| 2021-10-08 10:22:28 | 2ND REVIEW FBC-2020 PLUMBING |
| | PERMIT- 21090852 |
| | 10/8/2021 |
| | CODES IN EFFECT: |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| | FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020 |
| | FBC M- FLORIDA MECHANICAL CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. PLUMBING COMMENTS FOR THE |
| | FOUNDATION PERMIT WERE EXTRACTED FROM THE 2ND REVIEW OF |
| | THE MAIN BUILDING PLANS UNDER PERMIT 21070675. THE |
| | COMMENTS ARE APPLICABLE TO BOTH PERMITS. |
| | |
| | 12) FAILED P1.1.0 SAND/OIL INTERCEPTOR (SOI-1): A) |
| | FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION INSTRUCTIONS- SECTION 1003.4.2 FBC P. |
| | PLEASE ADD THE SOI-1 TO THE SEPARATE PERMIT LIST ON |
| | SHEET G1.0.1. FAILED. C) PROVIDE SIZING CALCULATIONS IN |
| | ACCORDANCE WITH SECTION 1003.4.2.1 OR PER |
| | MANUFACTURER'S SPECIFICATIONS. IT APPEARS THAT THE |
| | SO1-1 CALCULATIONS HAVE BEEN MISLABELED AS LINT |
| | INTERCEPTOR CALCULATION. IF THAT IS THE CASE, IT ALSO |
| | APPEARS THAT THE OS-75 AT 93 GALLONS CAPACITY IS |
| | UNDERSIZED PER THE 110 GALLONS REQUIRED BY THE |
| | CALCULATIONS. |
| | |
| | 13) FAILED. P1.1.0 LINT TRAP (LI-1): A) SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS- SECTION 1003.6 FBC P. SEE COMMENT #12 |
| | REGARDING THE LINT INTERCEPTOR SIZING CALCULATIONS. |
| | PLEASE CLARIFY HOW THE LINT INTERCEPTOR WAS SIZED. |
| | |
| | 14) FAILED. P1.1.0 STORM SUMP PUMP: A) FAILED. SUBMIT |
| | MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| | INSTRUCTIONS- SECTION 1113.1 FBC P. PLEASE ADD THE SUMP |
| | PUMP COMPONENTS TO THE DEFERRED SUBMITTALS LIST ON |
| | G1.01. REVIEW COMMENT #16 NOTES BELOW. |
| | |
| | 16) FAILED. P1.1.0, C2 & C2.1: SHOW THE DRAINAGE PIPING |
| | CONNECTIONS FOR THE TRENCH DRAINS (TD-1) LOCATED AT THE |
| | BAY DOORS. IF CONNECTING TO THE CITY STORM DRAINAGE |
| | SYSTEM, REFER TO SEC. 90-203 WPB CODE OF ORDINANCES AND |
| | VERIFY THAT THE DRAINS WILL CONVEY ONLY STORM WATER |
| | INTO THE SYSTEM. PLEASE NOTE THAT IT IS UNLAWFUL FOR |
| | ANY OTHER SUBSTANCES TO DISCHARGE INTO THE SYSTEM |
| | UNLESS MEETING ONE OF THE EXCEPTIONS UNDER SEC. 90- 205 |
| | WPB. PLEASE REFER TO SEC. 90-203-205 WPB CODE OF |
| | ORDINANCES- THE PLAN SHOWS TRENCH DRAINS FROM THE |
| | GARAGE DRAINING DIRECTLY INTO THE SUMP PIT, BUT NEARBY |
| | FLOOR DRAINS DRAINING INTO THE OIL SEPARATOR. PLEASE |
| | CLARIFY WHY THE DRAINAGE FROM THE FLOOR DRAINS WOULD |
| | CONTAIN SUBSTANCES THAT REQUIRE SEPARATION AND THE |
| | TRENCH DRAINS WOULD NOT. THE EOR SHALL VERIFY THAT THE |
| | DISCHARGE FROM THE SUMP INTO THE STORM DRAIN SYSTEM |
| | WILL CONTAIN ONLY STORMWATER AND NO OTHER SUBSTANCES |
| | SUCH AS OIL, GREASE, OR CHEMICALS. PLEASE NOTE THAT AN |
| | OIL SEPARATOR MAY BE REQUIRED- SEC. 1003.4 FBC P. |
| | |
| | 17) FAILED- SEE NOTES. P1.1.0 SANITARY BACKWATER VALVE: |
| | A) FAILED. SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATIONS INSTRUCTIONS- SECTIONS 715.2- 715.4. NOT |
| | PROVIDED. PLEASE ADD THE VALVE TO THE DEFERRED |
| | SUBMITTALS LIST ON G1.01.B) FAILED. PROVIDE AN |
| | INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS |
| | 715.5 & 305.7. NOT PROVIDED. |
| | |
| | 19) FAILED. P1.1.1 GREASE INTERCEPTOR. C) FAILED. |
| | PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING- |
| | SECTION 107.2.1 WPB. NOT PROVIDED- DEFERRED UNDER |
| | SEPARATE PERMIT. D) FAILED. PLEASE NOTE ONLY FIXTURES |
| | DISCHARGING GREASE LADEN WASTE WATER SHALL FLOW INTO |
| | THE GREASE INTERCEPTOR. CLEAR WATER WASTE FROM HAND |
| | SINKS, ICE MACHINES ETC. SHALL NOT DRAIN INTO THE |
| | SYSTEM- SECTION 1003.3.1 FBC P. THE CALCULATIONS ON |
| | P5.02 SHOW BAR SINKS. PLEASE CLARIFY THE LOCATIONS OF |
| | BAR SINKS ON THE PLANS AND WHAT THEIR USES ARE- THEY |
| | ARE NOT SPECIFIED IN THE SCHEDULE. |
| | |
| | 20) FAILED. P1.1.1 SOLIDS INTERCEPTOR S1-1: A) FAILED. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED. THE |
| | RESPONSE NARRATIVE INDICATES THE S1-1 SPECS LOCATED AT |
| | DETAIL 2 ON SHEET P5.02 HOWEVER DETAIL 2 IS THE STORM |
| | SUMP PUMP DETAIL. B) FAILED. PROVIDE SIZING |
| | CALCULATIONS- 1003.3.4. NOT PROVIDED. C) FAILED. |
| | PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING- |
| | SECTION 107.2.1 WPB. |
| | |
| | 21) FAILED. P1.1.1 SAMPLING PORT (SP-1): A) FAILED. |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTION 1003.3.2 FBC P. NOT PROVIDED- |
| | PLEASE ADD TO THE DEFERRED SUBMITTALS LIST. B) FAILED. |
| | PROVIDE AN ENLARGED SITE-SPECIFIC PIPING DRAWING- |
| | SECTION 107.2.1 WPB. NOT PROVIDED- PLEASE ADD TO THE |
| | DEFERRED SUBMITTALS LIST. |
| | |
| | 22) FAILED. P1.1.1: PROVIDE NOTES AT THE TERMINATION |
| | LOCATIONS OF THE GREASE WASTE AND SANITARY SEWER LINES |
| | OR SHOW THE POINTS OF CONNECTIONS TO THE SEWER LINE- |
| | SECTION 107.2.1 WPB. SHEET C3.1 SHOWS A SEWER |
| | CONNECTION AT THE LIFT STATION FOR THE STORM DRAINAGE- |
| | PLEASE CORRECT. |
| | |
| | 23) FAILED. P1.1.1 STORM WATER BACKWATER VALVE: A) |
| | SUBMIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATIONS |
| | INSTRUCTIONS- SECTIONS 715.2- 715.4. B) PROVIDE AN |
| | INSTALLATION DETAIL AND SUBMIT MANUFACTURER'S |
| | SPECIFICATIONS FOR THE VALVE BOX AND COVER SECTIONS |
| | 715.5 & 305.7. NOT PROVIDED. PLEASE ADD TO THE DEFERRED |
| | SUBMITTALS LIST. |
| | |
| | 26) FAILED. P4.01, P7.02: THE GW FIXTURE DRAIN FROM THE |
| | MOP SINK IS SHOWN TO BE CONNECTING TO THE SANITARY |
| | DRAIN- SECTION 1003.3.1 FBC P. THE GREASE WASTE |
| | ISOMETRIC IS MISSING FROM THE DRAWINGS. |
| | |
| | 27) FAILED. P4.01, P4.02, P7.01, P7.02, K7, K8, & K9: |
| | CLEAR WATER WASTE DRAINAGE FROM HAND SINKS AND WASTE |
| | RECEPTORS AT ICE BIN AND ICE MAKER LOCATIONS ARE SHOWN |
| | DISCHARGING INTO THE GW LINE WHICH IS PROHIBITED- |
| | SECTION 1003.3.1 FBC P. THE GREASE WASTE ISOMETRIC IS |
| | MISSING FROM THE DRAWINGS. |
| | |
| | 28) FAILED. P4.01 & K7: CONDENSATE FROM THE WALK-IN BOX |
| | EVAPORATORS SHALL NOT DRAIN INTO THE CITY SANITARY |
| | SYSTEM- SEC. 90-126 WPB CODE OF ORDINANCES. REFER TO |
| | SHEETS P.401 & P.702 AND CLARIFY HOW THE CONDENSATE |
| | WILL BE DISPOSED OF. SHOW THE CONDENSATE LINES FROM THE |
| | EVAPORATORS AND DISCHARGE LOCATIONS. IT APPEARS THAT |
| | HUB DRAINS CANNOT BE USED BECAUSE THEY MAY BE CONVEYING |
| | OTHER WASTE AND NOT JUST CONDENSATE. PLEASE NOTE THAT |
| | P.4021 SHOWS THE HUB DRAINS CONNECTING TO THE STORM, |
| | AND P.702 SHOWS CONNECTION TO THE SANITARY. |
| | |
| | 32) FAILED. P7.02: TD-2 AND SH-2 IN THE MEN'S BATHROOM |
| | DO NOT APPEAR TO BE VENTED PROPERLY. PLEASE CLARIFY HOW |
| | THE FIXTURES ARE BEING VENTED- SECTION 901.2.1 FBC P. |
| | A) RELOCATE THE 2-INCH VENT FOR BETWEEN THE TWO L2 |
| | DRAIN CONNECTIONS- SECTION 912.2.1 FBC P. B) PROVIDE AN |
| | INDIVIDAUL VENT FOR SH-2- SECTION 910.1 FBC P. C) |
| | RELOCATE THE SH-1 SHOWER VENT TO A LOCATION BETWEEN THE |
| | TWO MOST UPSTREAM FIXTURES CONNECTING TO THE HORIZONTAL |
| | BRANCH- SECTION 912.2.1 FBC P. |
| | |
| | 33) FAILED. P7.01 & P7.02: INDICATE HOW TRAP SEAL |
| | PROTECTION WILL BE PROVIDED FOR FLOOR DRAINS AND OTHER |
| | TRAP SEALS SUBJECT TO EVAPORATION WILL BE PROTECTED- |
| | SECTION 1002.4.1 FBC P. THE CHIEF PLUMBING INSPECTOR |
| | FOR THE CITY OF WPB BUILDING DEPT. HAS PROHIBITED THE |
| | USE OF BARRIER-TYPE TRAP SEALS IN AREAS SUCH AS |
| | COMMERCAIL KITCHENS AND OTHER FLOOR AREAS WHERE |
| | EXCESSIVE GREASE OR OTHER SUBSTANCES AND DEBRIS WILL |
| | CAUSE THE TRAP TO FAIL. PLEASE PROVIDE AN ACCEPTABLE |
| | MEANS IN THE KITCHEN, BASEMENT AND LAUNDRY AREAS. |
| | |
| | 38) FAILED. P.7.04: PROVIDE AN ENLARGED WATER |
| | FILTRATION PIPING DETAIL SHOWING SUPPLY CONNECTION TO |
| | THE FILTER, AND SUPPLY LINES TO FIXTURES AND EQUIPMENT |
| | REQUIRING FILTRATION. PLEASE NOTE THAT BACKFLOW |
| | PREVENTERS ARE REQUIRED FOR THE WATER SUPPLY LINES IN |
| | AND OUT OF THE FILTER- SECTION 608.3 FBC P. THE |
| | REQUESTED ENLARGED FILTER PIPING PLAN NOT PROVIDED. THE |
| | ISOMETRIC DRAWING APPEARS TO SHOW THE LOCATION OF THE |
| | FILTER BUT NO SUPPLY LINES TO EQUIPMENT. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |
| | |