Plan Review Details - Permit 21091061
Plan Review Stops For Permit 21091061
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 08:36 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2022-01-12 Cont ID  
Sent By rmcphers Date 2022-01-12 Time 07:47 Rev Time 0.00
Received By rmcphers Date 2022-01-12 Time 07:47 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-11-08 Cont ID  
Sent By rmcphers Date 2021-11-08 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-11-08 Time 08:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2021-10-13 Time 10:12 Sent To  
Notes
2021-10-14 14:07:00REMODEL MAINTENANCE BUILDING
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH 2017 WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS. FBC 1405.13

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2022-01-27 Cont ID  
Sent By jleahy Date 2022-01-27 Time 10:03 Rev Time 0.00
Received By jleahy Date 2022-01-27 Time 09:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:26 Rev Time 0.00
Received By fgiaquin Date 2021-12-08 Time 11:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-15 Cont ID  
Sent By jleahy Date 2021-10-15 Time 14:34 Rev Time 0.00
Received By jleahy Date 2021-10-15 Time 14:33 Sent To  
Notes
2021-10-15 14:37:48ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NEED TO INSTALL A GROUNDING ELECTRODE SYSTEM AT
 SEPARATE BUILDING. 250.32

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2022-01-18 Cont ID  
Sent By pleduc Date 2022-01-18 Time   Rev Time 0.00
Received By pleduc Date 2022-01-18 Time 13:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2022-01-12 Cont ID  
Sent By pleduc Date 2022-01-12 Time   Rev Time 0.00
Received By pleduc Date 2022-01-12 Time 10:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-09-29 Cont ID  
Sent By pleduc Date 2021-09-29 Time   Rev Time 0.00
Received By pleduc Date 2021-09-29 Time 14:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2022-01-27 Cont ID  
Sent By jleahy Date 2022-01-27 Time 10:03 Rev Time 0.00
Received By jleahy Date 2022-01-14 Time 14:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2022-01-13 Cont ID  
Sent By medwards Date 2022-01-13 Time 07:21 Rev Time 0.00
Received By medwards Date 2022-01-11 Time 15:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 13:48 Rev Time 0.00
Received By medwards Date 2021-12-13 Time 16:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-12-08 Cont ID  
Sent By fgiaquin Date 2021-12-08 Time 11:26 Rev Time 0.00
Received By fgiaquin Date 2021-11-03 Time 15:50 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-15 Cont ID  
Sent By jleahy Date 2021-10-15 Time 14:37 Rev Time 0.00
Received By jleahy Date 2021-09-28 Time 10:39 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2022-01-13 Cont ID  
Sent By medwards Date 2022-01-13 Time 07:21 Rev Time 0.00
Received By medwards Date 2022-01-13 Time 07:21 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 13:36 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 13:36 Sent To  
Notes
2021-12-16 13:42:191) PLEASE PROVIDE THE MECHANICAL EQUIPMENT SIZING
 CALCULATIONS FOR THE PTAC. IF THIS IS A CHANGE OUT LIKE
 FOR LIKE PLEASE FILL OUT THE LIKE FOR LIKE CHANGE FORM
 IN IT'S ENTIREITY. FBC EC C403.2.1
  
 2) WHAT IS THE OCCUPANCY OF THE MAINTENANCE BUILDING?
 HOW DOES THIS PTAC PROVIDE HEAT? FBC M 309.1
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-08 Cont ID  
Sent By medwards Date 2021-11-08 Time 12:20 Rev Time 0.00
Received By medwards Date 2021-11-08 Time 12:20 Sent To  
Notes
2021-11-08 12:22:03PLEASE SEE 1ST CYCLE COMMENTS. THERE ARE ONLY6 DRAWINGS
 IN THIS SUBMITTAL. PLEASE PROVIDE A COMPLETE SET OF
 DRAWINGS.
  
 THERE ARE NO MECHANICAL SHEETS SUBMITTED FOR THIS
 PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-04 Cont ID  
Sent By medwards Date 2021-10-04 Time 15:09 Rev Time 0.00
Received By medwards Date 2021-10-04 Time 15:09 Sent To  
Notes
2021-10-04 15:10:26THERE ARE NO MECHANICAL SHEETS SUBMITTED FOR THIS
 PROJECT.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2022-01-18 Cont ID  
Sent By rmcphers Date 2022-01-18 Time 08:36 Rev Time 0.00
Received By rmcphers Date 2022-01-18 Time 08:36 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2022-01-12 Cont ID  
Sent By rmcphers Date 2022-01-12 Time 07:47 Rev Time 0.00
Received By rmcphers Date 2022-01-12 Time 07:47 Sent To  
Notes
2022-01-12 07:52:04SIGNATURE REVIEW
  
 CORRECTIONS NEEDED -
  
 1) DRAWINGS T1.0, A9.1, E1.03, E2.03, E3.01 DO NOT SHOW
 AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-12-16 Cont ID  
Sent By medwards Date 2021-12-16 Time 13:47 Rev Time 0.00
Received By medwards Date 2021-12-16 Time 13:43 Sent To  
Notes
2021-12-16 13:47:54PLEASE RESPOND TO PREVIOUS REVIEW COMMENTS BELOW:
  
  
 SIGNATURE REVIEW
  
 DRAWINGS T1.0, A9.1, A10.1, E1.03, E2.03, E3.01 DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-08 Cont ID  
Sent By rmcphers Date 2021-11-08 Time 08:55 Rev Time 0.00
Received By rmcphers Date 2021-11-08 Time 08:55 Sent To  
Notes
2021-11-08 08:58:30SIGNATURE REVIEW
  
 DRAWINGS T1.0, A9.1, A10.1, E1.03, E2.03, E3.01 DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-14 Cont ID  
Sent By rmcphers Date 2021-10-14 Time 14:07 Rev Time 0.00
Received By rmcphers Date 2021-10-14 Time 14:07 Sent To  
Notes
2021-10-14 14:08:41SIGNATURE REVIEW
  
 ALL OF THE SIGNED AND SEALED DRAWINGS IN PROJECTDOX DO
 NOT SHOW AS DIGITALLY SIGNED IN ADOBE READER - SIGNED
 AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  