| Plan Review Stops For Permit 21091083 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2021-10-20 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-10-20 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-10-20 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2021-10-20 16:17:36 | ADDRESS APPROPRIATE FOR PROJECT. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
07:37 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-15 |
Time |
07:37 |
Sent To |
|
|
| Notes |
| 2022-03-15 07:38:27 | BUILDING AUDIT COMPLETE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-11 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-10 |
Time |
17:27 |
Sent To |
|
|
| Notes |
| 2022-02-11 09:34:32 | FIRST BUILDING AUDIT COMMENTS | | | | | | FBC SEVENTH EDITION (2020) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | 1) SUBMIT PRODUCT APPROVALS FOR THE ROOF COVERING | | | MATERIALS THAT HEVE BEEN APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. FBC AMENDMENTS 107.3.4 - PROVIDE | | | TWO SETS OF PRODUCT APPROVALS FOR THOSE PRODUCTS WHICH | | | ARE REGULATED BY FAC 61G20-3.001 PER FLORIDA STATUTE | | | 553.842 (5) THAT HAVE BEEN REVIEWED AND APPROVED IN | | | WRITING BY THE DESIGNER OF RECORD. PROVIDE TWO COMPLETE | | | PRODUCT APPROVALS WITH FL OR NOA NUMBERS INCLUDING | | | INSTALLATION INSTRUCTIONS AND MAXIMUM DESIGN PRESSURES | | | FOR EACH OF THE DIFFERENT ROOFING MATERIALS, WINDOW | | | (GLASS TYPES), STRUCTURAL MULLIONS AND EXTERIOR DOOR | | | TYPES. THESE ITEMS CAN BE DEFERRED IF REQUESTED, | | | HOWEVER, THE DOCUMENTS MUST BE SUBMITTED AND APPROVED | | | BY THE BUILDING DEPARTMENT BEFORE THEY CAN BE | | | INSTALLED. ONLY ONE SET IS REQUIRED TO BE UPLOADED FOR | | | ELECTRONICALLY SUBMITTED DOCUMENTS. | | | | | | 2) SUBMIT THE EVALUATION REPORT FOR THE SPRAY FOAM | | | INSULATION THAT WILL BE INSTALLED IN THE UN-VENTED | | | ATTIC. FBC AMENDMENTS 107.2.1 | | | | | | 3) SPECIFY THE SIZE AND LOCATION OF THE ATTIC ACCESS ON | | | THE PLANS. FBC-R807.1 | | | | | | 4) THE ROOF SHEATHING FASTENING SCHEDULE ON SHEET 4 | | | DOES NOT COMPLY WITH FBC-R803.2.3.1. THE FASTENING | | | SPACING REQUIREMENTS FOR A WIND SPEED OF 170 MPH IN | | | EXPOSURE C WITH TRUSSES 24 INCHES O.C. AND A SPECIFIC | | | GRAVITY OF 0.49 IS 4" O.C. AT THE EDGES AND IN THE | | | FIELD OF THE PLYWOOD PANEL IN ROOF ZONES 2 & 3. THE | | | SPACING CAN BE 6" O.C. AT THE EDGES AND THE FIELD OF | | | THE PANELS THAT ARE LOCATED A MINIMUM OF 4 FEET FROM | | | THE PERIMETER EDGE OF THE ROOF, INCLUDING 4 FEET ON | | | EACH SIDE OF RIDGES AND HIPS. | | | | | | 5) ON SHEET 3 THE BATHROOM WINDOW (W6) IS MARKED AS | | | MEETING EGRESS IN THE WINDOW SCHEDULE. PLEASE CORRECT. | | | FBC AMENDMENTS 107.2.1 | | | | | | 6) THE VALUATION HAS BEEN INCREASED BASED ON THE LATEST | | | ICC VALUATION DATA FROM $358,427.00 TO $366,509.00. FBC | | | AMENDMENTS 109.3 | | | A/C SPACE = 2307 X $148.33 = $342,197.31 | | | NON A/C SPACE = 406 X $ 59.88 = $24,311.28 | | | TOTAL = $366,509.59 | | | | | | 7) PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW EACH | | | OF THE AUDIT REVIEW COMMENTS HAS BEEN ADDRESSED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-03-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-03-15 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-02-10 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-02-10 |
Time |
10:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2022-03-15 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
jleahy |
Date |
2022-03-09 |
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-03-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-02-24 |
Time |
09:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-11 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-01-26 |
Time |
10:29 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-01-26 |
Time |
10:28 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-20 |
Time |
07:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2022-01-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-01-03 |
Time |
12:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2021-11-08 |
Time |
07:20 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2021-10-20 |
Time |
07:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2022-03-08 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2022-03-08 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2022-02-24 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2022-03-08 13:31:01 | RECEIPT MU-2022-08575 - $2491.56 PAID | | | | | 2022-02-24 08:00:47 | 2/24/22 EMAILED IMPACT OFFICE FOR REVIEW. LEM |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-10-15 |
Time |
|
Rev Time |
|
| Received By |
|
Date |
2021-10-15 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-10-15 08:34:10 | PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE | | | DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS | | | OFFICE. NOTIFICATION WILL OCCUR WHEN PLANS ARE NEAREST | | | FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE | | | OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL | | | IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME | | | THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM | | | CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS | | | TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF | | | |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2022-03-14 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-03-14 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-03-14 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2022-03-14 06:48:59 | MECHANICAL PP AUDIT APPROVED. ME |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2022-02-11 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-02-11 |
Time |
07:13 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-02-10 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2022-02-11 06:16:01 | 1ST PP MECHANICAL AUDIT FBC-2020 MECHANICAL | | | PERMIT-21091083 | | | | | | CODES IN EFFECT: | | | | | | FBC B- FLORIDA BUILDING CODE | | | FBC M- FLORIDA MECHANICAL CODE | | | FBC EC- FLORIDA ENERGY CONSERVATION | | | FBC FG- FLORIDA FUEL GAS | | | FBC EX- FLORIDA EXISTING BUILDING CODE | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | AUDIT RESULTS: DENIED. | | | | | | 1) THE DRYER EXHAUST DUCT SHALL MEET FBC RES M1502.4.1. | | | IT MUST BE 4 INCH NOMINAL IN DIAMETER. | | | | | | | | | M1502.4.1 MATERIAL AND SIZE. EXHAUST DUCTS SHALL HAVE A | | | SMOOTH INTERIOR FINISH AND BE CONSTRUCTED OF METAL | | | HAVING A | | | MINIMUM THICKNESS OF 0.0157 INCH (28 GAUGE). THE DUCT | | | SHALL BE 4 INCHES (102 MM) NOMINAL IN DIAMETER. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | MICHAEL EDWARDS | | | MECHANICAL EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL. 33401 | | | 561-805-6728 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2022-02-07 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2022-02-07 |
Time |
12:04 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2022-02-07 |
Time |
12:04 |
Sent To |
|
|
| Notes |
| 2022-02-07 12:05:17 | PLUMBING AUDIT APPROVED, LAC |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
4 |
Status |
P |
Date |
2022-03-11 |
|
|
Cont ID |
|
| Sent By |
ccole |
Date |
2022-03-10 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
ccole |
Date |
2022-03-10 |
Time |
13:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
3 |
Status |
P |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-26 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-26 |
Time |
09:38 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
2 |
Status |
F |
Date |
2022-01-15 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2022-01-15 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2022-01-15 |
Time |
11:00 |
Sent To |
|
|
| Notes |
| 2022-01-15 11:09:42 | FS553.791, AFFIDAVIT SIGNED ON 12/22/21 REFERS TO PLANS | | | PREPARED BY WILLIAM GENZ DATED 9/2/21. PLANS SUBMITTED | | | HAVE A REVISION DATE AFTER 9/2/21. FOR AN EXAMPLE, SEE | | | SHEET 1. THIS APPLIES TO OTHER SHEETS PREPARED BY OTHER | | | DESIGN PROFESSIONALS. A NUMBER OF PRODUCT APPROVALS | | | WERE SUBMITTED BUT WERE NOT REVIEWED BY THE PRIVATE | | | PROVIDER. | | | | | | |
|
|
| Review Stop |
PRIVATEPRV |
PRIVATE PROVIDER DOCUMENTS |
| Rev No |
1 |
Status |
F |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2021-11-01 |
Time |
|
Rev Time |
0.00 |
| Received By |
|
Date |
2021-11-01 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-01 17:34:12 | AFFIDAVITS REQUIRED PRIOR TO AUDIT FS553.791(1)H. | | | | | | |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
N |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
06:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-15 |
Time |
06:58 |
Sent To |
|
|
| Notes |
| 2022-03-15 07:02:41 | ROOFING PRODUCT APPROVALS HAVE BEEN DEFERRED. THE | | | ROOFING PRODUCT APPROVALS SHALL BE SUBMITTED FOR AUDIT | | | AFTER THEY HAVE BEEN REVIEWED AND APPROVED BY THE | | | PRIVATE PROVIDER. ROOFING MATERIALS SHALL NOT BE | | | INSTALLED UNTIL THEY HAVE BEEN APPROVED BY THE PRIVATE | | | PROVIDER AND AUDITED BY THE CITY BUILDING DEPARTMENT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2022-02-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-02-10 |
Time |
16:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-02-10 |
Time |
16:27 |
Sent To |
|
|
| Notes |
| 2022-02-10 16:31:59 | NO PRODUCT APPROVALS FOR ROOFING WERE SUBMITTED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2022-03-15 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2022-03-15 |
Time |
08:04 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2022-03-15 |
Time |
08:04 |
Sent To |
|
|
| Notes |
| 2022-03-14 06:49:50 | MECHANICAL DIGITAL SIGNATURE NOT REQUIRED. |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2022-01-26 |
|
|
Cont ID |
|
| Sent By |
medwards |
Date |
2022-01-26 |
Time |
09:41 |
Rev Time |
0.00 |
| Received By |
medwards |
Date |
2022-01-26 |
Time |
09:41 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2022-03-09 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-03-09 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-03-09 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-03-09 10:07:00 | ZONING APPROVED WITH THE FOLLOWING PROVISOS - MUST BE | | | ADDRESSED PRIOR TO CERTIFICATE OF OCCUPANCY (C.O.): | | | | | | 1.) SEPARATE DRIVEWAY PERMIT SUBMISSION, REVIEW, | | | APPROVAL AND INSTALLATION REQUIRED FOR THE PROPOSED | | | CIRCULAR DRIVE. PER S. 94-312 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDRS), THE CIRCULAR DRIVE | | | CANNOT EXCEED 10 FT. IN WIDTH AT THE PROPERTY LINE FOR | | | EACH ACCESS POINT. | | | | | | 2.) SEPARATE LANDSCAPE PERMIT SUBMISSION, REVIEW, | | | APPROVAL AND INSTALLATION REQUIRED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2022-01-11 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2022-01-11 |
Time |
|
Rev Time |
0.00 |
| Received By |
llouie |
Date |
2022-01-11 |
Time |
|
Sent To |
|
|
| Notes |
| 2022-01-11 16:42:46 | ZONING APPROVED WITH THE FOLLOWING PROVISOS - MUST BE | | | ADDRESSED PRIOR TO CERTIFICATE OF OCCUPANCY (C.O.): | | | | | | 1.) SEPARATE DRIVEWAY PERMIT SUBMISSION, REVIEW, | | | APPROVAL AND INSTALLATION REQUIRED FOR THE PROPOSED | | | CIRCULAR DRIVE. PER S. 94-312 OF THE ZONING AND LAND | | | DEVELOPMENT REGULATIONS (ZLDRS), THE CIRCULAR DRIVE | | | CANNOT EXCEED 10 FT. IN WIDTH AT THE PROPERTY LINE FOR | | | EACH ACCESS POINT. | | | | | | 2.) SEPARATE LANDSCAPE PERMIT SUBMISSION, REVIEW, | | | APPROVAL AND INSTALLATION REQUIRED. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2021-11-04 |
|
|
Cont ID |
|
| Sent By |
llouie |
Date |
2021-11-04 |
Time |
|
Rev Time |
|
| Received By |
llouie |
Date |
2021-11-04 |
Time |
|
Sent To |
|
|
| Notes |
| 2021-11-04 08:23:57 | ** FAILED ** | | | | | | PLEASE ADDRESS THE FOLLOWING COMMENTS. RESPOND TO THE | | | COMMENTS IN WRITING AND/OR ON THE PLANS WHERE | | | APPLICABLE: | | | | | | 1.) WIDTH OF INGRESS/EGRESS AT THE PROPERTY LINE FOR | | | THE CIRCULAR DRIVE CANNOT EXCEED 10 FT. IN WIDTH AT THE | | | PROPERTY LINE AT EACH POINT. [ZLDR S.94-312] | | | | | | 2.) ALTHOUGH A CONDITIONAL APPROVAL FORM HAS BEEN | | | PROVIDED (CURRENTLY PENDING), THE SITE PLAN MUST | | | DEMONSTRATE BY PROVIDING CALCULATIONS THAT THERE IS A | | | MINIMUM OF 1,000 SQ. FT. OR 75% OF THE FRONT YARD WILL | | | BE PROVIDED WITH LANDSCAPING. [ZLDR S.94-442] | | | | | | 3.) SHOW SETBACK DISTANCE FROM THE PROPOSED A/C UNIT | | | COMPRESSOR PAD TO THE PROPERTY LINE. [ZLDR | | | S.94-305(A)94)] | | | | | | | | | NOTES: | | | | | | * ANY REVISIONS MAY RESULT IN ADDITIONAL COMMENTS. | | | | | | * CONTACT LINDA LOUIE @ (561) 822-1458 IF THERE ARE | | | QUESTIONS. | | | | | | * ZONE: SF7 | | | | | | * SIGNED CONDITIONAL APPROVAL FOR LANDSCAPING FORM | | | RECEIVED AND SIGNED BY AV ON 11/3; SENT TO RG/DB ON | | | 11/3 FOR BUILDING OFFICIAL SIGNATURE. | | | | | | * PROVISO: A CERTIFICATE OF OCCUPANCY (C.O.) WILL NOT | | | BE ISSUED UNTIL A LANDSCAPE PERMIT HAS BEEN ISSUED AND | | | INSPECTION OF LANDSCAPE INSTALLATION HAS BEEN APPROVED. | | | | | | * FRONT SCREEN NOTE: SPECIFIC CONDITIONS APPLY ? SEE | | | ZONING PROVISO. | | | |
|
|