Plan Review Details - Permit 21090540
Plan Review Stops For Permit 21090540
Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 2 Status P Date 2021-11-01 Cont ID  
Sent By jwitmer Date 2021-11-01 Time 13:11 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop ASBESTOS CONFIRM RPT SENT TO PBC HEALTH
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 09:47 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-06 09:47:17PALM BEACH COUNTY HEALTH DEPARTMENT NEEDS VERIFICATION
 THE CONTRACTORS ARE AWARE OF THIS FL. STATE STATUTE.
 PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT FROM THE
 CONTRACTOR, ON LETTERHEAD, STATING THAT THE
 INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM
 COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH
 COUNTY WILL BE FOLLOWED, AND THAT NOTIFICATION WILL BE
 GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS
 REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE:
  
 HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE
 S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/ASBESTOS-DEMOLITION-
 RENOVATION.HTML
  
 THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO
 [email protected]. THE INFORMATION SHOULD BE IN
 PDF FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE
 INCLUDE THE PERMIT NUMBER AND "ASBESTOS" IN THE SUBJECT
 LINE.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By pvalenti Date 2021-12-06 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2021-12-06 Time 10:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 08:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-30 08:45:21WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090540
 ADD: 701 S OLIVE AVE # 910
 CONT: PERSAL PROPERTY IMPROVEM
 TEL: 954-709-7815
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: TUES. NOV. 301/ 2021
 ACTION: DENIED
  
 1) NEW COMMENT, PROFLEX LV200 FOR LUXURY VINYL PLANK
 WAS SUBMITTED AND MEETS ALL TESTING REQUIREMENTS, BUT
 THE ARCHITECT IS STILL STATING THE SOUNDPROOFING IS TO
 BE ECO-ULTRA QUIET AS THE UNDERLAYMENT, BOTH THE
 PRODUCT TESTING AND THE REQUIREMENT FROM THE ARCHITECT
 NEED TO MATCH. IT WOULD APPEAR THE ARCHITECT NEEDS TO
 UPDATE THE PLANS. FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC.
  
 2) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2021-11-01 Cont ID  
Sent By jwitmer Date 2021-11-01 Time 13:12 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2021-11-01 13:12:42WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090540
 ADD: 701 S OLIVE AVE # 910
 CONT: PERSAL PROPERTY IMPROVEM
 TEL: 954-709-7815
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: MON. NOV. 01/ 2021
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) 2ND REQUEST, SEMI-COMPLIED. THIS REVIEW THE FINISH
 FLOOR WAS IDENTIFIED AS OPTIMA ECO RESILIENT FLOORING
 OR VINYL FLOORING. THIS REVIEW A TECHNICAL SHEET WAS
 SUBMITTED FOR PROFLEX SUPER SIM-90. WE HAVE TEST
 REPORTS FOR THE USE OF PROFLEX SUPERSIM 90 ONLY FOR
 MARBLE/ TILE, NOT FOR VINYL FLOORING.
 1ST ROUND COMMENTS. THE SCOPE OF WORK INDICATES
 ECO-ULTRA QUIET UNDERLAYMENT BUT DOES NOT STATE WHAT
 TYPE OF FINISH FLOOR IS TO BE INSTALLED ON TOP OF THE
 UNDERLAYMENT. THIS NEEDS TO BE KNOWN SINCE THE
 UNDERLAYMENT HAS NOT BEEN TESTED FOR ALL FLOOR
 FINISHES. FLOOR INSULATION/ UNDERLAYMENT (FBC-B 2020)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) 2ND REQUEST. FBC-B 2020 1207.3 STRUCTURE-BORNE
 SOUND. FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS
 OR BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) 2ND REQUEST. FBC-B 2020 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 3C) 2ND REQUEST. FLAME SPREAD- FBC-B 2020 603.1.
 EXCEPTION 2. INSULATION INSTALLED BETWEEN A FINISHED
 FLOOR AND SOLID DECKING WITHOUT INTERVENING AIRSPACE
 SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 09:46 Rev Time  
Received By jwitmer Date   Time   Sent To  
Notes
2021-10-06 09:46:34WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 21090540
 ADD: 701 S OLIVE AVE # 910
 CONT: PERSAL PROPERTY IMPROVEM
 TEL: 954-709-7815
 E-MAIL: [email protected]
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: WED. OCT. 06TH/ 2021
 ACTION: DENIED
 1) SHEET 001 A, DE, RC THE NEW FLOOR PLAN UNDER THE
 DESCRIPTION OF WORK LIST THE ALTERATION LEVEL AS
 LEVEL-1. PLEASE REVIEW THE 2020 EXISTING BUILDING CODE
 SECTION 504.1 LEVEL 2 ALTERATIONS INCLUDE THE
 RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION
 OF ANY DOORS AND WINDOWS, THE RECONFIGURATION OR
 EXTENSION OF ANY SYSTEM, OR INSTALLATION OF ANY
 ADDITIONAL EQUIPMENT. WITH THE RELOCATION OF KITCHEN
 EQUIPMENT, STOVE, DISH WASHER AND SINK, IN THE MASTER
 BATH THE RELOCATION OF THE WATER CLOSET, ELIMINATION OF
 SHOWER AND RELOCATION OF THE WATER CLOSET, THIS IS A
 LEVEL 2 ALTERATION. PLEASE UPDATE.
  
 2) PLEASE NOTE THIS BUILDING WAS BUILT UNDER THE FAIR
 HOUSING GUIDELINES. . FAIR HOUSING ACT DESIGN AND
 CONSTRUCTION REQUIREMENTS. FOR PURPOSES OF THIS
 SECTION, A COVERED MULTIFAMILY DWELLING SHALL BE DEEMED
 TO BE DESIGNED AND CONSTRUCTED FOR FIRST OCCUPANCY ON
 OR BEFORE MARCH 13, 1991, IF THEY ARE OCCUPIED BY THAT
 DATE OR IF THE LAST BUILDING PERMIT OR RENEWAL THEREOF
 FOR THE COVERED MULTIFAMILY DWELLINGS IS ISSUED BY A
 STATE, COUNTY OR LOCAL GOVERNMENT ON OR BEFORE JANUARY
 13, 1990.
  
 THE FAIR HOUSING ACT MANUAL REVISED APRIL 1998 PAGE
 7.7. THE GUIDELINES REQUIRE A CLEARANCE OF AT LEAST 40
 INCHES BETWEEN ALL OPPOSING BASE CABINETS, COUNTERTOPS,
 APPLIANCES AND WALLS. PAGE 7.8 DETAILS OF KITCHEN WITH
 ISLAND IN THE CENTER OF A KITCHEN 40 INCHES MUST BE
 MAINTAINED BETWEEN THE ISLAND AND ALL OPPOSING
 FEATURES. THE ALTERNATIVE IS A NOTARIZED LETTER FOR
 FAIR HOUSING:
  
 FAIR HOUSING LETTER AS AN ALTERNATE METHOD. SEE LETTER:
 PROJECT ADDRESS: ______________________________________
 _____________________
 PERMIT NUMBER: ________________________
 THE OWNER AND DESIGNER OF RECORD ACKNOWLEDGE THAT THE
 PROPOSED KITCHEN DESIGN DOES NOT MEET THE REQUIREMENTS
 OF THE FAIR HOUSING ACCESSIBILITY GUIDELINES. THE OWNER
 AGREES TO REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF
 SALE IF SO, REQUESTED BY THE BUYER.
  
 SIGNATURE OF DESIGNER: ______________________________
 PRINTED NAME OF DESIGNER: ___________________________
  
 SIGNATURE OF OWNER: ________________________________
 PRINTED NAME OF OWNER: _____________________________
 NOTARY FOR OWNER?S SIGNATURE:
 STATE OF FLORIDA, COUNTY OF PALM BEACH
 THE FOREGOING INSTRUMENT WAS ACKNOWLEDGED BEFORE ME
 THIS _____ DAY OF ________, 20__ BY
 ___________________________ WHO IS PERSONALLY KNOWN TO
 ME OR WHO HAS PRODUCED: ___________________________ AS
 IDENTIFICATION AND WHO DID / DID NOT TAKE AN OATH.
 NOTARY SIGNATURE ___________________________________
 NOTARY PRINTED NAME ________________________________
  
 3) THE SCOPE OF WORK INDICATES ECO-ULTRA QUIET
 UNDERLAYMENT BUT DOES NOT STATE WHAT TYPE OF FINISH
 FLOOR IS TO BE INSTALLED ON TOP OF THE UNDERLAYMENT.
 THIS NEEDS TO BE KNOWN SINCE THE UNDERLAYMENT HAS NOT
 BEEN TESTED FOR ALL FLOOR FINISHES. FLOOR INSULATION/
 UNDERLAYMENT (FBC-B 2020) FOR TILE, STONE, MARBLE,
 VINYL AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING:
 PLEASE PROVIDE ALL THREE TEST REPORTS FOR TYPE I AND OR
 TYPE II BUILDINGS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2020 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E-492.
  
 3B) FBC-B 2020 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2020 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 LVT & LPT LUXURY VINYL TILE. FLOOR FINISH
 CLASSIFICATION AS REQUIRED IN SECTION 804.2
 CLASSIFICATION AND 804.3 TESTING AND IDENTIFICATION OF
 THE 2020 FBC-B.
  
 4) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
  
  
 MONDAY AUGUST 02ND/ 2021 ALL PLANS EXAMINERS WILL BE
 WORKING FROM CITY HALL.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ RETIRED.
  
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 16:26 Rev Time 0.00
Received By jleahy Date 2021-11-03 Time 16:24 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2021-10-02 Cont ID  
Sent By jleahy Date 2021-10-02 Time 09:49 Rev Time 0.00
Received By jleahy Date 2021-10-02 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By pleduc Date 2021-12-06 Time   Rev Time 0.00
Received By pleduc Date 2021-12-06 Time 10:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2021-11-23 Cont ID  
Sent By pleduc Date 2021-11-23 Time   Rev Time 0.00
Received By pleduc Date 2021-11-23 Time 10:24 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2021-11-03 Cont ID  
Sent By pleduc Date 2021-11-03 Time   Rev Time 0.00
Received By pleduc Date 2021-11-03 Time 10:10 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2021-09-23 Cont ID  
Sent By pleduc Date 2021-09-23 Time   Rev Time 0.00
Received By pleduc Date 2021-09-23 Time 10:27 Sent To  
Notes
2021-09-23 10:43:04THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS AN INDICATION OF REPLACING THE FLOORING
 HOWEVER THERE ARE NO SPEC SHEET FOR THE FLOOR
 UNDERLAYMENT, NOR ACTUAL PROPOSED FLOORING.
  
 TILE FLOORING COULD HAVE DIFFERENT MEANINGS AND IF NOT
 CERAMIC/PORCELAIN/MARBLE/CEMENT IT CAN BE
 VINYL/LAMINATE ETC AND IS MANUFACTURED
 AROUND THE WORLD AND NOT ALL ARE TESTED AND MEETING
 LISTED AND NFPA STANDARDS.
  
 FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE SPECIFIC
 FLOORING TYPE AND/OR PRODUCT SPEC SHEETS OF THE
 PROPOSED FINISHED FLOORING INDICATING THE FIRE BEHAVIOR
 RATING.
  
  
 2) THE FLOOR PLAN SUBMITTED INDICATES THE LOCATION OF
 THE BATHROOM & KITCHEN THAT APPEAR TO BE LOCATED ALONG
 A
 FIRE RATED TENANT AND/OR CORRIDOR SEPARATION WALL
 REQUIRING MAINTENANCE/REPAIR OF THE FIRE RATED WALL
 SHOULD THE DEMO DAMAGE THAT WALL.
  
 PLEASE REVIEW, ENSURE WALL FIRE RATING IS NOT
 COMPROMISED AND PROVIDE A NOTE OF ACKNOWLEDGEMENT ON
 THE FLOOR PLAN.
  
  
  
 3) PROTECT FIRE SPRINKLERS AND FIRE ALARM DEVICES AND
 EQUIPMENT.
  
 DO NOT PAINT OVER SPRINKLER HEADS AND/OR FIRE ALARM
 DEVICES/EQUIPMENT.
  
 THE FS AND FA SYSTEMS SHALL BE MAINTAINED THROUGHOUT
 DEMO AND CONSTRUCTION.
  
 ALL FIRE SPRINKLER & FIRE ALARM WORK. INCLUDING DEMO,
 SHALL BE DONE UNDER SEPARATE PERMITS & SHOP DRAWINGS.
  
  
 PLEASE REVIEW, ENSURE COMPLIANCE AND PROVIDE A NOTE OF
 ACKNOWLEDGEMENT ON THE FLOOR PLAN.
  
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2021-12-06 Cont ID  
Sent By pvalenti Date 2021-12-06 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2021-12-03 Time 08:22 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date   Cont ID  
Sent By   Date 2021-11-30 Time   Rev Time 0.00
Received By aoliver Date 2021-11-22 Time 07:29 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 16:27 Rev Time 0.00
Received By jleahy Date 2021-10-29 Time 12:43 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2021-10-06 Cont ID  
Sent By jwitmer Date 2021-10-06 Time 09:47 Rev Time 0.00
Received By jwitmer Date 2021-09-22 Time 09:05 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 14:02 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 14:02 Sent To  
Notes
2021-09-23 14:02:52NO MECHANICAL WORK SHOWN ON THE DRAWINGS FOR THIS
 PROJECT. ME

Review Stop P PLUMBING
Rev No 2 Status P Date 2021-11-02 Cont ID  
Sent By ccole Date 2021-11-02 Time 10:11 Rev Time 0.00
Received By ccole Date 2021-11-02 Time 09:58 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2021-09-29 Cont ID  
Sent By ccole Date 2021-09-29 Time 15:29 Rev Time 0.00
Received By ccole Date 2021-09-29 Time 14:09 Sent To  
Notes
2021-09-29 15:33:121ST REVIEW FBC-2020 PLUMBING
 PERMIT- 21090540
 9/28/2021
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) FAIR HOUSING ACT COMPLIANCE: THE CONDOMINIUMS AT TWO
 CITY PLAZA- 701 S. OLIVE AVE. WERE DESIGNED AND
 CONSTRUCTED IN COMPLIANCE THE FAIR HOUSING ACT DESIGN
 MANUAL. THE PROPOSED ALTERATIONS TO THE KITCHEN AND
 BATHROOM IN UNIT 910 SHALL ALSO BE IN COMPLIANCE.
 PLEASE PROVIDE CODE DATA INFORMATION ON SHEET 1 THAT
 INCLUDES COMPLIANCE WITH THE FAIR HOUSING ACT DESIGN
 MANUAL AND THE CURRENT FLORIDA BUILDING CODES- 2020 7TH
 EDITION. THE FAIR HOUSING ACCESSIBILITY GUIDELINES ARE
 INCLUDED IN THE FLORIDA ACCESSIBILITY CODE- 2020 7TH
 EDITION AND THE FAIR HOUSING DESIGN ACT MANUAL.
  
 A) SHEET 1 & 2: THE DESIGN PROFESSIONAL OF RECORD SHALL
 INDICATE ON THE PLAN WHICH OF THE TWO BATHROOM TYPES IS
 THE BASIS OF DESIGN- SPECIFICATION TYPE A OR B ON THE
 PLANS. PLEASE REFER TO PAGES 7.34- 7.39 OF THE DESIGN
 MANUAL FOR EXPLANATORY INFORMATION ON SPECIFICATION A &
 B AND SHOW COMPLIANCE.
 B) SHEET 1 & 2: REFER TO CHAPTER 7 (REQUIREMENT 7
 USABLE KITCHENS & USABLE BATHROOMS) AND PROVIDE
 ENLARGED BATHROOM AND KITCHEN DRAWINGS AND DETAILS.
 BASED ON THE DESIGN SPECIFICATIONS PLEASE PROVIDE
 DETAILS AND NOTES IN COMPLINACE WITH THE CODE SECTIONS
 LISTED BELOW.
 PAGES 7.1- 7.6 CLEAR FLOOR SPACES FOR SINKS AND
 APPLIANCES
 PAGES 7.7- 7.11 CLEARANCES BETWEEN KITCHEN COUNTERS AND
 ALL OPPOSING ELEMENTS.
 PAGES 7.12- 7.16 REMOVABLE SINK AND APPLIANCE CABINET
 DOORS INCLUDING KNEE SPACES.
 PAGES 7.40-7.46 WATER CLOSET CLEAR FLOOR SPACES.
 PAGES 7.47- 7.52: LAVATORY AND VANITY CLEAR FLOOR AND
 KNEE AND TOE CLEARANCES.
 PAGES 7.53- 7.55: BATHTUB CLEAR FLOOR SPACE AND CONTROL
 LOCATIONS
 C) SHEET 1 & 2: REFER TO CHAPTER 6 (REINFORCED WALLS
 FOR GRAB BARS). BASED ON CHAPTER 7 COMPLIANCES LISTED
 ABOVE, PLEASE PROVIDE DRAWINGS AND DETAILS SHOWING GRAB
 BAR REINFORCEMENT LOCATIONS AND INSTALLATION DETAILS.
 PAGES 6.3- 6.8- WATER CLOSETS
 PAGES 6.8- 6.11 BATHTUBS
 PAGES 6.14- 6.16 REINFORCEMENT METHODS
  
 PLEASE NOTE: AS AN ALTERNATIVE TO MEETING THE
 GUIDELINES FOR THE BATH ALTERATIONS, THE OWNER AND
 DESIGNER OF RECORD FOR THE PROPOSED PROJECT MAY PROVIDE
 A SIGNED AND NOTARIZED AFFIDAVIT WHICH WOULD INDICATE
 ACKNOWLEDGEMENT THAT THE PROPOSED DESIGN DOES NOT MEET
 THE REQUIREMENTS OF THE FAIR HOUSING ACCESSIBILITY
 GUIDELINES, BUT WILL ALSO REQUIRE THE OWNER TO AGREE TO
 REVERT THE UNIT BACK TO COMPLIANCE AT TIME OF SALE IF
 REQUESTED BY THE BUYER. IF THIS OPTION IS CHOSEN,
 PLEASE SEND AN EMAIL TO [email protected] AND I WILL SEND A
 COPY OF THE FAIR HOUSING AFFIDAVIT.
  
 2) SHEET 2: SHOW THE WATER LINE RUN TO THE REFRIGERATOR
 ICE MAKER, AND INDICATE A WATER HAMMER ARRESTOR AND
 BACKFLOW PREVENTER WILL BE INSTALLED- SECTION 604.9 &
 608.3 FBC P.
  
 3) SHEET 2: PLEASE REMOVE THE BROWARD COUNTY AMENDMENTS
 REFERENCE SHOWN BELOW THE PLUMBING NOTES- SECTION
 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 4 Status P Date 2021-12-06 Cont ID  
Sent By pvalenti Date 2021-12-06 Time 10:44 Rev Time 0.00
Received By pvalenti Date 2021-12-06 Time 10:13 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status P Date 2021-11-30 Cont ID  
Sent By jwitmer Date 2021-11-30 Time 08:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status P Date 2021-11-03 Cont ID  
Sent By jleahy Date 2021-11-03 Time 16:26 Rev Time 0.00
Received By jleahy Date 2021-11-03 Time 16:26 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2021-09-23 Cont ID  
Sent By medwards Date 2021-09-23 Time 14:03 Rev Time 0.00
Received By medwards Date 2021-09-23 Time 14:03 Sent To  
Notes
***NONE***


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved