| Plan Review Stops For Permit 21090786 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
4 |
Status |
P |
Date |
2021-12-29 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-29 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-29 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2021-12-29 10:18:51 | UNITS 306 AND 307 MERGED INTO A SINGLE UNIT WITH THE | | | PCN OF 74434322360033060 AND THE ADDRESS OF 101 N | | | CLEMATIS ST # 307 |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
3 |
Status |
F |
Date |
2021-12-23 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-23 |
Time |
09:10 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-23 |
Time |
09:10 |
Sent To |
|
|
| Notes |
| 2021-12-23 09:22:20 | THE UNITY OF TITLE PROVIDED ARE NOT FOR THESE UNITS | | | THEY ARE FOR UNITS 404 AND 405. PLEASE PROVIDE A UNIT | | | OF TITLE FOR 306 AND 307. PLEASE CONTACT JOSE AVILA | | | 561-355-3330 AT THE PROPERTY APPRAISERS, HE IS | | | EXPECTING YOUR CALL. WHEN YOU SPEAK TO HIM PLEASE | | | REQUEST A PRELIMINARY LETTER OF THE UNIFIED PCN. ONCE | | | YOU HAVE RECEIVED THE PRELIMINARY LETTER PLEASE CONTACT | | | [email protected] OR CALL 561-805-6659 TO BE ISSUED AN | | | ADDRESS. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
F |
Date |
2021-12-01 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-01 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-01 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2021-12-01 12:08:25 | PREVIOUS COMMENTS NOT ADDRESSED:TWO UNITS 306 & 307 ARE | | | TO BE COMBINED, YOU WILL NEED TO CONTACT VINCE NOEL | | | [email protected] OR CALL 561-494-1040 TO START THE UNITY | | | OF TITLE PROCEDURE. CURRENTLY THERE ARE TWO SEPARATE | | | PCNS FOR THE TWO UNITS, A SINGLE PCN MUST BE ISSUED BY | | | THE COUNTY. ONCE YOU HAVE RECEIVED THE SINGLE PCN AFTER | | | DOING THE UNITY OF TITLE AND THEN CONTACTING THE | | | PROPERTY APPRAISERS AND ISSUED A SINGLE PROPERTY | | | CONTROL NUMBER (PCN) PLEASE CONTACT [email protected] OR | | | CALL 561-805-6659 TO BE ISSUED AN ADDRESS. |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2021-09-22 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-09-22 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-09-22 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2021-09-22 14:27:43 | TWO UNITS 306 & 307 ARE TO BE COMBINED, YOU WILL NEED | | | TO CONTACT VINCE NOEL [email protected] OR CALL | | | 561-494-1040 TO START THE UNITY OF TITLE PROCEDURE. | | | CURRENTLY THERE ARE TWO SEPARATE PCNS FOR THE TWO | | | UNITS, A SINGLE PCN MUST BE ISSUED BY THE COUNTY. ONCE | | | YOU HAVE RECEIVED THE SINGLE PCN AFTER DOING THE UNITY | | | OF TITLE AND THEN CONTACTING THE PROPERTY APPRAISERS | | | AND ISSUED A SINGLE PROPERTY CONTROL NUMBER (PCN) | | | PLEASE CONTACT [email protected] OR CALL 561-805-6659 TO | | | BE ISSUED AN ADDRESS. |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
2 |
Status |
P |
Date |
2021-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-07 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-07 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ASBESTOS |
CONFIRM RPT SENT TO PBC HEALTH |
| Rev No |
1 |
Status |
F |
Date |
2021-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-15 |
Time |
14:32 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-15 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2021-11-15 14:33:14 | PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE | | | CONTRACTOR, ON LETTERHEAD, STATING THAT THE | | | INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM | | | COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH | | | COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE | | | GIVEN TIMELY. | | | | | | ADDITIONAL INFORMATION REGARDING ASBESTOS REQUIREMENTS | | | CAN BE FOUND ON THEIR WEBSITE: | | | | | | HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE | | | S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION- | | | RENOVATION.HTML | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2021-12-23 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-23 |
Time |
07:40 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-23 |
Time |
07:40 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2021-12-22 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-22 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-22 |
Time |
08:15 |
Sent To |
|
|
| Notes |
| 2021-12-22 08:16:54 | CONDO ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) UNITY OF TITLE IS REQUIRED | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2021-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-07 |
Time |
10:30 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-07 |
Time |
10:30 |
Sent To |
|
|
| Notes |
| 2021-12-07 10:48:05 | CONDO ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) UNITY OF TITLE IS REQUIRED | | | | | | 2) ORIGINAL BUILDING DRAWINGS PERMIT NUMBER 98009083 | | | DRAWING A10.4 AND S2.10 SHOWS MEZZANINE FLOOR AS NON | | | COMBUSTIBLE (BAR JOIST, STEEL DECK AND CONCRETE). FLOOR | | | CONSTRUCTION SHOULD BE NON COMBUSTIBLE PER FBC 602.2 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2021-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-15 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-15 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2021-11-15 14:29:52 | CONDO ALTERATION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) UNITY OF TITLE IS REQUIRED | | | | | | 2) PLEASE SHOW THE BUILDING CONSTRUCTION TYPE FBC 602.1 | | | | | | 3) PLEASE SHOW THE SILL HEIGHT FOR THE 2ND FLOOR | | | WINDOWS - FBC 1015.8 | | | | | | 4) STRUCTURAL DRAWING SHOWS THE USE OF WOOD FRAMING AND | | | WOOD FLOOR DECKING - BUILDING CONSTRUCTION TYPE MAY NOT | | | ALLOW COMBUSTIBLE MATERIALS = PLEASE SEE FBC CHAPTER | | | 603 | | | | | | 5) IF FLOORING ON THE 1ST FLOOR (3RD FLOOR) IS TO BE | | | PART OF THIS PERMIT - (PLEASE SHOW THE TYPE OF FLOORING | | | ON THE DRAWINGS) THE FOLLOWING ACUSTICAL TEST REPORTS | | | ARE REQUIRED: | | | | | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST | | | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE | | | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) | | | | | | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING | | | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR | | | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS | | | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR | | | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.. | | | PROVIDE A COPY OF THE TEST REPORT. (A DROP CEILING | | | SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING ASSEMBLY | | | DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED DROP | | | CEILING DESCRIPTION) | | | | | | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN | | | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC | | | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN | | | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN | | | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH | | | ASTM E 492. PROVIDE A COPY OF THE TEST REPORT. (A DROP | | | CEILING SHOULD NOT BE INCLUDED IN THE FLOOR/CEILING | | | ASSEMBLY DESCRIPTION UNLESS THE UNIT MATCHES THE TESTED | | | DROP CEILING DESCRIPTION) | | | | | | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE | | | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 | | | OR UL 723. (DO NOT NEED THIS REPORT IF THE PADDING IS | | | ATTACHED TO THE FLOORING) | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2021-11-12 |
|
|
Cont ID |
|
| Sent By |
fgiaquin |
Date |
2021-11-12 |
Time |
19:50 |
Rev Time |
0.00 |
| Received By |
fgiaquin |
Date |
2021-11-12 |
Time |
19:06 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2021-12-02 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-12-02 |
Time |
|
Rev Time |
0.00 |
| Received By |
pleduc |
Date |
2021-12-02 |
Time |
10:17 |
Sent To |
|
|
| Notes |
| 2021-12-02 10:22:29 | FIRE PROVISO: | | | | | | ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS FOR CODE COVERAGE COMPLIANCE. | | | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER SHALL BE MAINTAINED AND REMAIN ACTIVE | | | THROUGHOUT THE CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2021-11-09 |
|
|
Cont ID |
|
| Sent By |
lmarchan |
Date |
2021-11-09 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
lmarchan |
Date |
2021-11-09 |
Time |
14:34 |
Sent To |
|
|
| Notes |
| 2021-11-09 14:34:23 | PASSED PER PLEDUC IN WRONG STOP | | | FIRE PROVISO: | | | | | | ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS | | | FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER | | | SHALL BE MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2021-12-23 |
|
|
Cont ID |
|
| Sent By |
cpuell |
Date |
2021-12-23 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
cpuell |
Date |
2021-12-23 |
Time |
08:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2021-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-07 |
Time |
10:50 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-01 |
Time |
06:55 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2021-11-15 |
|
|
Cont ID |
|
| Sent By |
pleduc |
Date |
2021-11-15 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-09-22 |
Time |
11:39 |
Sent To |
|
|
| Notes |
| 2021-09-23 13:32:19 | FIRE PROVISO: | | | | | | ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO, | | | SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS. | | | | | | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR | | | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND/OR | | | FIRE SPRINKLER SYSTEMS BY APPLICABLE LICENSED | | | CONTRACTORS | | | FOR CODE COVERAGE COMPLIANCE. | | | | | | | | | THE EXISTING LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR | | | FIRE SPRINKLER | | | SHALL BE MAINTAINED AND REMAIN ACTIVE THROUGHOUT THE | | | CONSTRUCTION PERIOD, INCLUDING DEMO. | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2021-12-06 |
|
|
Cont ID |
|
| Sent By |
lcrespo |
Date |
2021-12-06 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
lcrespo |
Date |
2021-12-06 |
Time |
08:23 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
2 |
Status |
P |
Date |
2021-12-07 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-12-07 |
Time |
10:49 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-12-07 |
Time |
10:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
SIGNATURE |
ELECTRONIC SIGNATURE SHEET |
| Rev No |
1 |
Status |
P |
Date |
2021-11-15 |
|
|
Cont ID |
|
| Sent By |
rmcphers |
Date |
2021-11-15 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcphers |
Date |
2021-11-15 |
Time |
14:33 |
Sent To |
|
|
| Notes |
|
|