Plan Review Details - Permit 21090965
Plan Review Stops For Permit 21090965
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 3 Status P Date 2021-10-26 Cont ID  
Sent By lmarchan Date 2021-10-26 Time 12:46 Rev Time 0.00
Received By lmarchan Date 2021-10-26 Time 12:45 Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status F Date 2021-10-26 Cont ID  
Sent By jwitmer Date 2021-10-26 Time 08:10 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-26 08:10:02TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 14:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-06 14:22:07TO THE BUILDING CONTRACTOR:
 PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2021-10-26 Cont ID  
Sent By jwitmer Date 2021-10-26 Time 08:10 Rev Time 0.00
Received By jwitmer Date 2021-10-26 Time 07:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 14:22 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-06 14:22:47WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090965
 ADD: 651 OKKEECHOBEE BLVD. # 207
 CONT: O&D TOATAL HOME REPAIR CORP
 TEL: 561-969-3121
 E-MAIL: ODTOTALHOMEREPAIRCORP@GMAIL
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 06TH/2021
 ACTION: DENIED
  
 1) SUBMITTED SPECS FOR SAM # 90 SOUND CONTROL MEMBRANE.
 PLEASE NOTE WE DO NOT EXCEPT MANUFACTURER?S SPEC
 SHEETS. TO GET RESULTS OF IIC= 70 AND STC 67 THE FLOOR
 CEILING ASSEMBLY MUST BE A FLOOR TRUSS ASSEMBLY AND
 FULL OF INSULATION. NOT A 6 INCH CONCRETE SLAB.
  
 FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020) FOR TILE,
 STONE, MARBLE, VINYL AND WOOD FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 1A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 1B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 1C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-02 Cont ID  
Sent By jleahy Date 2021-10-02 Time 09:57 Rev Time 0.00
Received By jleahy Date 2021-10-02 Time 09:50 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-10-20 Cont ID  
Sent By pleduc Date 2021-10-20 Time   Rev Time 0.00
Received By pleduc Date 2021-10-20 Time 14:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By pleduc Date 2021-09-23 Time   Rev Time 0.00
Received By pleduc Date 2021-09-23 Time 09:54 Sent To  
Notes
2021-09-23 10:15:50THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF THE SPEC SHEET FOR THE
 FLOOR UNDERLAYMENT, BUT NO SPEC SHEET FOR THE ACTUAL
 PROPOSED FLOORING TILE.
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED
 AROUND THE WORLD AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 TILE TYPE AND/OR PRODUCT SPEC SHEETS OF THE PROPOSED
 FINISHED FLOORING INDICATING THE FIRE BEHAVIOR RATING.
  
  
 2) THE FLOOR PLAN SUBMITTED INDICATES THE LOCATION OF
 THE BATHROOM & KITCHEN THAT APPEAR TO BE LOCATED ALONG
 A
 FIRE RATED TENANT AND/OR CORRIDOR SEPARATION WALL
 REQUIRING MAINTENANCE/REPAIR OF THE FIRE RATED WALL
 SHOULD THE DEMO DAMAGE THAT WALL.
  
 PLEASE REVIEW, ENSURE WALL FIRE RATING IS NOT
 COMPROMISED AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE FLOOR PLAN.
  
  
  
 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT ON THE FLOOR PLAN.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date   Cont ID  
Sent By   Date 2021-10-27 Time   Rev Time 0.00
Received By cdecoeur Date 2021-10-19 Time 14:54 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 14:23 Rev Time 0.00
Received By jwitmer Date 2021-09-22 Time 10:35 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-10-27 Cont ID  
Sent By ccole Date 2021-10-27 Time 07:59 Rev Time 0.00
Received By ccole Date 2021-10-27 Time 07:37 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-29 Cont ID  
Sent By ccole Date 2021-09-29 Time 16:51 Rev Time 0.00
Received By ccole Date 2021-09-29 Time 15:33 Sent To  
Notes
2021-09-29 16:22:321ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21090965
 9/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FAIR HOUSING ACT COMPLIANCE: THE CONDOMINIUMS AT THE
 TOWER CONDOMINIUM- 651 OKEECHOBEE BLVD WERE DESIGNED
 AND CONSTRUCTED IN COMPLIANCE THE FAIR HOUSING ACT
 DESIGN MANUAL, THEREFORE THE PROPOSED ALTERATIONS TO
 THE KITCHEN AND BATHROOM IN UNIT 207 SHALL ALSO BE IN
 COMPLIANCE. PLEASE PROVIDE CODE DATA INFORMATION ON
 SHEET 1 THAT INCLUDES COMPLIANCE WITH THE FAIR HOUSING
 ACT DESIGN MANUAL AND THE CURRENT FLORIDA BUILDING
 CODES- 2020 7TH EDITION. THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES ARE INCLUDED IN THE FLORIDA ACCESSIBILITY
 CODE- 2020 7TH EDITION AND THE FAIR HOUSING DESIGN ACT
 MANUAL.
  
 2) SHEET 1: THE ARCHITECT SHALL SPECIFY WHICH USABLE
 BATHROOM SPECIFICATION TYPE A OR B WAS CHOSEN AS THE
 ORIGINAL DESIGN. PLEASE REFER TO PAGES 7.34- 7.39 OF
 THE FAIR HOUSING DESIGN ACT MANUAL FOR EXPLANATORY
 INFORMATION ON SPECIFICATION A & B. AN ENLARGED
 DIMENSIONED BATHROOM DRAWING WITH ELEVATION DETAILS
 WILL BE REQUIRED IN ORDER TO VERIFY COMPLIANCE FOR THE
 NEW FIXTURE INSTALLATIONS- SECTION 107.2.1 WPB.
  
 2) SHEET 1: PLEASE REFER TO PAGES 7.47- 7.52 AND SHOW
 THE LAVATORY CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS
 AND KNEE AND TOE CLEARANCES. REFER TO PAGES 7.40- 7.46
 AND PROVIDE THE WATER CLOSET CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSION.
  
 3) SHEET 1: PLEASE REFER TO PAGES 7.56- 7.59 OF THE
 MANUAL AND PROVIDE THE SHOWER INTERIOR CLEAR FLOOR
 SPACE DIAGRAM WITH DIMENSIONS. PLEASE NOTE THE DRAWING
 IS NOT IN COMPLIANCE BECAUSE NO FIXTURES ARE ALLOWED TO
 OVERLAP THE CLEAR FLOOR SPACE REQUIRED FOR THE SHOWER-
 SEE PAGE 7.57. REFER TO PAGE 7.58 AND INDICATE THE
 SHOWER DIMENSIONS. PLEASE NOTE THAT THE MINIMUM
 REQUIRED DIMENSIONS ARE 36-INCHES X 36-INCHES.
  
 4) SHEET 1: BASED ON EITHER SPECIFICATION A OR B PLEASE
 REFER TO PAGES 6.12- 6.13 AND PROVIDE AN ELEVATION
 DETAIL SHOWING THE SHOWER CONTROLS LOCATION, AND THE
 GRAB BAR AND SEAT REINFORCEMENT DETAILS. SHOW THE
 LENGTHS, WIDTHS AND HEIGHTS AND THE TYPE OF
 REINFORCEMENT MATERIAL TO BE USED. SEE SECTION 603.1
 FOR ALLOWABLE MATERIALS IN NON-COMBUSTIBLE BUILDINGS.
  
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE
 GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-10-19 Cont ID  
Sent By mpeterso Date 2021-10-19 Time 15:04 Rev Time 0.00
Received By mpeterso Date   Time   Sent To  
Notes
2021-10-19 15:05:41REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-22 Cont ID  
Sent By ccole Date 2021-09-22 Time 11:43 Rev Time 0.00
Received By ccole Date 2021-09-22 Time 11:43 Sent To  
Notes
2021-09-22 11:44:59REVIEW OF SIGNATURE AND SEAL ON PAPER PLANS APPROVED
 AND PLANS ROUTED TO STORAGE- CLC.