| 2021-09-27 13:18:13 | 09/27/21 1ST LP GAS REVIEW**DENIED** WITH COMMENTS |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME, AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | 1. SIGNED AND SEALED DRAWING OF THE TIE-DOWN IS A COPY |
| | AND THE ORIGINAL SIGNED AND SEALED DOCUMENT. PLEASE SEE |
| | THE COMMENT ON THE SIGNATURE STOP FOR MORE INFORMATION. |
| | THE COPY OF THE TIE-DOWN IS NOT ACCEPTABLE. THE |
| | ENGINEER WHO PREPARED THE TANK TIE-DOWN DETAILS SHALL |
| | PROVIDE AN ELECTRONIC SIGNATURE AND SEAL THE DOCUMENT- |
| | FL. STATUTE 471.025 & FLORIDA ADMINISTRATIVE CODE SEC. |
| | 61G15-23.005. OR YOU MAY VISIT |
| | HTTPS://WWW.ENGINEERINGEXPRESS.COM/ THEY MAY BE ABLE TO |
| | PROVIDE THIS DOCUMENT. |
| | |
| | 2. THERE IS NO GENERATOR PERMIT OR APPLICATION FOR THE |
| | ADDRESS ON THE CITY RECORDS. A LICENSED CONTRACTOR IS |
| | REQUIRED FOR AN ELECTRICAL PERMIT ON THE GENERATOR PER |
| | THE WPB AMENDMENTS TO THE FBC SEC. 105.1. |
| | |
| | 3. WOULD YOU PLEASE PROVIDE A GAS RISER DIAGRAM PER THE |
| | WPB AMENDMENTS TO THE FBC SEC. 107.3.5.3 (12) |
| | RESIDENTIAL GAS; |
| | |
| | A. SHOW AND LABEL TANK, REGULATORS, UNIONS, SHUT-OFF |
| | VALVES, THE PIPE BEING USED, DISTANCE, LINE SIZE, AND |
| | PRESSURE. |
| | |
| | B. THE PHYSICAL ADDRESS OF THE RESIDENCE MUST BE ON |
| | PLANS IN FULL, NUMBER, STREET, CITY, STATE, AND ZIP |
| | CODE PER THE WPB AMENDMENTS TO THE FBC SEC.107.2.1 |
| | INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | C. PLEASE PROVIDE THE SIGNATURE OF ALL INFORMATION, |
| | DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING DATA THAT |
| | SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN PER THE WPB AMENDMENTS TO |
| | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 4. CLEARLY SHOW THE LOCATION AND CAPACITY OF LP |
| | TANK(S), TYPE OF TANK (DOT OR ASME), THE DISTANCE OF |
| | THE TANK FROM THE EXTERIOR BUILDING WALL AND ADJACENT |
| | PROPERTY LINES, THE DISTANCE OF THE TANK FROM ALL |
| | SOURCES OF IGNITION, OTHER CONTAINERS, BUILDINGS, AND |
| | THE LOCATION OF ANY BUILDING OPENINGS BELOW THE RELIEF |
| | VALVE OF THE TANK PER THE NFPA 58, TABLE 3-2.2.2. |
| | |
| | 5. A CATHODIC PROTECTION SYSTEM SHALL BE REQUIRED PER |
| | NFPA 58 SECS. 5.2.1.11, 6.6.6.1 (I) SHALL BE MONITORED |
| | PER THE NFPA 58 SEC.6.6.6.1 (J). SUBMIT DETAILS ON THE |
| | TYPE OF CATHODIC PROTECTION, SIZE (LBS.) & THE NUMBER |
| | OF MAGNESIUM BAG(S), SIZE & TYPE OF ANODE CABLE AMOUNT |
| | OF WATER TO ACTIVATE IT. |
| | |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION & |
| | REMOVE ANY VOIDED SHEETS & REPLACE ANY NECESSARY PAGES. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND, WILL HELP EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | HTTPS://CODES.ICCSAFE.ORG/CODES/FLORIDA |
| | |
| | LUIS A. CRESPO |
| | PLUMBING PLAN EXAMINER / INSPECTOR |
| | EMAIL: [email protected] OFFICE: 561 805-6720 |
| | |