| 2021-11-02 10:08:40 | REROOF SECOND BUILDING REVIEW COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #21090963 |
| | |
| | NOTE: SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK |
| | SHALL COMPLY WITH THE MATERIALS AND METHODS |
| | REQUIREMENTS IN THE FLORIDA BUILDING CODE. |
| | |
| | ORIGINAL COMMENT: |
| | 1- TPO ROOF SYSTEMS NOA 18-0109.09 SUBMITTED: CLEARLY |
| | MARK WHICH APPROVED ASSEMBLY IS GOING TO BE INSTALLED |
| | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. |
| | 1609.1 FBC-BUILDING. NOTE: IF THE SELECTED ASSEMBLY |
| | DOESN'T MEET THE DESIGN PRESSURES FOR ALL ROOF ZONES, |
| | THEN SIGNED AND SEALED RAS 117 CALCULATIONS ARE |
| | REQUIRED. SEE GENERAL LIMITATION #7 ON LAST PAGE OF |
| | NOA. ASSEMBLIES WITH GENERAL LIMITATION #9 CAN NOT BE |
| | USED IF THEY DON'T MEET THE DESIGN PRESSURES FOR ALL |
| | ROOF ZONES. |
| | |
| | RESPONSE: |
| | SELECTED ASSEMBLY ON PAGE 5 OF 7 OF NOA 18-0109.09 CAN |
| | NOT BE USED. THE MAXIMUM DESIGN PRESSURE FOR THIS |
| | ASSEMBLY IS -45PSF AND IS LIMITED BY GENERAL LIMITATION |
| | #9. THIS ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES FOR |
| | ANY OF THE ROOF ZONE OF THIS BUILDING. |
| | NEED TO SPECIFY ANY OTHER ASSEMBLY WITH GENERAL |
| | LIMITATION #7 AND PROVIDE SIGNED AND SEALED RAS 117 |
| | CALCULATIONS. |
| | |
| | ORIGINAL COMMENT: |
| | 2- NEED TO SPECIFY THE MEAN ROOF HEIGHT OF THE BUILDING |
| | AS REQUIRED BY THE CITY POLICY FOR ALL ROOFING PERMITS. |
| | SEC. 107.2.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | ORIGINAL COMMENT: |
| | 3- TPO ROOF SYSTEMS NOA 18-0109.09 SUBMITTED IS FOR |
| | WOOD DECKS. ROOFING FASTENER NOA 18-0308.04 IS NOT FOR |
| | WOOD DECKS. REVISE AS REQUIRED. IT IS NOT CLEAR WHAT |
| | MATERIAL IS THE ROOF DECK. SEC. 107.2.1 CITY |
| | AMENDMENTS. |
| | NOTE: VERIFY ROOF DECK TYPE AND PROVIDE CORRECT PRODUCT |
| | APPROVAL TO AVOID CONFLICTS/DELAYS. CHECK LIMITATIONS |
| | ON LAST PAGE OF NOA. ADDITIONAL INFORMATION MAY BE |
| | REQUIRED. |
| | |
| | RESPONSE: |
| | THERE WAS NO RESPONSE TO THIS ITEM. NO SURE OF ACTUAL |
| | ROOF DECK. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |