT | | | AND TERMINATION DETAILS. PLEASE NOTE THE SPOUTS SHALL | | | TERMINATE NOT LESS THAN 1 FT. FROM THE BUILDING- 1101.6 | | | FBC P. NOT PROVIDED. | | | | | | NEW COMMENT: | | | 1) DUE TO A CHANGE IN PROCESS, THE POTABLE WATER | | | BACKFLOW PERMIT AND GREASE INTERCEPTOR PERMIT ARE | | | REQUIRED TO BE SUBMITTED PRIOR TO ISSUANCE OF THE | | | PRIMARY PERMIT. YOU CAN SUBMIT AN APPLICATION "TBD" (TO | | | BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR SELECTED | | | BY EMAILING A COMPLETED PERMIT APPLICATION TO | | | [email protected] . YOU WILL RECEIVE INSTRUCTIONS | | | TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND | | | PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS | | | REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES | | | AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE | | | PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL | | | CHANGE THE REVIEW STATUS TO PASS. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-01 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-01 |
Time |
08:56 |
Sent To |
|
|
| Notes |
| 2021-12-01 15:38:25 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 21091104 | | | 12/1/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) SHEET A-400: FBC-ACC COMPLIANCE DETAILS- | | | A) LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE | | | DIAGRAM FOR THE WATER CLOSET- SECTION 604.3. | | | B) LENGTH AND WIDTH DIMENSIONS OF THE CLEAR FLOOR SPACE | | | DIAGRAMS FOR THE LAVATORIES- 606.2. | | | C) TURNING SPACE DIAMETER- 304.3. | | | D) THE TOILET COMPARTMENT DOOR SHALL NOT SWING INTO THE | | | CLEAR FLOOR SPACE REQUIRED FOR THE LAVATORY- 603.2.3. | | | E) SHOW THE HEIGHTS OF THE MIRRORS FROM THE FINISHED | | | FLOORS TO THE REFLECTIVE SURFACES- SECTION 603.3 | | | F) PLEASE SHOW THE ACTUAL LENGTH OF THE SIDE GRAB BAR | | | AT THE WATER CLOSET AND THE MINIMUM 54-INCH EXTENSION | | | FROM THE REAR WALL- SECTION & FIGURE 604.5.1 & FIGURES | | | 604.5.1 & 604.5.2. | | | G) PLEASE SHOW THE 36 MIN. LENGTH MEASUREMENT FOR THE | | | REAR GRAB BAR AT THE WATER CLOSET- SECTION & FIGURE | | | 604.5.2. | | | | | | 2) A-410: SEE COMMENT #1 ABOVE AND SHOW COMPLIANCE FOR | | | THE MEN'S BATHROOMS. | | | | | | 3) P0.1 & A4.00: PLEASE ADD THE MAKES AND MODELS OF THE | | | DRINKING FOUNTAINS TO THE FIXTURE SPECIFICATION TABLE- | | | SECTION 410.1 FBC P. | | | | | | 4) A-100, A-400: SHOW THE CLEAR FLOOR SPACE DIAGRAM AND | | | DIMENSIONS FOR THE WHEELCHAIR ACCESSIBLE DRINKING | | | FOUNTAINS- SECTION 306 FBC ACC. | | | | | | 5) A-100, A-400: INDICATE PROTRUSION LIMITS COMPLIANCE | | | FOR THE DRINKING FOUNTAINS- SECTION 307.2 FBC ACC. | | | | | | 6) P0.1, P1.1, P3.1: THE CLEAR WATER WASTE FROM THE | | | HAND SINK AND THE ICE MAKER SHALL NOT DRAIN INTO THE | | | GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. | | | | | | 7) P0.1, P1.1 & P3.1 GREASE INTERCEPTOR: A) PROVIDE | | | SIZING CALCULATIONS- SECTIONS 1003.3.5 & 1003.3.7 FBC | | | P. B) PROVIDE AND EQUIPMENT SCHEDULE INDICATING THE | | | MAKE AND MODEL OF THE INTERCEPTOR, CAPACITY AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5 & | | | 1003.3.7. C) PLEASE NOTE A SEPARATE PERMIT IS REQUIRED | | | FOR INSTALLATION OF THE INTERCEPTOR. | | | | | | 8) P1.1 & P3.1: URINALS ARE NOT INCLUDED IN THE | | | DEFINITION OF BATHROOM GROUP AND THEIR DRAINS CANNOT | | | CONNECT TO A HORIZONTAL WET VENT- SECTIONS 202 & 912.1 | | | FBC P. IN ORDER FOR THE HWC DOWNSTREAM OF THE URINAL TO | | | BE VENTED TO CODE, THE HWC DRAIN CONNECTION MUST BE | | | RELOCATED TO A POINT DOWNSTREAM OF THE URINAL BRANCH | | | CONNECTION TO THE 4-INCH DRAIN. | | | | | | 9) P2.1 & P3.3: INDICATE HOW TEMPERED WATER WILL BE | | | DELIVERED FROM THE LAVATORIES- 419.5 FBC P. | | | | | | 10) P2.1 & P3.3: REFER TO TABLE 608.3 FBC P AND PROVIDE | | | AN EQUIPMENT SCHEDULE FOR THE REQUIRED BACKFLOW | | | PREVENTERS FOR SUPPLY LINES TO THE DISHWASHER, ICE | | | MAKER, AND THE ICE TEA AND COFFEE BREWERS. PLEASE | | | PROVIDE A BF SYMBOL AT THE DISHWASHER. | | | | | | 11) P0.2: PLEASE PROVIDE THE EFFICIENCY RATING OF THE | | | WATER HEATER AND SUBMIT MANUFACTURERS SPECIFICATIONS- | | | TABLE C404.2 FBC EC. REVISE THE ENERGYGAUGE REPORT TO | | | INCLUDE THE COMPLIANCE DATA FOR THE WATER HEATER AND | | | PIPING- C101.5.1. | | | | | | 12) A1.10: IT APPEARS THAT ROOF DRAINAGE PLANS AND | | | CALCULATIONS FOR THE LOWER ENTRANCE CANOPIES HAVE NOT | | | BEEN PROVIDED. PLEASE INDICATE HOW STORMWATER FROM | | | THESE AREAS WILL DRAIN TO APPROVED PLACES OF DISPOSAL- | | | SECTION 1101.2 FBC P. | | | | | | 13) A1.10: PLEASE SHOW ON THE CIVIL PLANS THE DISCHARGE | | | LOCATIONS OF THE DOWNSPOUTS TO APPROVED DRAINAGE | | | LOCATIONS SUCH STORM DRAINS, CATCH BASINS OR TO GRADED | | | AREAS- SECTION 1101.2 FBC P. | | | | | | 14) A5.30: PROVIDE THE DIMENSIONS OF THE SCUPPERS- | | | SECTION 1108.3 FBC P. | | | | | | 15) A5.40 & P0.1: PROVIDE THE MAKE AND MODEL OF THE | | | ROOF DRAIN ASSEMBLY AND ADD IT TO THE FIXTURE SCHEDULE- | | | SECTION 1105.1 FBC P. | | | | | | 16) A5.30: PROVIDE DOWNSPOUT CONNECTION SUPPORT AND | | | TERMINATION DETAILS. PLEASE NOTE THE SPOUTS SHALL | | | TERMINATE NOT LESS THAN 1 FT. FROM THE BUILDING- 1101.6 | | | FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-07-08 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-07-08 |
Time |
17:34 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-07-08 |
Time |
14:29 |
Sent To |
|
|
| Notes |
| 2022-07-08 17:35:35 | GREASE INTERCEPTOR UNDER PERMIT- 22090360 |
|
|
| Review Stop |
P-GREASE |
GREASE INTERCEPTOR/TRAP REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-01 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-01 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2021-12-01 15:51:01 | 1ST REVIEW FBC-2020 PLUMBING- GREASE INTERCEPTOR. | | | PERMIT- 21091104 | | | 12/1/2021 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 | | | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION | | | 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) P0.1, P1.1 & P3.1: PLACE A NOTE ON THE PLAN | | | INDICATING THE GREASE INTERCEPTOR WILL BE INSTALLED | | | UNDER A SEPARATE PERMIT- SECTION 105.1 & 107.1 WPB. | | | | | | 2) P0.1, P1.1, P3.1: THE CLEAR WATER WASTE FROM THE | | | HAND SINK AND THE ICE MAKER SHALL NOT DRAIN INTO THE | | | GREASE INTERCEPTOR- SECTION 1003.3.1 FBC P. | | | | | | 3) P0.1, P1.1 & P3.1: GREASE INTERCEPTOR: A) PROVIDE | | | SIZING CALCULATIONS- SECTIONS 1003.3.5 & 1003.3.7 FBC | | | P. B) PROVIDE AND EQUIPMENT SCHEDULE INDICATING THE | | | MAKE AND MODEL OF THE INTERCEPTOR, CAPACITY AND SUBMIT | | | MANUFACTURER'S SPECIFICATIONS- SECTIONS 1003.3.5 & | | | 1003.3.7 FBC P. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|
|
| Review Stop |
P-IRRIGATE |
IRRIGATION REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2021-12-01 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2021-12-01 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2021-12-01 15:46:05 | IRRIGATION SYSTEM UNDER PERMIT- 21121122. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-20 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-20 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2022-07-20 10:39:52 | ROOFING SYSTEM TO BE DEFERRED |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-09 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-09 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2021-12-09 15:37:01 | SEE BUILDING PLAN REVIEW |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
5 |
Status |
P |
Date |
2022-11-02 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-11-02 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-11-02 |
Time |
10:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
4 |
Status |
F |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-29 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-29 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2022-09-29 10:12:09 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THE PROVIDED SURVEY DOES NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
3 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-02 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-02 |
Time |
09:38 |
Sent To |
|
|
| Notes |
| 2022-09-02 09:40:02 | SIGNATURE REVIEW | | | | | | CORRECTIONS NEEDED - | | | | | | 1) SURVEY AND THE SOIL REPORT DO NOT SHOW AS DIGITALLY | | | SIGNED IN ADOBE READER - | | | | | | SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE | | | DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | | SPECIFIC TYPE OF E-SIGNATURE). | | | |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-20 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-20 |
Time |
10:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-09 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-09 |
Time |
15:50 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
4 |
Status |
P |
Date |
2022-09-29 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-29 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-29 |
Time |
10:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
3 |
Status |
F |
Date |
2022-09-02 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-09-02 |
Time |
09:34 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-09-02 |
Time |
09:34 |
Sent To |
|
|
| Notes |
| 2022-09-02 09:38:34 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | A) PAGE 8 OF THE THRESHOLD INSPECTOR FORMS REQUIRES THE | | | PROPERTY OWNERS SIGNATURE - - - THRESHOLD INSPECTOR: | | | WPB AMENDMENT 110.8.1 W.P.B. CONSTRUCTION SERVICES | | | DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A SPECIAL | | | INSPECTOR AS REQUIRED BY 553.79(5) FLORIDA STATUTES TO | | | THE MINIMUM INSPECTIONS REQUIRED BY THIS CODE. | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2022-07-20 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2022-07-20 |
Time |
10:40 |
Sent To |
|
|
| Notes |
| 2022-07-20 10:48:07 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE | | | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". | | | YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION | | | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. | | | | | | C) PLEASE PROVIDE COPIES OF LICENSES PER "GUIDELINES | | | AND POLICIES FOR PROJECTS CONCERNING THRESHOLD/SPECIAL | | | INSPECTORS AND RESIDENT INSPECTORS" | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
THRESHOLD |
THRESHOLD INSPECTOR DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
2021-12-09 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-09 |
Time |
15:37 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-09 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2021-12-09 15:40:40 | THRESHOLD BUILDING | | | | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | PLEASE READ AND FILL OUT THE REQUIRED DOCUMENTS PER THE | | | "GUIDELINES AND POLICIES FOR PROJECTS CONCERNING | | | THRESHOLD/SPECIAL INSPECTORS AND RESIDENT INSPECTORS". | | | YOU CAN E MAIL ME AND ASK FOR A COPY. | | | | | | A) FBC (CITY AMENDMENTS)110.8.1 THRESHOLD INSPECTION | | | PLAN. THE ENFORCING AGENCY SHALL REQUIRE A SPECIAL | | | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A | | | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION | | | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL | | | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING | | | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR | | | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE | | | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE | | | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT | | | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE | | | WITH THE PERMITTED DOCUMENTS. | | | | | | B) THRESHOLD INSPECTOR: WPB AMENDMENT 110.8.1 W.P.B. | | | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD | | | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY 553.79(5) | | | FLORIDA STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY | | | THIS CODE. THE THRESHOLD INSPECTION FORMS ARE REQUIRED | | | TO BE FILED OUT BY ALL PARTIES WITH INTEREST, NOTARIZED | | | AND RETURNED TO THIS OFFICE, AND REVIEWED AND APPROVED | | | BEFORE PERMIT ISSUANCE WILL TAKE PLACE. | | | | | | C) THRESHOLD BLDG. REQUIRED STATEMENT: W.P.B. AMENDMENT | | | 110.8.4.4 ALL PLANS FOR THE BUILDING WHICH ARE REQUIRED | | | TO BE SIGNED AND SEALED BY THE ARCHITECT OR ENGINEER OF | | | RECORD SHALL CONTAIN A STATEMENT THAT, TO THE BEST OF | | | THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE PLANS AND | | | SPECIFICATIONS COMPLY WITH THE APPLICABLE MINIMUM | | | BUILDING CODES AND THE APPLICABLE FIRE-SAFETY STANDARDS | | | AS DETERMINED BY THE LOCAL AUTHORITY IN ACCORDANCE WITH | | | THIS SECTION AND CHAPTER 633 FLORIDA STATUTES. | | | | | | D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME OF | | | INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE RESUME | | | MUST BE ACCOMPANIED BY ALL CERTIFICATES AS SPECIFIED | | | HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE WILL | | | REVIEW THE RESUME. AFTER THE RESUME IS REVIEWED, AN | | | INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES | | | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST | | | MEETING THE ABOVE CRITERIA. | | | | | | | | | | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-10-11 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2022-10-11 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2022-10-11 |
Time |
09:30 |
Sent To |
|
|
| Notes |
| 2022-10-11 09:30:43 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 10.11.2022 | | | PERMIT NO.: 21091104 | | | ________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. SEPARATE PERMITS REQUIRED FOR: | | | | | | 1.1. LANDSCAPING | | | 1.2. FENCING/GATES | | | 1.3. SITE/PRIVACY WALLS | | | 1.4. SITE LIGHTING | | | 1.5. IRRIGATION | | | 1.6. GENERATOR | | | 1.7. SIGNAGE | | | 1.8. PARING LOT / STRIPING / HARDSCAPE | | | 1.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.) | | | | | | 2. AT THE TIME OF SUBMITTAL OF THE PERMIT APPLICATION | | | FOR FENCING/GATES SURROUNDING THE A/C EQUIPMENT | | | PADS/AREA TO THE WEST OF THE PROPOSED GYMNASIUM, PLEASE | | | NOTE THAT THIS EQUIPMENT NEEDS TO BE SCREENED FROM VIEW | | | WITH A WALL OR OPAQUE FENCE CONSISTING OF BRICK, | | | DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR | | | COMPARABLY DURABLE WOOD/STEEL. CHAIN LINK FENCING WITH | | | SLATS DOES NOT COMPLY WITH THIS REQUIREMENT. | | | | | | 3. AT THE TIME OF SUBMITTAL OF THE PERMIT APPLICATION | | | FOR THE BIKE RACKS, PLEASE NOTE THAT THE TYPE AND | | | SPACING OF THE RACKS SHALL COMPLY WITH THE CITY?S | | | STANDARDS AND DETAIL. PLEASE CONTACT THE CITY?S | | | PLANNING DIVISION TO OBTAIN THE MINIMUM SPECIFICATIONS. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-07-20 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2022-07-20 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2022-07-20 |
Time |
09:11 |
Sent To |
|
|
| Notes |
| 2022-07-20 09:48:32 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: 07.20.2022 | | | PERMIT NO.: 21091104 | | | ________________________________________ | | | | | | REVIEW STATUS: PASSED WITH PROVISOS | | | ________________________________________ | | | | | | THIS REVIEW HAS BEEN PASSED SUBJECT TO THE FOLLOWING | | | PROVISOS: | | | | | | 1. SEPARATE PERMITS REQUIRED FOR: | | | | | | 1.1. LANDSCAPING | | | 1.2. FENCING/GATES | | | 1.3. SITE/PRIVACY WALLS | | | 1.4. SITE LIGHTING | | | 1.5. IRRIGATION | | | 1.6. GENERATOR | | | 1.7. SIGNAGE | | | 1.8. PARING LOT / STRIPING / HARDSCAPE | | | 1.9. SITE FIXTURES (I.E. BIKE RACKS, ETC.) | | | | | | 2. AT THE TIME OF SUBMITTAL OF THE PERMIT APPLICATION | | | FOR FENCING/GATES SURROUNDING THE A/C EQUIPMENT | | | PADS/AREA TO THE WEST OF THE PROPOSED GYMNASIUM, PLEASE | | | NOTE THAT THIS EQUIPMENT NEEDS TO BE SCREENED FROM VIEW | | | WITH A WALL OR OPAQUE FENCE CONSISTING OF BRICK, | | | DECORATIVE CONCRETE, OTHER DECORATIVE MASONRY, OR | | | COMPARABLY DURABLE WOOD/STEEL. CHAIN LINK FENCING WITH | | | SLATS DOES NOT COMPLY WITH THIS REQUIREMENT. | | | | | | 3. AT THE TIME OF SUBMITTAL OF THE PERMIT APPLICATION | | | FOR THE BIKE RACKS, PLEASE NOTE THAT THE TYPE AND | | | SPACING OF THE RACKS SHALL COMPLY WITH THE CITY?S | | | STANDARDS AND DETAIL. PLEASE CONTACT THE CITY?S | | | PLANNING DIVISION TO OBTAIN THE MINIMUM SPECIFICATIONS. | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2022-01-14 |
|
|
Cont ID |
|
| Sent By |
jroach |
Date |
2022-01-14 |
Time |
13:18 |
Rev Time |
0.00 |
| Received By |
jroach |
Date |
2022-01-14 |
Time |
12:08 |
Sent To |
|
|
| Notes |
| 2022-01-14 13:18:53 | ZONING PLAN REVIEW | | | ________________________________________ | | | | | | DATE OF REVIEW: | | | PERMIT NO.: 21091104 | | | ________________________________________ | | | | | | REVIEW STATUS: FAILED | | | ________________________________________ | | | | | | PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN | | | REVIEW COMMENTS: | | | | | | 1. ALL LANDSCAPE PLANS, IRRIGATION PLANS, ETC. SHALL BE | | | REMOVED FROM THE BUILDING PERMIT SUBMITTAL AS A | | | SEPARATE LANDSCAPE PERMIT IS REQUIRED. | | | | | | 2. PURSUANT TO THE APPROVAL OF FORMAL SITE PLAN REVIEW | | | CASE NO. 19-06, THE FOLLOWING SHALL BE | | | PROVIDED/COMPLETED: | | | | | | 2.1. UTILITY LETTERS SHALL BE PROVIDED FROM ALL UTILITY | | | COMPANIES. | | | | | | 2.2. PER SEC. 94-233(C)(4) OF THE CITY'S ZLDRS, THE | | | MAXIMUM FAR ALLOWED IS 0.2 - THE SITE DATA TABLE | | | INDICATES 0.75 IS PERMITTED. PLEASE ADJUST THE PLAN | | | ACCORDINGLY. | | | | | | 2.3. PER SEC 94-233(B) OF THE CITY'S ZLDRS, THE MAXIMUM | | | BUILDING HEIGHT PERMITTED IS 40 FEET - THE SITE DATA | | | TABLE INDICATES 30 FEET. PLEASE ADJUST THE PLAN | | | ACCORDINGLY. | | | | | | 2.4. THE A/C EQUIPMENT PADS/AREA TO THE WEST OF THE | | | PROPOSED GYMNASIUM NEEDS TO BE SCREENED FROM VIEW WITH | | | A WALL OR OPAQUE FENCE CONSISTING OF BRICK, DECORATIVE | | | CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY | | | DURABLE WOOD/STEEL. CHAIN LINK FENCING WITH SLATS DOES | | | NOT COMPLY WITH THIS REQUIREMENT. ADDITIONALLY, THE | | | SHRUBS/HEDGES SHALL BE IN FRONT OF THE FENCE/WALL | | | (BETWEEN THE SIDEWALK AND THE FENCE/WALL). | | | ________________________________________ | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | ________________________________________ | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING: | | | | | | JOHN P. ROACH, AICP, PRINCIPAL PLANNER | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION | | | 401 CLEMATIS STREET - P.O. BOX 3147 | | | WEST PALM BEACH, FLORIDA 33402 | | | | | | P: 561.822.1448 | | | TTY: 800.955.8771 | | | E: [email protected] | | | | | | W: WPB.ORG | | | |
|
|