Plan Review Details - Permit 21090829
Plan Review Stops For Permit 21090829
Review Stop G GAS REVIEW
Rev No 4 Status P Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 12:11 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 12:11 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2021-10-23 Cont ID  
Sent By abelisle Date 2021-10-23 Time 12:35 Rev Time 0.00
Received By abelisle Date 2021-10-23 Time 12:10 Sent To  
Notes
2021-10-23 12:14:543RD REVIEW FBC-2020 GAS
 PERMIT-21090829
 10/23/2021
  
 CODES IN EFFECT:
  
 FBC P- FLORIDA PLUMBING CODE SEVENTH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE SEVENTH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE SEVENTH EDITION 2020
 FBC B- FLORIDA BUILDING CODE SEVENTH EDITION 2020
 FBC M- FLORIDA MECHANICAL CODE SEVENTH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SEVENTH
 EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE SEVENTH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SEVENTH
 EDITION 2020
  
 PLAN REVIEW RESULTS: DENIED.
  
 1. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. THE ONE SUBMITTED IT BELONGS TO
 ENGPLANS LLC, AND IT CLEARLY SAYS IT SHALL NOT BE
 REPRODUCED IN A HOLE OR PART. THE COPY OF THE TIE-DOWN
 IS NOT ACCEPTABLE. VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT.
  
 2. CLEARLY INDICATE ON THE SURVEY IF THE SHELL FOR THE
 TANK IS 18 IN. BELOW GRADE HOW FAR FROM THE DRIVEWAY
 PER THE NFPA 58 SECTION 6.8.6.1?
  
 3. THERE IS A GRILL ON THE LP SYSTEM DOWN STREAM OF THE
 GENERATOR AND NOT IN THE CALCULATION OR SHOWN ON THE
 ISOMETRIC WOULD YOU PLEASE CORRECT BY ADDING IT WITH
 THE BTU'S AND THE LOCATION PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. WOULD YOU PLEASE PROVIDE HOW LP TANK IS TIE-DOWN AND
 WHAT METHOD, IF YOU ARE USING STRAPS OR CABLE, IF CABLE
 HOW IS IT PROTECTED FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58, BELOW GROUND IT SHALL BE ANCHORED PER NFPA
 58 SEC.3-2.2.7 (H). SHOW THE DEPTH OF THE LP GAS
 CONTAINER BELOW GRADE TO COMPLY WITH NFPA 58 SEC.
 6.6.6.1.
 MAY VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY
 BE ABLE TO PROVIDE THIS DOCUMENT.
  
 5. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 6. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF
 VALVES, THE PIPE USED, DISTANCE, LINE SIZE, AND
 PRESSURE.
  
 7. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND
 GENERATOR PER THE 2020 FBC RES. SEC.G2408.1.
  
 8. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 9. THE GENERATOR SHALL BE ONE FOOT SIX INCHES (1?-6?)
 FROM THE HOUSE, FIVE (5?-0?) FROM THE PROPERTY LINE,
 EXHAUST SHALL BE TEN (10?-0?) FROM ANY OPENING UNLESS
 OTHERWISE STATED IN THE MANUFACTURES SPECIFICATION
 INSTRUCTIONS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 08:56 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 08:56 Sent To  
Notes
2021-10-22 09:01:3810/22/21 2ND LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005. THE ONE SUBMITTED IT BELONGS TO
 ENGPLANS LLC, AND IT CLEARLY SAYS IT SHALL NOT BE
 REPRODUCED IN A HOLE OR PART. THE COPY OF THE TIE-DOWN
 IS NOT ACCEPTABLE. VISIT
 HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO
 PROVIDE THIS DOCUMENT.
  
 2. WOULD YOU PLEASE SHOW ON THE SURVEY IF THE SHELL FOR
 THE TANK IS 18 IN. ABOVE GRADE, OR DOES IT REQUIRE
 VEHICULAR BARRIER PROTECTION BECAUSE IT IS BELOW GRADE
 AND HOW FAR FROM THE DRIVEWAY PER THE NFPA 58 SECTION
 6.8.6.1?
  
 3. THERE IS A GRILL ON THE LP SYSTEM DOWN STREAM OF THE
 GENERATOR AND NOT IN THE CALCULATION OR SHOWN ON THE
 ISOMETRIC WOULD YOU PLEASE CORRECT BY ADDING IT WITH
 THE BTU'S AND THE LOCATION PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 12:06 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 12:06 Sent To  
Notes
2021-09-28 12:30:1209/28/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. WOULD YOU PLEASE PROVIDE HOW LP TANK IS TIE-DOWN AND
 WHAT METHOD, IF YOU ARE USING STRAPS OR CABLE, IF CABLE
 HOW IS IT PROTECTED FOR THE LP TANK AND APPURTENANCES
 PER NFPA 58, BELOW GROUND IT SHALL BE ANCHORED PER NFPA
 58 SEC.3-2.2.7 (H). SHOW THE DEPTH OF THE LP GAS
 CONTAINER BELOW GRADE TO COMPLY WITH NFPA 58 SEC.
 6.6.6.1.
 MAY VISIT HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY
 BE ABLE TO PROVIDE THIS DOCUMENT.
  
 2. PROVIDE THE UG TANK CLEARANCE DISTANCES IN
 MEASUREMENTS TO THE HOUSE, DRIVEWAY, AND PROPERTY LINE-
 SEE TABLE 6.4.1.1 AND SECTION 6.8.6.1 NFPA 58. PLEASE
 NOTE THAT IF THE TANK IS LESS TANK 10 FT. FROM THE
 DRIVEWAY, THE SHELL FOR THE TANK SHALL BE 18 IN. ABOVE
 GRADE, AND VEHICULAR BARRIER PROTECTION WILL BE
 REQUIRED.
  
 3. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE
 WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12)
 RESIDENTIAL GAS.
  
 A. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF
 VALVES, THE PIPE USED, DISTANCE, LINE SIZE, AND
 PRESSURE.
  
 B. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON
 PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP
 CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 C. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION,
 DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 4. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP
 TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF
 THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT
 PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL
 SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND
 THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF
 VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2.
  
 5. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND
 GENERATOR PER THE 2020 FBC RES. SEC.G2408.1.
  
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA
  
 LUIS A. CRESPO
 PLUMBING PLAN EXAMINER / INSPECTOR
 EMAIL: [email protected] OFFICE: 561 805-6720
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 12:11 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 11:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-10-31 Cont ID  
Sent By lmarchan Date 2021-10-31 Time 08:35 Rev Time 0.00
Received By lmarchan Date 2021-10-19 Time 10:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 11:43 Rev Time 0.00
Received By lcrespo Date 2021-09-23 Time 09:52 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status N Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 12:11 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 12:11 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status N Date 2021-10-23 Cont ID  
Sent By abelisle Date 2021-10-23 Time 12:09 Rev Time 0.00
Received By abelisle Date 2021-10-23 Time 10:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2021-09-28 Cont ID  
Sent By lcrespo Date 2021-09-28 Time 11:43 Rev Time 0.00
Received By lcrespo Date 2021-09-28 Time 11:42 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-19 Cont ID  
Sent By lcrespo Date 2021-11-19 Time 12:10 Rev Time 0.00
Received By lcrespo Date 2021-11-19 Time 12:10 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2021-10-22 Cont ID  
Sent By lcrespo Date 2021-10-22 Time 08:50 Rev Time 0.00
Received By lcrespo Date 2021-10-22 Time 08:50 Sent To  
Notes
2021-10-22 08:50:36THE ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS
 SHALL PROVIDE AN ELECTRONIC SIGNATURE AND SEAL ON THE
 DOCUMENT- FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE
 CODE SEC. 61G15-23.005.

Review Stop Z ZONING
Rev No 1 Status P Date 2021-10-29 Cont ID  
Sent By awooten Date 2021-10-29 Time   Rev Time 0.00
Received By awooten Date 2021-10-29 Time   Sent To  
Notes
***NONE***