| 2021-10-22 07:10:59 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 10/22/21 REVIEW - SEE PREVIOUS LIST FOR REQUIREMENTS. |
| | THREE TEST REPORTS WERE UPLOADED BUT DO NOT REFLECT THE |
| | FIELD CONDITION OF THIS PROJECT. |
| | |
| | FILE NAMED TEST REPORT 1 (IIC) PRODUCT WAS TESTED WITH |
| | "SUSPENDED GYPSUM BOARD CEILING". THIS PROJECT DOES NOT |
| | HAVE A SUSPENDED GYPSUM BOARD CEILING IN THE UNIT |
| | BELOW. |
| | FILE NAMED TEST REPORT 2 (FLAME SPREAD) - TEST REPORT |
| | IS FOR SUPER SIM 90, NOT MAXXIM SIM 90. IT IS POSSIBLE |
| | THIS TEST CAN BE WAIVED DUE TO THE NONCOMBUSTIBLE |
| | NATURE OF THE PROPOSED FLOORING (TILE) |
| | FILE NAMED TEST REPORT 3 (STC) - PRODUCT WAS TESTED |
| | WITH "SUSPENDED GYPSUM BOARD CEILING". |
| | |
| | COMMENTS FROM PREVIOUS LIST: |
| | |
| | 1. MAXXIM SIM 90 FLOORING UNDERLAYMENT IS PROPOSED. |
| | SUBMIT THE THREE TEST REPORTS REQUIRED, STC, IIC, FLAME |
| | SPREAD. PLEASE CONTACT THE MANUFACTURER AS PROFLEX |
| | KNOWS WHICH TEST REPORTS ARE ACCEPTABLE, LISTED BELOW. |
| | |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |