Plan Review Details - Permit 21090944
Plan Review Stops For Permit 21090944
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2021-12-08 Cont ID  
Sent By cpuell Date 2021-12-08 Time 09:05 Rev Time 0.00
Received By cpuell Date 2021-12-08 Time 09:05 Sent To  
Notes
2021-12-08 09:05:57SUITE CREATED, ADDRESS APPROVED

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2021-12-05 Cont ID  
Sent By cpuell Date 2021-12-05 Time 13:01 Rev Time 0.00
Received By cpuell Date 2021-12-08 Time 09:05 Sent To  
Notes
2021-12-05 13:01:58SUITE 200 IS NOT AN APPROVED SUITE NUMBER, PLEASE
 PROVIDE A FLOOR PLAN SHOWING EVERY SUITE ON THAT FLOOR.
 PLEASE EMAIL TO [email protected] FOR FURTHER QUESTIONS
 YOU CAN ALSO CALL 561-805-6659

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 11:51 Rev Time 0.00
Received By rmcphers Date 2021-11-10 Time 14:14 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-05 Cont ID  
Sent By rmcphers Date 2021-11-05 Time 08:40 Rev Time 0.00
Received By rmcphers Date 2021-11-05 Time 08:40 Sent To  
Notes
2021-11-05 08:42:24OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING A3.02 HAS NOT BEEN REVISED PER THE COMMENT
 RESPONSE LETTER - PLEASE PROVIDE THE RAISED FLOOR
 DETAILS - MANUFACTURE SPECS. FBC 107.2.1
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-25 Cont ID  
Sent By rmcphers Date 2021-10-25 Time 11:54 Rev Time 0.00
Received By rmcphers Date 2021-10-25 Time 10:08 Sent To  
Notes
2021-10-25 11:53:51OFFICE BUILDOUT
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
 1) PLEASE SHOW THE WALL FINISH AROUND THE MOP SINK TO
 COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 2) WALLS SHOWN IN DETAILS 4 AND 5 ON DRAWING A1.31 -
 SHOWS PAINT ON THE DRYWALL (DRYWALL IS NOT CONSIDERED A
 HARD SURFACE) FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR,
  
 3) PLEASE PROVIDE THE RAISED FLOOR DETAILS -
 MANUFACTURE SPECS. FBC 107.2.1
  
 4) PLEASE SHOW THE TOILET PAPER DISPENSER LOCATION FROM
 THE FRONT OF THE TOILET PER FBC 604.7 DISPENSERS.
 TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4 AND
 SHALL BE 7 INCHES (180 MM) MINIMUM AND 9 INCHES (230
 MM) MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO
 THE CENTERLINE OF THE DISPENSER.
  
 5) THE 18 INCH VERTICAL GRAB BAR IS NOT REQUIRED PER
 FBC - PLEASE SHOW THE REQUIRED 12 INCHES CLEARANCE
 BETWEEN THE TOP OF THE GRAB BAR AND PROTRUDING OBJECTS
 ABOVE THE HORIZONTAL GRAB BAR - FBC 609.3 THE SPACE
 BETWEEN THE GRAB BAR AND PROJECTING OBJECTS ABOVE SHALL
 BE 12 INCHES (305 MM) MINIMUM.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2021-11-24 Cont ID  
Sent By jleahy Date 2021-11-24 Time 12:44 Rev Time 0.00
Received By jleahy Date 2021-11-24 Time 12:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 08:51 Rev Time 0.00
Received By jleahy Date 2021-11-05 Time 08:39 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By jleahy Date 2021-10-22 Time 12:48 Rev Time 0.00
Received By jleahy Date 2021-10-22 Time 12:16 Sent To  
Notes
2021-10-22 12:50:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 RISER DIAGRAM FOR THIS SPACE PLEASE CLOUD IT OR
 SEPARATE IT FROM BUILDING RISER SO IT IS EASIER TO
 FIND.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-15 Cont ID  
Sent By pleduc Date 2021-11-15 Time   Rev Time 0.00
Received By pleduc Date 2021-11-15 Time 09:02 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2021-10-07 Cont ID  
Sent By pleduc Date 2021-10-07 Time   Rev Time 0.00
Received By pleduc Date 2021-10-06 Time 13:42 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date   Cont ID  
Sent By   Date 2021-12-08 Time   Rev Time 0.00
Received By aoliver Date 2021-12-01 Time 07:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date   Cont ID  
Sent By   Date 2021-11-30 Time   Rev Time 0.00
Received By aoliver Date 2021-11-19 Time 09:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 12:55 Rev Time 0.00
Received By rmcphers Date 2021-11-09 Time 07:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-05 Cont ID  
Sent By jleahy Date 2021-11-05 Time 10:48 Rev Time 0.00
Received By jleahy Date 2021-10-28 Time 09:04 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 12:28 Rev Time 0.00
Received By mpeterso Date 2021-10-25 Time 12:28 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2021-12-03 Cont ID  
Sent By medwards Date 2021-12-03 Time 07:59 Rev Time 0.00
Received By medwards Date 2021-12-03 Time 07:59 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2021-11-22 Cont ID  
Sent By medwards Date 2021-11-22 Time 15:24 Rev Time 0.00
Received By medwards Date 2021-11-22 Time 14:59 Sent To  
Notes
2021-11-22 15:26:38THE VERSIONS OF SHEETS M202 AND M302 ARE NOT THE LATEST
 VERSIONS. PLEASE SUBMIT THE MOST UPDATED VERSIONS FOR
 REVIEW AND SIGNATURES.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2021-11-15 Cont ID  
Sent By medwards Date 2021-11-15 Time 06:32 Rev Time 0.00
Received By medwards Date 2021-11-15 Time 06:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2021-11-03 Cont ID  
Sent By medwards Date 2021-11-03 Time 16:16 Rev Time 0.00
Received By medwards Date 2021-11-03 Time 16:16 Sent To  
Notes
2021-11-03 16:16:412ND REVIEW FBC-2020 MECHANICAL
 PERMIT-21090944
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 THE 2020 FBC M 403.3.1.1 AND TABLE 403.3.1.1 YOU MUST
 USE THE TABLE FOR THE OCCUPANT COUNT IN EACH SPACE AND
 NOT THE ARCHITECTURAL COUNT. PLEASE ALSO SEPARATE THE
 CORRIDORS FROM THE OTHER SPACES.
  
 2) PLEASE SHOW THE TERMINATION LOCATION OF THE
 CONDENSATE DRAINAGE. FBC M 307
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2021-10-15 Cont ID  
Sent By medwards Date 2021-10-15 Time 06:16 Rev Time 0.00
Received By medwards Date 2021-10-14 Time 16:24 Sent To  
Notes
2021-10-15 06:16:361ST REVIEW FBC-2020 MECHANICAL
 PERMIT-21090944
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE
 FBC M- FLORIDA MECHANICAL CODE
 FBC EC- FLORIDA ENERGY CONSERVATION
 FBC FG- FLORIDA FUEL GAS
 FBC EX- FLORIDA EXISTING BUILDING CODE
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE SUITE NUMBER ON THE DRAWINGS FOR
 THIS TENANT SPACE. FBC 107.2.1
  
 2) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS FOR EACH
 USE OF SPACE IN THIS TENANT SPACE. FBC M 403.3.1.1 &
 TABLE 403.3.1.1
  
 3) SHEET M202: PLEASE EXPLAIN THE EXISTING 20 X 16 OA
 DUCT, IS THIS GOING UP TO THE ROOF TO A UNIT THAT IS
 CONDITIONING THE AIR? FBC 107.2.1
  
 4) PLEASE EXPLAIN AND SHOW ON THE DRAWING HOW YOU ARE
 SUPPLYING THE OUTDOOR AIR TO EACH HEAT PUMP. FBC
 107.2.1
  
 5) PLEASE EXPLAIN THE 6 INCH DUCT COMING FROM THE
 BATHROOM AND DUMPING AIR INTO THE CORRIDORS. FBC M
 601.5-7
  
 6) PLEASE SHOW THE CFM?S THAT HEAT PUMP 4 IS SUPPLYING
 TO THE OFFICE SUPPLY GRILLES. FBC 107.2.1
  
 7) SHEET M202: PLEASE EXPLAIN THE EF-1 SHOWN IN THE
 BATHROOM, THERE IS NOTHING SHOWN BEING DUCTED TO THIS
 EF-1.
  
 8) SHEET M302: THE CONDENSATION FROM THE MECHANICAL
 SYSTEMS CANNOT TERMINATE INTO THE SANITARY SEWER
 SYSTEM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  

Review Stop P PLUMBING
Rev No 5 Status P Date 2021-12-08 Cont ID  
Sent By ccole Date 2021-12-08 Time 08:42 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:31 Sent To  
Notes
2021-12-08 08:43:22PASS ENTERED INTO SYSTEM FOR PLUMBING PLAN REVIEWER
 JERALD SMITH.

Review Stop P PLUMBING
Rev No 4 Status P Date 2021-11-30 Cont ID  
Sent By ccole Date 2021-11-30 Time 15:03 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:32 Sent To  
Notes
2021-12-08 08:43:37PASS ENTERED INTO SYSTEM FOR PLUMBING PLAN REVIEWER
 JERALD SMITH.

Review Stop P PLUMBING
Rev No 3 Status P Date 2021-11-12 Cont ID  
Sent By cthroop Date 2021-11-12 Time 09:29 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:31 Sent To  
Notes
2021-11-12 09:29:4521090944 360 S ROSEMARY AVE #200
  
 PLUMBING COMMENTS: APPROVED
  
 ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL
  
 BY REVIEWING THE PLANS / SPECIFICATIONS FOR CODE
 COMPLIANCE DOES NOT RELIEVE THE OWNER, DESIGN
 PROFESSIONAL, CONTRACTORS OR THEIR REPRESENTATIVES FROM
 THE RESPONSIBILITY TO COMPLY WITH ALL LOCAL, STATE AND
 NATIONAL CODES AND STANDARDS IN EFFECT AT THE TIME OF
 PERMIT ISSUANCE. OUR REVIEW IS NOT A CHECK OF EVERY
 ITEM AND DOES NOT PREVENT THIS DEPARTMENT FROM
 REQUIRING CORRECTIONS DURING CONSTRUCTION. ANY CHANGES
 / ALTERATIONS TO APPROVED PLANS SHALL BE APPROVED TO
 AVOID VOIDING OF THE PERMIT.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090944 360 S ROSEMARY AVE #200

Review Stop P PLUMBING
Rev No 2 Status F Date 2021-11-04 Cont ID  
Sent By cthroop Date 2021-11-04 Time 16:25 Rev Time 0.00
Received By jesmith Date 2022-02-01 Time 13:31 Sent To  
Notes
2021-11-04 16:26:30CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090944 360 S ROSEMARY AVE #200
  
 2ND REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.NEW COMMENT: P-601/DETAIL 7; APPLIANCE BOX TO
 REFRIGERATOR SHALL BE TAG IB2 W/WATER HAMMER ARRESTOR,
 NOT IB1. FBC PL 604.9 WATER HAMMER
  
 2.REGARDING THE WATER HAMMER ARRESTORS, PER WPB FBC
 107.2.1, PLEASE PROVIDE A PDI SIZE
 SCHEDULE/SPECIFICATION (SECOND REQUEST) AND TAG THE
 WATER HAMMER ARRESTORS SHOWN ON THE WATER RISER DIAGRAM
 THE APPROPRIATE SIZE. THIS IS NOT REQUIRED FOR THE IB2
 GUY GRAY APPLIANCE BOXES.
  
 3.P-601/DETAIL 7; PER WPB FBC 107.2.1, COORDINATE
 P-601/DETAIL 7 WATER TO REFRIGERATOR WITH P-202
 BACKFLOW PREVENTER SCHEDULE AND P-202/NOTE 12. DETAIL
 AS DRAWN WOULD REQUIRE A LF7R DUAL CHECK VALVE, NOT A
 LF289 VACUUM BREAKER.
  
 4.P-202 NOTES 10, 11 AND 12 CALL FOR STAINLESS STEEL
 TUBING CONNECTIONS. PER FBC PL TABLE 604.5, THIS
 PRODUCT IS NOT PERMITTED IN IN WATER DISTRIBUTION;
 STAINLESS STEEL PIPE CONFORMING TO ASTM A312 OR ASTM
 778 IS ALLOWED BUT THIS IS A MINIMUM SCHEDULE
 10/SCHEDULE 40 FOR WELDED OR THREADED APPLICATIONS. FBC
 PL 605.6 ALLOWS ACCESSIBE FLEXIBLE CONNECTORS
 CONFORMING TO ASME A112.18.6/CSA B125.6 OR COPPER OR
 COPPER-ALLOY TUBING (TYPE K, WK, L, WL, M OR WM)
 CONFORMING TO ASTM B75; ASTM B88; ASTM B251; ASTM B447
 PER FBC PL TABLE 604.5/ FBC PL TABLE 604.5.
  
 5.P-202 AND P-601/DETAIL 3; DETAIL SHOWS WATER HEATER
 ABOVE MOP BASIN, P-202 SHOWS AT OPPOSITE END OF THE
 ROOM. PER WPB FBC 107.2.1, CLARIFY.
  
 6.P-202 AND P-601/DETAIL 3; DETAIL SHOWS RELIEF LINE
 AND PAN DRAIN EACH INDEPENDENTLY DISCHARGING TO AN
 APPROVED LOCATION. PER WPB FBC 107.2.1, PROVIDE ACTUAL
 TERMINATION FOR THE DRAINS ON THE DETAIL. THE FOLLOWING
 ARE ACCEPTABLE.
 ?A) FBC PL 504.6(5)(10); (5) DISCHARGE RELIEF LINE TO
 THE FLOOR (NOT RECOMMENDED FOR THIS INSTALLATION), TO
 THE PAN SERVING THE WATER HEATER OR STORAGE TANK, TO A
 WASTE RECEPTOR OR TO THE OUTDOORS; (10)TERMINATE NOT
 MORE THAN 6 INCHES (152 MM) ABOVE AND NOT LESS THAN TWO
 TIMES THE DISCHARGE PIPE DIAMETER ABOVE THE FLOOR OR
 FLOOD LEVEL RIM OF THE WASTE RECEPTOR.
 ?B) FBC PL 504.7.2 THE PAN DRAIN SHALL EXTEND FULL SIZE
 AND TERMINATE OVER A SUITABLY LOCATED INDIRECT WASTE
 RECEPTOR OR FLOOR DRAIN OR EXTEND TO THE EXTERIOR OF
 THE BUILDING AND TERMINATE NOT LESS THAN 6 INCHES (152
 MM) AND NOT MORE THAN 24 INCHES (610 MM) ABOVE THE
 ADJACENT GROUND SURFACE.
 ?C) PLEASE NOTE THAT PER FBC PL CHAPTER 2, DEFINITIONS,
 A WASTE RECEPTOR IS DEFINED AS A FLOOR SINK, STANDPIPE,
 HUB DRAIN OR FLOOR DRAIN THAT RECEIVES THE DISCHARGE OF
 ONE OR MORE INDIRECT WASTE PIPES. THE MOP
 RECEPTOR/BASIN DOES NOT QUALIFY AS A WASTE RECEPTOR.
 ?D) PER WPB FBC PROVIDE REQUIRED TRAPPED AND VENTED
 WASTE RECEPTOR ON P-202 PLUMBING PLANS RISER AND PLAN
 VIEW
  
  
 7.THE INDIVIDUAL VENTS FOR THE FLOOR SINK (SECOND
 REQUEST) AND THE TWO (2) ADDED FLOOR DRAINS ARE NOT
 COMPLIANT. VENTS SHALL CONNECT ABOVE THE CENTERLINE OF
 THE DRAIN OF THE HORIZONTAL DRAIN AND SHALL RISE
 VERTICALLY TO A POINT NOT LESS THAN 6 INCHES ABOVE THE
 FLOOD LEVEL RIM OF THE HIGHEST TRAP OR TRAPPED FIXTURE
 BEING VENTED PER FBC PL 905.3 AND 905.4.
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090944 360 S ROSEMARY AVE #200
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-10-20 Cont ID  
Sent By pvalenti Date 2021-10-20 Time 07:17 Rev Time 0.00
Received By pvalenti Date 2021-10-19 Time 07:57 Sent To  
Notes
2021-10-20 07:17:51CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 21090944 360 S ROSEMARY AVE #200
  
 1ST REVIEW
  
 PLUMBING COMMENTS: DENIED
  
 A REVIEW OF MINIMUM PLUMBING FIXTURE REQUIREMENTS AS
 REQUIRED BY FBC ACC IS PART OF THE PLUMBING REVIEW
 PROCESS BUT IS TYPICALLY ADDRESSED ON THE ARCHITECTURAL
 PLANS. ANY COMMENTS CONCERNING THESE REQUIREMENTS MUST
 BE SATISFACTORILY ADDRESSED PRIOR TO A PLUMBING REVIEW
 APPROVAL.
  
 1.RE: A0.02
 PER WPB FBC 107.2.1, TO SHOW COMPLIANCE WITH FBC ACC
 CHAPTERS 2, 3 AND 6 PROVIDE PLAN AND ELEVATION DETAILS
 FOR NEW TOILET ROOM INDICATING THE FOLLOWING:
 ...A) PER FBC PL 604.8.1.1WHEELCHAIR ACCESSIBLE
 COMPARTMENTS SHALL BE 60 INCHES WIDE MINIMUM MEASURED
 PERPENDICULAR TO THE SIDE WALL, AND 56 INCHES DEEP
 MINIMUM FOR WALL HUNG WATER CLOSETS AND 59 INCHES DEEP
 MINIMUM FOR FLOOR MOUNTED WATER CLOSETS MEASURED
 PERPENDICULAR TO THE REAR WALL.
 ......1A) SPECIFIED WATER CLOSETS ARE FLOOR MOUNTED.
 PER WPB FBC 107.2, SHOW COMPLIANCE IN DETAIL 2/A0.02
 ...B) THE REAR WALL GRAB BAR SHALL BE 36 INCHES LONG
 MINIMUM AND EXTEND FROM THE CENTERLINE OF THE WATER
 CLOSET 12 INCHES MINIMUM ON ONE SIDE AND 24 INCHES
 MINIMUM ON THE OTHER SIDE PER FBC ACC 604.5.2
 ......1B)PER WPB FBC 107.2, REMOVE 6 INCH DIMENSION
 BETWEEN SIDE WALL AND GRAB BAR IN DETAIL 2/A0.02
 ...C) TOILET PAPER DISPENSERS SHALL COMPLY WITH 309.4
 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES MAXIMUM IN
 FRONT OF THE WATER CLOSET MEASURED TO THE CENTERLINE OF
 THE DISPENSER PER FBC ACC 604.8.
 ...D) THE SEAT HEIGHT OF A WATER CLOSET ABOVE THE
 FINISH FLOOR SHALL BE 17 INCHES (430 MM) MINIMUM AND 19
 INCHES (485 MM) MAXIMUM MEASURED TO THE TOP OF THE
 SEAT, NOT TO THE RIM. SEATS SHALL NOT BE SPRUNG TO
 RETURN TO A LIFTED POSITION PER FBC ACC 604.4.
 ...E) PER FBC ACC 604.8.1.2 AND 604.8.1.7, THE DOOR TO
 THE ACCESSIBLE TOILET RM/COMPARTMENT SHALL BE LOCATED
 IN THE FRONT PARTITION OR IN THE SIDE WALL OR PARTITION
 FARTHEST FROM THE WATER CLOSET, DIAGONAL TO THE WATER
 CLOSET.
 ......1E) SEE MENS ADA RM 209; PER WPB FBC 107.2, SHOW
 COMPLIANCE WITH FBC ACC 604.8.1.2 AND 604.8.1.7
 ...F) SHOW TOE AND KNEE CLEARANCE FOR ACCESSIBLE
 LAVATORIES AS REQUIRED BY FBC ACC 306.2 AND 306.3
 ...G) KNEE AND TOE CLEARANCE COMPLYING WITH 306 SHALL
 BE PROVIDED FOR THE DRINKING FOUNTAIN PER FBC ACC
 602.2.
 ...H) THE SPOUT FOR THE DRINKING FOUNTAIN SHALL BE
 LOCATED 15 INCHES (380 MM) MINIMUM FROM THE VERTICAL
 SUPPORT AND 5 INCHES (125 MM) MAXIMUM FROM THE FRONT
 EDGE OF THE UNIT, INCLUDING BUMPERS PER FBC ACC 602.5.
  
 2.PER WPB FBC 107.2.1, ADD NOTE TO P9.01, SECTION 2.01
 DOMESTIC WATER ?ALL FIXTURES AND COMPONENTS IN THE
 DOMESTIC WATER SYSTEM SHALL BE LEAD FREE?
  
 3.PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL WITH
 A NOTE STATING, "HORIZONTAL PIPE SHALL BE SUPPORTED IN
 ACCORDANCE WITH FBC PL TABLE 308.5."
  
 4.PROVIDE DETAIL FOR STRUCTURAL SUPPORT OF SUSPENDED
 WATER HEATER PER WPB FBC 107.2.1. DETAIL SHALL INCLUDE
 BUT IS NOT LIMITED TO, ROD SIZE, SIZE AND TYPE OF
 ANCHORS, BEAM CLAMPS, MATERIAL AND THICKNESS OF
 PLATFORM, PLATFORM DIMENSIONS AND HEIGHT ABOVE THE
 FLOOR TO BOTTOM OF THE ASSEMBLY.
  
 5.PER WPB FBC107.2.1, PROVIDE RATED WALL/FLOOR DETAILS
 FOR PIPE PENETRATIONS COMPLYING WITH FBC CHPT. 7
  
 6.SEE M302 SHOWING CONDENSATE TO THE MOP RECEPTACLE.
 PER WPB CODE OF ORDINANCE CHAPTER 90, ARTICLE 3,
 SECTION 90-12B5, A/C CONDENSATE (INTERPRET THIS AS ANY
 CONDENSATION FROM EVAPORATOR COILS) SHALL NOT DISCHARGE
 TO THE CITY UTILITIES SANITARY SEWAGE INFRASTRUCTURE
 WITHOUT PERMISSION FROM THE UTILITIES DEPARTMENT.
 MOVING FORWARD, DISCHARGE THE CONDENSATE TO AN EXTERIOR
 DRYWELL OR TO THE STORM SYSTEM; PER WPB FBC 107.2.1 AND
 FBC PL SECTION 314, PROVIDE ROUTING AND CONNECTION
 DETAIL AT THE POINT OF DISCHARGE.
  
 7.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TRAP PRIMER
 FROM WATER SOURCE TO THE FLOOR SINK.
  
 8.PER WPB FBC 107.2.1, PROVIDE DETAIL FOR TEMPERED
 WATER TO LAVATORIES SHOWING COMPLIANCE WITH FBC PL
 419.5
  
 9.PER WPB FBC 107.2.1, PROVIDE A SCHEDULE AND SHOW
 LOCATIONS OF EQUIPMENT REQUIRING PLUMBING CONNECTIONS
 INCLUDING, BUT NOT LIMITED TO WATER FILTERS, ICE
 MACHINES/MAKERS, BEVERAGE MACHINES AND COFFEE MAKER.
 SPECIFY ON THE SCHEDULE THE APPROPRIATE METHOD OF
 BACKFLOW PREVENTION AND BACKFLOW PREVENTION DEVICE,
 COMPLYING WITH FBC PL SECTION 608.
  
 10.PER WPB FBC 107.2.1, PROVIDE DETAIL OF EACH PIECE OF
 EQUIPMENT REQUIRING PLUMBING CONNECTIONS INCLUDING, BUT
 NOT LIMITED TO WATER FILTERS, ICE MACHINES/MAKERS,
 BEVERAGE MACHINES AND COFFEE MAKER. SHOW COMPLIANCE
 WITH FBC PL SECTION 608
  
 11.THE INDIVIDUAL VENTS FOR THE WATER CLOSETS, FLOOR
 SINK AND THE MOP RECEPTACLE ARE NOT COMPLIANT. VENTS
 SHALL CONNECT ABOVE THE CENTERLINE OF THE DRAIN OF THE
 HORIZONTAL DRAIN AND SHALL RISE VERTICALLY TO A POINT
 NOT LESS THAN 6 INCHES ABOVE THE FLOOD LEVEL RIM OF THE
 HIGHEST TRAP OR TRAPPED FIXTURE BEING VENTED PER FBC PL
 905.3 AND 905.4.
  
 12.PER FBC PL 604.9, PROVIDE WATER HAMMER ARRESTORS FOR
 QUICK CLOSING VALVES IN THE DOMESTIC WATER SYSTEM.
 INDICATE THE REQUIRED LOCATIONS ON THE PLANS. WATER
 HAMMER ARRESTORS SHALL CONFORM TO ASSE 1010.
  
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
 PLEASE NOTE THAT I TYPICALLY WORK ON TUESDAYS AND
 THURSDAYS
  
 21090944 360 S ROSEMARY AVE #200
  

Review Stop PRIVATEPRV PRIVATE PROVIDER DOCUMENTS
Rev No 1 Status P Date 2021-11-09 Cont ID  
Sent By rgathrig Date 2021-11-09 Time 13:53 Rev Time 0.00
Received By rgathrig Date 2021-11-09 Time 13:53 Sent To  
Notes
2021-11-09 13:55:38PRIVATE PROVIDER INSPECTIONS ONLY APPROVED
 ECS FLORIDA DAVID BREACE PE
  
 RICHARD GATHRIGHT
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 5 Status P Date 2021-12-08 Cont ID  
Sent By ccole Date 2021-12-08 Time 08:41 Rev Time 0.00
Received By ccole Date 2021-12-08 Time 08:19 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status F Date 2021-11-29 Cont ID  
Sent By rmcphers Date 2021-11-29 Time 12:47 Rev Time 0.00
Received By rmcphers Date 2021-11-29 Time 12:46 Sent To  
Notes
2021-11-29 12:47:41SIGNATURE REVIEW
  
 DRAWINGS A0.02, A1.31 DO NOT SHOW AS DIGITALLY SIGNED
 IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2021-11-17 Cont ID  
Sent By rmcphers Date 2021-11-17 Time 12:55 Rev Time 0.00
Received By rmcphers Date 2021-11-17 Time 12:53 Sent To  
Notes
2021-11-17 12:55:09SIGNATURE REVIEW
  
 DRAWINGS A0.02, A1.31,M-202, M-302, M-701, M-801,
 P-701, P-901, E-402, E-501, E-602 DO NOT SHOW AS
 DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2021-11-05 Cont ID  
Sent By rmcphers Date 2021-11-05 Time 08:42 Rev Time 0.00
Received By rmcphers Date 2021-11-05 Time 08:42 Sent To  
Notes
2021-11-05 08:47:53SIGNATURE REVIEW
  
 DRAWINGS A0.02, A1.31,M-202, M-302, M-701, M-801,
 P-202, P-601, P-701, P-901, E-402, E-501, E-602 DO NOT
 SHOW AS DIGITALLY SIGNED IN ADOBE READER -
  
 SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED BY THE ENGINEER OR
 ARCHITECT TO BE USED IN ELECTRONIC PLAN REVIEW. (A
 CERTIFICATE-BASED DIGITAL SIGNATURE (OFTEN JUST CALLED
 A DIGITAL SIGNATURE) IS A SPECIFIC TYPE OF
 E-SIGNATURE).- OR - IF YOUR ARCHITECT OR ENGINEER DOES
 NOT HAVE AN ELECTRONIC OR DIGITAL SIGNATURE - YOU CAN
 DROP OFF THE ORIGINAL SIGNED AND SEALED
 DRAWINGS/DOCUMENTS TO THE FRONT DESK IN THE BUILDING
 DIVISION AT THE CITY HALL.
  
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-10-25 Cont ID  
Sent By mpeterso Date 2021-10-25 Time 12:27 Rev Time 0.00
Received By rmcphers Date 2021-10-25 Time 12:52 Sent To  
Notes
2021-10-25 12:27:55REVIEW OF SIGNATURE AND SEAL ON DIGITAL PLANS APPROVED

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-18 Cont ID  
Sent By aaponte Date 2021-10-18 Time 09:22 Rev Time 0.00
Received By aaponte Date 2021-10-18 Time 09:22 Sent To  
Notes
***NONE***